6075-900, B.2 – FlexSmart™ 607X Series Installation Guide 

 

The following are recommended cable types and maximum cable lengths for a cable connecting the power supply 
to the reader.

 

Cable Type 

Maximum Cable Length 

24 AWG (0.60mm), three conductors, with an overall foil shield, 9533 or 
equivalent. 

200’ (61 m) 

22 AWG (0.80mm), two conductors, with an overall foil shield, Alpha 5192 
or equivalent. 

300’ (91 m) 

18 AWG (1.20mm), two conductors, with an overall foil shield, 5836 or 
equivalent.  

500’ (152 m) 

The following are recommended wiring types at various maximum distances. Variations in distances 
require different wire gauges, because of system data termination differences. Contact your system 
manufacturer for its exact requirements. Installation should be in accordance with National Electric Code 
ANSI/NFPA 70. 

Cable Type 

Maximum Cable Length 

22 AWG (0.80mm), six or eight conductor, with an overall foil shield, Alpha 
5196, 5198 or equivalent.  

500’(152 m) 

18 AWG (1.20mm), six or eight conductor, with an overall foil shield, Alpha 
5386, 5388 or equivalent. 

500’ (152m) 

3.2

 

Grounding 

Connect the reader directly to an earth ground (an earth ground can be established by driving a copper 
clad ground rod into the earth). Make certain the DC resistance between your established earth ground 
and the system ground is 50 Ohms or less. If a direct connection to a ground rod is not possible, connect 
the reader to an earth grounded cold water metal pipe 

(do not connect to a copper fire sprinkler system 

because it may have non-conductive couplings) 

or steel frames 

(building beams)

 that connect to earth. 

Connection of the shield/drain to an earth ground will provide greater ESD protection of the reader.  

Prevent ground loops by connecting both the cable shield and the negative line of the power supply to one 
common earth ground point. Connecting different points to separate earth grounds may result in a ground 
loop.  

Note: 

For the heavy duty keypad readers, the Shield/drain wire should be floating at the power supply. 

Note: 

Ground loops may cause poor read range and communication line interference, resulting in no code 

or improper code seen by the controller. 

Reader Defaults 

 

Reader Wiring 

 

Card read (LED, beep & backlight) 

 

Red 

+12Vdc 

One-line control (bi-colour LED) 

 

Black 

0Vdc 

Keypad Defaults 

 

Green 

Data 0/Strobe 

Key-press (LED, beep & backlight) 

 

White 

Data 1/Data 

1 0001 

2 0010 

3 0011 

 

Brown 

LED Control 

4 0100 

5 0101 

6 0110 

 

Blue 

Beeper Control 

7 0111 

8 1000 

9 1001 

 

Orange 

Not Used 

Θ

1010 

0 0000 

# 1011 

 

Shield/drain 

Door controller earth ground 

 

Page 6 of 8 

 

February 5, 2007 

© 2007 HID Global Corporation.  All rights reserved. 

 

Summary of Contents for FlexSmart 607 Series

Page 1: ...292 Jeronimo Road Irvine CA 92618 1905 HID FlexSmart 607X Series Readers INSTALLATION GUIDE 2007 HID Global Corporation All rights reserved February 5 2006 Document Number 6075 900 Document Version B...

Page 2: ...tents 1 Overview 3 2 Mounting 4 3 Wiring 5 Regulatory 7 Models 7 Contact 8 List of Figures Figure 1 Reader Dimensions and Mounting 4 Figure 2 Keypad Reader Dimensions and Mounting 5 Page 2 of 8 Februa...

Page 3: ...with FlexSmart readers 1 Installation Guide 2 MIFARE reader module for Slim or Wall switch 3 Cover Bezel reader only 1 3 Specifications Supply Voltage 9VDC to 16VDC Supply Current 15 75mA Keypad 25 1...

Page 4: ...ing the Reader Format The reader format is found on the ID label see below which is located on the reader electronics module Reader Format 2 Mounting Figure 1 Reader Dimensions and Mounting Page 4 of...

Page 5: ...le to the controller 4 Using the two 6 32 or M 3 screws attach the reader to the first two mounting holes 5 Once the reader module is screwed in place snap on the bezel 3 Wiring 3 1 Cable Types and Ma...

Page 6: ...ke certain the DC resistance between your established earth ground and the system ground is 50 Ohms or less If a direct connection to a ground rod is not possible connect the reader to an earth ground...

Page 7: ...rference received including interference that may cause undesired operation Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to o...

Page 8: ...90 Europe Middle East and Africa HID Corporation Ltd Haverhill UK email eusupport hidcorp com main 44 0 1440 714 850 support 44 0 1440 711 822 fax number 44 0 1440 714 840 Asia Pacific HID Asia Pacifi...

Reviews: