6
Receipt
telegram specification
16
Triton OMD CAN protocol / Rev.-No. 03
6.3
Sensor configuration CRC invalidity report
Command:
99
Data bytes:
2
Destination:
from individual sensor to master.
Timeout:
not periodical telegram
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
High byte
Low byte
High byte
Low byte
High byte
Low byte
High byte
Low byte
Data item
Sensor Configuration
CRC
-
-
-
-
-
Tab. 6.3 Command 99
6.4
Measurement value report telegram
Command:
20
Data bytes:
8
Destination:
from individual sensor to master.
Timeout:
0.2 s
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
High byte
Low byte
High byte
Low byte
High byte
Low byte
High byte
Low byte
Data item
OM Concentration
[mg/l]
OM Concentration
Alarm Percentage
Measured Tempera-
ture
Message Counter
Tab. 6.4 Command 20
Telegram function details are described in section
7.5.1 Measurement value report