22
3.3
parameter setting and display
to go into the parameter menu:
– from the selected mode (eg. WInteR)
– press the buttons
r
and
t
(for approximately 5 seconds)
at the same time until “paR 01” (parameter number) and the
value set (0-4) appears on the display
– press the button
t
to scroll up the list of parameters and
then
r
to scroll down the list
Nb:
holding the buttons
r
or
t
increases the speed of the
scrolling movement.
– once the required parameter has been reached, press
the buttons
>
or
<
to modify the value within the permitted
range. the modifications are stored automatically.
When all the parameter modifications have been made, exit
the parameter menu by pressing and holding down the but-
tons
r
and
t
at the same time until the initial screen is dis-
played.
3.4
List of parameters
Type
No.
Description
Range
Unit of
meas-
urement
Step
Default
CONFigURaTiON
PaR
01
Index showing boiler power in kW
0=24; 1=25; 2=30; 3=35; 4=40
0 .. 3
-
1
1
PaR
02
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or heating only
2 = hot water tank with sensor
3 = two programmer
0 .. 3
-
1
2
PaR
03
Gas type Configuration
0 = G20; 1 = G31
0 .. 1
-
1
0
PaR
04
Combustion configuration
0 = sealed chamber with combustion control
1 = open chamber with smoke probe
0 .. 1
-
1
0
PaR
07
Ignition power
0 .. 40
%
1
0
PaR
08
external sensor value correction
-5 .. +5
°C
1
0