Description of the menu navigation and adjustment values
11
Betriebsanleitung_pelletfire_Touch_Englisch_V1.2
45
Term
Description
Unit
Parameter I
Room must
temperature
Setting up the required room temperature during heating time. This
setting is only used in connection with a remote control.
°C
Kneeling temperature
Setting up required room temperature during lowering time (10-22).
°C
Flow fixed temperature
Setting up the flow temperature (20 to maximum flow set temperature)
during the set heating ti
me (operation mode “flow fixed”.
°C
Room influence
Room influence (0-10) influences the flow temperature as a function of
the room temperature:
Depending on the level of this value (0-10), the difference of required
room- and room set temperature exerts more influence on the
calculation of the flow set temperature
-
Correction
The correction influences respectively adjust the flow set temperature:
This value (-5 to +5) gets multiplied by 2 and added to the flow set
temperature
°C
Kneeling influence
Setting up the factor (0-10) of the lowering temperature influence.
-
End run
Setting up outside temperature (-25 to 10) which conducts a permanent
running of the pump to avoid freezing.
°C
Parameter II
Switching temperature
Setting up the switching temperature (10-35). That´s the average
daytime temperature that conducts the switching between winter set
temperature and summer set temperature. A higher level of the
switching temperature will delay the switching to summer operation.
°C
Temp. increase
Setting up an increase (0-15) of the required heat circuit temperature
Compensates heat loss between buffer and heat circuit by exceeding
the hot water tank set temperature.
High heat loss assumes a higher value.
°C
Outside temp. sensor
Selection of the outside temperature sensor
If multiple outside temperature sensors are installed, the desired one
can be assigned to the chosen heat circuit.
-
Balancing outside
sensor
Adjusting the balancing of the outside temperature sensor
Adjustment with a reference thermometer (actual outside
temperature)
°C
Hot water tank priority
Activation hot water tank priority (ON/OFF)
The hot water tank is loaded prior compared to the heating circuit.
-
Kneeling barrier
Activation kneeling barrier (ON/OFF)
Heating circuit gets locked during permanent reduction respectively
beyond heating time.
-
Heat curve settings
Flow temperature
maximum
Setting up maximum flow temperature (30-95) of chosen heating circuit.
°C
MODUL
Boiler
Buffer
Hot water tank
Heating circuit
Time mode
Solar
Hydr.compensat
Net pump
Zone valve
Ext. requirement
addit. boiler
Summary of Contents for pelletfire
Page 1: ...Operating instructions Log Wood Pellet heatingsystem pelletfire 20 40 ...
Page 86: ...16 Annex 86 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Hydraulic recommendation 2 ...
Page 87: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 87 16 2 Solar module Program 1 ...
Page 88: ...16 Annex 88 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 2 ...
Page 89: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 89 Program 3 ...
Page 90: ...16 Annex 90 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 4 ...
Page 91: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 91 Program 5 ...
Page 92: ...16 Annex 92 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 6 ...
Page 93: ...Notes 17 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 93 17 NOTES ...
Page 94: ...17 Notes 94 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 ...
Page 95: ...Notes 17 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 95 ...