8
HQ..
m
– Axial high-performance fans
Installation and Operating Instructions
5.0 Technical data
Protection to
IP 55
Temperature class
T1-T3
Max. air flow temperature
-20 °C bis +40 °C
5.1 Type plate
Example:
Character keys of fan type plate:
➊
Manufacturer's address
➋
Execution:
HQD
= Type name; Three-phase current
560
= Size
/6
= pole
Ex
= Apparatus manufactured to 2014/34/EU (ATEX)
➌
Reference number
➍
Serial number
➎
Marking of explosion-proof fans:
CE
= CE mark
II 2G
= Product category
c
= Mechanical part of fan / Protection by constructual safety
IIB
= Explosion subgroup
H
2
= Hydrogen (only in combination with polymer impellers)
T3
= Temperature class
Type of protection of the motors
= Classification
➏
Production code / Year of manufacture
Art.-Nr. (Ref.no.), SNR (serial number) and PC (production code) number identify clearly the fan.
5.2 Motor type plate
A copy of the motor type plate is located next to the fan type plate.
Technical data are shown on the motor type plate.
5.3 Accessories for explosion-proof fans
Information on explosion-proof accessories can be found from the Internet, the main catalogue or sales literature.
CHAPTER 5
TECHNICAL DATA
UK
HELIOS VENTILATOREN
Lupfenstr. 8
78056 Villingen-Schwenningen Germany
Art.Nr.: 0378/020
HQD 560/6 EX
SNR: 123456/
011
II 2G c IIB + H
2
T3
A
m
Motor : II 2G Ex e II
PC 23114
Herstelljahr 2013
Fig.5
➊
➋
➌
➍
➏
➎
Type
Casing Ø (mm)
Weight max. kg
HQ.. 250 Ex
250
8
HQ.. 315 Ex
315
9
HQ.. 355 Ex
355
10
HQ.. 400 Ex
400
14
HQ.. 450 Ex
450
16
HQ.. 500 Ex
500
18
HQ.. 560 Ex
560
25
HQ.. 630 Ex
630
35
HQ.. 710 Ex
710
105
Summary of Contents for Explosion-proof Series
Page 14: ...12 HQ m Axial Hochleistungsventilatoren Montage und Betriebsvorschrift D ...
Page 15: ...Notizen 13 HQ m Axial Hochleistungsventilatoren Montage und Betriebsvorschrift D ...
Page 30: ...12 HQ m Axial high performance fans Installation and Operating Instructions UK ...
Page 31: ...Notes 13 HQ m Axial high performance fans Installation and Operating Instructions UK ...
Page 46: ...12 HQ m Ventilateurs à haut rendement Notice de montage et d utilisation F ...
Page 47: ...Notes 13 HQ m Ventilateurs à haut rendement Notice de montage et d utilisation F ...