UK
– Duct inside diameter
M1
/100
N / C
= 100 mm or
M1
/120
N / C
= 120 mm
and distance to room corners: at least 90 mm.
– With regard to surface mounted cabling, the side entry knockout for the cable (fig.9, Pos
➀
) in the casing must be
broken out!
– The connection cable and the control line must be stored so that no water can get in along the cable in case of wa-
ter exposure. The cables must not be placed over sharp edges!
2. Drill holes:
Set casing against the wall, mark the holes and drill. Fasten with at least 2 screws and plugs.
3. Back draught shutter and guide van
– When installing the device, the guide vane must be mounted vertically (fig. 8).
Snaps into place every 90° rotation.
– Affix the rubber foam (scope of delivery) before final assembly (fig.8)
MiniVent M1/
100/120
N / C
Installation and Operation Instructions
8
fig.6
Ø
1
0
0
m
m
Ø
1
2
0
m
m
*
r=
5
8
m
m
r=
6
8
m
m
*
min. 90 mm
m
in
.
9
0
m
m
Cable exit
possible as
required in
dark area
drill holes
Recommen-
ded cable
exit optional
0...-360 °,
ideally 45°
fig.7
Cable routing under the casing. Cable
length from wall at least
180 mm.
*
Type M1/120..
fig.8
When installing the device, the
gui-
de vane
➎
must be mounted verti-
cally (as depicted). Snaps into place
every 90° rotation.
Guide vane
➎
removable
Back dr-
aught
shutter
➏
removable
➎
Affix the
rub-
ber foam
vertical for wall installation
top
bottom
fig.9
➁
Condensate drain holes for
ceiling suspension.
➀
➀
Break out entry
knockout for cable for
wall mounting
➁
➂
➁
Summary of Contents for M1/100 N/C
Page 18: ...MiniVent M1 100 120 N C Montage und Betriebsvorschrift 16 Notizen D...
Page 19: ...MiniVent M1 100 120 N C Montage und Betriebsvorschrift 17 D Notizen...
Page 38: ...MiniVent M1 100 120 N C Installation and Operation Instructions 16 Notes UK...
Page 39: ...MiniVent M1 100 120 N C Installation and Operation Instructions 17 UK Notes...