3
MultiZoneBox - KWL-MZB
Installation and Operating Instructions
EN
D
Protection category
IP40
Mains connection KWL-MZB
3 x 1 .5 mm²
Connection control element
J-Y(St)Y 2 x 2 x 0 .6 (max . 100 m)
Wiring diagram
SS-1202
Dimensions
1040 x 722 x 200 mm
Weight
25 kg
1 .13 Accessories
KWL-MZB-BE
Control element Eco
(flush-mounted)
Manual 4 level operation or automatic mode
KWL-MZB-BET
Control element Touch
Manual 4 level operation, automatic mode or weekly programme
KWL-MZB-AP
Adapter plate
For installation in concrete ceiling
KWL-MZB-VSAP
Connection set
For connection of MultiZoneBox to the adapter plate. Set consists of 12 individual connec-
tors and mounting brackets
KWL-MZB-VOC-F
VOC-humidity sensor
For measuring the mixed gas concentration (VOC) and relative humidity
KWL-MZB-F
Humidity sensor
For measuring the relative humidity
KWL-MZB-RH7
Pipe support (for 7 pipes)
For single-sided or double-sided connection of
flex
pipe
plus
KWL-MZB-RH13
Pipe support (for 13 pipes)
For single-sided or double-sided connection of
flex
pipe
plus
When using more than 220 m³/h, increased flow noise may occur . It should be checked whether a correspon-
ding silencer must be provided on site .
2 .0 Assembly
The unit is designed for installation in internal rooms, to walls or ceilings. The room temperature must lie above +5 °C.
Narrow bends result in increased pressure losses and flow noises. The ventilation pipes must never be kinked. Ensure
the fixed and tight fastening of the connectors. The unit cover must be freely accessible for maintenance and installation
work.
2 .1 Air ducting
When designing the ductwork, use the shortest possible runs. Supply and extract air rooms must be defined in advan-
ce. Filters must generally be integrated in extract air valves. Extractor hoods must not be connected to the system.
Sufficient overflow openings (door gap, door grilles) are to be provided to ensure air circulation within the room.
Existing fire protection regulations must be observed .