Helvar
|
Helvar Oy Ab, Keilaranta 5 FI-02150 Espoo, Finland. Data is subject to change without notice. www.helvar.com
Conformity & standards
General and safety requirements
EN 61347-1
Particular safety requirements for DC
or AC supplied electronic control gear
for LED modules
EN 61347-2-13
Additional safety requirements for AC or
DC supplied electronic controlgear for
emergency lighting
EN 61347-2-13,
Annex J
Thermal protection class
EN 61347, C5e
Mains current harmonics
EN 61000-3-2
Limits for voltage fluctuations and flicker
EN 61000-3-3
Radio frequency interference
EN 55015
Immunity standard
EN 61547
Performance requirements
EN 62384
Digital addressing lighting interface:
General requirements for DALI system
Requirements for DALI control gear
Requirements for control gear of LED
modules
Particular requirements for control gear
- Colour control (Dali Device Type 8)
EN 62386-101
EN 62386-102
EN 62386-207
EN 62386-209
Recommended Practices for Modulating
Current in High-Brightness LEDs for
Mitigating Health Risks to Viewers
IEEE 1789-2015
Compliant with relevant EU directives
RoHS/REACH compliant
ENEC and CE / UKCA marked
Label symbols
Safety isolating control gear with short circuit protection
(SELV control gear).
Thermally controlled control gear, incorporating means
of protection against overheating to prevent the case
temperature under any conditions of use from exceeding
120
°C.
Driver
equipped with NFC wireless technology for
effortless configuration.
Helvar Intelligent Colour drivers providing DALI colour
control (tunable white) functionality.
Lamp failure functionality
No load
When open load is detected, driver will go to standby power
consumption and remains in automatic recovery mode. In automatic
recovery mode, the driver waits till load is returned and once that
happens, it returns to normal operation.
Short circuit
When short circuit is detected, driver goes to automatic recovery
mode and follows the same logic as described in the no load
condition.
Overload
When overload is detected, driver goes to standby mode and returns
through mains reset.
Underload
When undervoltage is detected, driver goes to standby mode and
returns through mains reset.
Switch-Control 2
Use of Switch-Control functionality
• Maximum numbers of LED drivers to be connected to one switch
is 60. Wire length is not restricted by the driver technology.
• Ensure that all components connected to Switch-Control
circuitry are mains rated.
• More information in Switch-Control User Guide at www.helvar.
com.
23.06.2022 7/7
Information and conformity
T22 187 1A