19. Install each drive in the same way the first was installed. Make sure to follow the drive layout shown in
the following image.
Figure 31: Drive Layout
20. Now that the drives are installed into the chassis, test the installation by sliding the enclosure in and out
of the rack a minimum of three times. If the enclosure binds, catches, or displays any incorrect motion
or behavior retry the installation of the drives and chassis.
21. If the chassis is being installed into a rack that will be shipped fully assembled, you must install eight
(four per side) of the included M5 x 10mm T15 Torx screws into the two brackets at the front of the chassis
in the following locations. These screws should be tightened to 3.38-3.61 Nm / 30-32 in-lbf using a Long
50
5
Installation
Installation Guide
5.2
Ultrastar 8 Installation Procedure