UK
MiniVent M1/
100/120
N / C
Installation and Operation Instructions
12
– Type M1/100 N / C
Position A - factory setting
Cl. 1 = 75 m³/h, activated via time function
Cl. 2 = 90 m³/h, manual activation
Position B
Cl. 1 = 90 m³/h, activated via time function
Cl. 2 = 75 m³/h, manual activation
– Type M1/120 N / C
Position A - factory setting
Cl. 1 = 150 m³/h, activated via time function
Cl. 2 = 170 m³/h, manual activation
Position B
Cl. 1 = 170 m³/h, activated via time function
Cl. 2 = 150 m³/h, manual activation
Functional test - Test mode:
When applying the supply voltage the fan is in the test mode for 1 minute (Requirement: Factory setting of DIP-switch,
see wiring diagram SS-920.1).
In this case the activation delay and the overrun function is deactivated within the first minute, or for a switching cycle.
NOTE