SYSTEM STATUS SCREEN
The System Status screen allows you to monitor the input and output
status of the power supply.
Input Voltage:
Displays the AC input voltage. Voltage display will
blink during an AC voltage failure. The Value can range from 100-265
VAC
Output Voltage:
Displays the DC output voltage. Voltage display will
blink during an output voltage failure.
Output Current:
Displays the output current. Current display will
blink when the power supply is in current limit.
SYSTEM SETTINGS SCREEN
From the System Status screen, press Enter to move to the System
Settings screen.
The System Settings screen allows you to modify the output settings of
the power supply.
Output Voltage:
Modifies the power supply output voltage. The
Range
of Output Voltage is 11.5 – 15.5 V (12V model, for other models, see
table 3)
Current Limit:
Modifies the power supply output current limit. The
Range of Current Limit is 25A – 120A (12V model, for other models,
see table 3)
DC Output:
Allows you to turn the DC Output On or Off. (Battery
contactor will open when output set to Off on units with LVD option)