33
498-1060
GB
SKD100
07. USING THE GENERATOR
07.4 STOPPING THE ENGINE
(picture 3)
• Disconnect the loads. The engine slows down
automatically
• Let the engine run in this condition for about one
minute, then turn the key switch
(5)
to position “OFF”.
07.5 USING THE POWER GENERATOR UNIT
The unit is equipped with an earth leakage circuit
breaker
(1)
capable of ensuring user protection in case
of accidental contact with live parts or failure of the
insulation system of connected users.
Press the test button T every month: the earth leakage
circuit breaker should trip and de-energise the sockets.
If this would not be the case, then it is advisable not to
use the unit and immediately seek technical advice.
Earth leakage circuit breaker (picture 2)
Apply only to authorised manufacturer
centres for technical service on electrical
components.
• Before connecting a load to sockets on the front
panel of the unit, make sure that the generator
supplies enough power for the tools that are
connected.
Beware: electric motors’ starting current
requirements are considerably higher
than rated full load values.
• Before connecting a load to single phase sockets,
make sure that the circuit breakers are open.
• At the end of work, before removing plugs from panel
sockets, open the circuit breakers.
• Connect loads to generator’s sockets only by using
cables of suitable size and in good conditions, with
plugs fitted for the sockets on the panel. Do not use
adapters.
• In order to achieve full output for AMF functionality
both 230V sockets will be required.
AUTO mode (picture 2 SKD100-IR version
only)
After checking and restoring if necessary the engine oil
level, and fuelling the unit, (if this is the first starting, it is
necessary to fuel the unit until the fuel gauge (2) on the
front panel is above the 50% of fuel capacity), proceed as
follows:
• Make sure that no load is connected to the unit.
• Make the switch
(3)
in “AUTO” position.
• Connect the AMF panel to the machine using the
connector
(4)
.
• If the Mains is switched on, the AMF panel controls
the mains circuit breaker closing, the load is fed by
the mains and the unit will stay in stand-by. When
the mains is switched off, the AMF panel controls the
mains circuit breaker opening and the starting proce-
dure of the unit.
• After a suitable heating of the unit, the AMF panel
controls the unit circuit breaker closing. At this time,
the load is fed by the generator. At the mains return,
the AMF panel controls the unit circuit breaker open-
ing, the mains circuit breaker closing and the engine
stop occurs after the heating time.
pic. 2
4
1
2
3
pic.2
1
pic. 3
Summary of Contents for SKD100-I
Page 3: ...SKD100 I 3000 RPM Diesel Generator...
Page 4: ......
Page 26: ...26 GB SKD100 498 1060 05 TECHNICAL DATA Trolley mounted unit 900 mm 979 mm 1746 mm...
Page 37: ...37 498 1060 GB SKD100 9 GENERATOR MAINTENANCE 09 1 Maintenance page 38 OIL...
Page 42: ...42 GB SKD100 498 1060 10 OPTIONAL ACCESSORIES 10 1 Trolley page 43 10 2 AMF Panel page 44...
Page 45: ...45 498 1060 GB SKD100 11 SPARE PARTS...
Page 48: ...48 GB SKD100 498 1060 11 SPARE PARTS...
Page 50: ...50 GB SKD100 498 1060 11 SPARE PARTS...
Page 58: ...Intentionally Left Blank...
Page 59: ...Intentionally Left Blank...
Page 60: ......