FCT.EXCESS PRESS
norm. closed -
norm. open
Delay HP 1s
FCT.MOTOR PROT.
norm. closed -
norm. open
FCT.CONCENTRATE
norm. closed
-
norm. open
Delay CO 5s
Switch off
FCT. STOP
norm. closed
norm. open
Delay Stop 1s
FCT. PROG.
norm. closed
-
norm. open
Em.Progam/BP -
Overflow
Function Excess pressure
,
Input excess pressure monitoring HP
Program the desired effect of the connected contact for monitoring the pressure pump,
normally closed or normally open.
Delay HP
Delay time in seconds after which an alarm is triggered and/or the plant should be
switched off if the pressure is too high.
Function Concentrate
,
Input concentrate flow monitoring CO
Program the desired effect of the connected contact for concentrate flow monitoring,
normally closed or normally open.
Delay CO
Delay time in seconds after which an alarm is triggered and/or the plant should
eventually be switched off.
Switch off
Program
A
Switch off
A
if the plant should be switched off after the end of the delay time if the concentrate flow is too low.
Function Motor protection
,
Input motor protection monitoring MP
Program the desired effect of the connected contact for monitoring the driving motor of
the pressure pump/s, normally closed or normally open.
The delay time of 2 seconds after which an alarm is triggered and the pump/s
is/are switched off is predetermined and cannot be changed.
Function Stop
,
Stop input
Program the desired effect of the connected contact for the switch off of the plant,
normally closed or normally open.
Delay Stop
Delay time in seconds after which the plant should be switched off.
Function PROG
,
programmable function input
Program the desired effect of the connected contact through which the following
programmed function should be triggered, normally closed or normally open.
Emergency program/BP
The by-pass valve BP is opened. Due to this, the storage tank or a subsequent plant can
be supplied with water in the case of possible external faults.
Tank overflow
The contact input is used for the tank overflow monitoring of the storage tank. If the storage tank is overflowing, the plant
is switched off and an alarm
A
Tank overflow
A
is triggered.