Chapter 4 Terminals
QE-
QE+
PE-
PE+
NC
485B
485A
NC
N/-
L/+
1
2
3
4
5
6
7
8
9
10
Energy Pulse Output
RS485
Communication
Power Supply
Upper Row of Terminals
Ua
Ub
Uc
Un
Ia
Ia*
Ib
Ib*
Ic
Ic*
21
22
23
24
25
26
27
28
29
30
Voltage Input
Current Input
Lower Row of Terminals
Chapter 5 Typical Wiring
5.1 Voltage and Current Wiring Instruction
A. Three-phase Four-wire Wiring Mode (3LN, 3CT)
The star-like 3-Phase 4-Line wiring mode is commonly used in low-voltage electric distribution power
systems. The “UL” (voltage wiring mode) on the parameter setting interface should be set as “3Ln”;
“IL” (current wiring mode) should be set as “3C”.
B. Three-Phase Three-Line Wiring Mode (2LL, 2CT)