background image

Helvar 478 8 Channel DALI Controller: Installation and User Guide

Menu Options Details

Addresses

The digital interface (DALI or SDIM/DMX) receives control messages from devices in the system.
You can set any address to any channel.

Note:  The base address is the first channel address, from which the remaining addresses are allocated (unless changed 

manually in the Address submenu).

Submenu items

Options

SDIM/DMX mode

DMX or SDIM (Default)

SDIM/DMX base

SDIM Base:  

1–247 (Default: 1)

DMX base: 

1–505

Disabled: 

The address will not be re-allocated 

SDIM/DMX addr

Channel: 1–8
SDIM Address:  1–254; Disabled (Default: 1)
DMX Address:  1–512; Disabled (Default: 1)
Disabled: 

The address will not be re-allocated 

DALI base

DALI Base: 

1–57 (Default: 1)

Disabled: 

The address will not be re-allocated

DALI addresses

Channel: 1–8
Address: 

1–64; Removed; Disabled

Removed: 

Next time you connect it to a controller program or router, the 

 

 

DALI address will be re-allocated

Disabled: 

The address will not be re-allocated. Select this if the channel is 

                              unused. 

Emergencies

When the unit detects an emergency light on a channel, it enables an emergency channel on the DALI system side. If there 

are no emergency ballasts connected on that channel, you can turn this setting off manually with the DOWN button from 

the ‘Emergencies’ screen. Subsequently, you can turn it on again with the UP button.

Sensors

The following Helvar presence sensors can be connected to this unit as long as their firmware versions are 6.37 or later: 

311 Ceiling PIR Detector, 312 Multisensor, 313 Low-Profile Microwave Detector, 314 Tilting Microwave Detector, 315 iDim 

Sense, 317 High-Bay Presence/Absence Detector, and 318 Wall-Mounted PIR Presence/Absence Detector.
 

Submenu items

Options

Enable/On time

The time that the lights are to stay on after the last movement is detected and 

before the ‘Transition Time’ is triggered. You can enter any time between 0 min (‘PIR 

disabled’) and 4 h 15 min.

Exit delay

The time that the lights are to stay on before motion detection resumes. Movement 

during this period will not turn the lights on. This allows time for a person to 

manually turn the lights off and then leave the area without causing the lights to 

turn on. You can set any time between 0 min (‘Off’) and 4 h 15 min.

Transition time

Time that follows the ‘On time’ (see above). If the unit gets a trigger from the 

sensors before the ‘Transition time’ (see below) has lapsed, it will set the ‘On time’. 

Otherwise, it will turn off the lights. You can set any time between 0 min (‘Off’) and 

4 h 15 min.

Check presence

Allows the unit to turn the lights on automatically. You can turn this setting on or off 

as required.

Check absence

Allows the unit to turn the lights off automatically. You can turn this setting on or off 

as required.

Summary of Contents for Digidim DALI 478

Page 1: ...vices connected on the DALI output channel must be programmed using Helvar s Toolbox software Output levels received on the control inputs are broadcast on the corresponding output channel to provide...

Page 2: ...Contents Section Page Product description i Mounting environmental and clearance requirements 1 Installation 1 Connections 1 Configuration 4 Adjust channel levels using the buttons 5 Module Menu Opti...

Page 3: ...VAC DALI channels DALI channels Term B SC 0 V A 0 V OVR 1 2 3 4 5 6 7 8 D1 D D2 D D3 D D4 D D5 D D6 D D7 D D8 D SDIM DMX DA DA DA DA Override DALI control Mains supply AC L Live N Neutral E Earth Grou...

Page 4: ...SDIM DMX AND DALI AT THE SAME TIME iii SDIM or DMX Data Cable from previous device iv Link for Termination if unit is at end of SDIM DMX cable line Note Keep unscreened wire lengths to a minimum i SDI...

Page 5: ...signer or using the control panel buttons and the LCD Set override level for all channels or set different override levels for each channel Vin 1 5 V Ishort 1 mA 85 VAC 264 VAC 45 Hz 65 Hz OK OK OK OK...

Page 6: ...and configure options for all and individual channels Note that the 478 is intended for controlling DALI ballasts drivers and load interface units except for the 490 Blinds Controller Do not connect c...

Page 7: ...annel as required Press the RIGHT button after channel 8 to display the status information about the emergency devices on channel 1 If no emergency devices are present on that channel the main display...

Page 8: ...ther service related information Recall scene Recall a DALI scene Save as scene Save levels as a DALI scene Default scenes Reset DALI scenes to default settings Groups Group and ungroup DALI channels...

Page 9: ...the Emergencies screen Subsequently you can turn it on again with the UP button Sensors The following Helvar presence sensors can be connected to this unit as long as their firmware versions are 6 37...

Page 10: ...f channels This option is always available even when password protection is applied to other options Range scenes 1 16 Save as scene The levels which are currently active for all channels of the dimme...

Page 11: ...ride level regardless of external control signals Options Channel 1 8 ALL Override level 0 100 do not apply override level Default 100 Minimum level Set the minimum DALI lighting level that the channe...

Page 12: ...ns Channel 1 8 ALL On up button Off x down button Default x Set Toolbox mode When this mode is enabled each DALI output channel only acts as a power supply Any DALI compatible control gear or Helvar D...

Page 13: ...8 up button x down button Default x no Press OK to confirm new selection and a Done message appears The password lock will be applied after a period of 60 seconds from this message appearing Enter pas...

Page 14: ...BUS SHORTED Either DALI channel terminals are short circuited Or Too many devices have been connected to a channel and too much current is being demanded from the 478 Note The 478 also reports DALI l...

Page 15: ...Standby power No standby mode DALI power provided for DALI channels Max total losses 7 W DALI consumption 2 mA DALI system input Inputs Control DALI SDIM or DMX Override OVR Wired override input User...