7. Cable specification
1130
(1) Single phase unit
Nameplate
maximum
current
Phase line
Earth line
MCB
Creepage protector
Signal line
No more
than 10A
2
2 X 1.5mm
2
1.5mm
20A
30mA less than 0.1 sec
2
n X 0.5mm
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
2
2 X 2.5mm
2
2.5mm
32A
2
2 X 4mm
2
4mm
40A
2
2 X 6mm
2
6mm
40A
2
2 X 10mm
2
10mm
63A
2
2 X 16mm
2
16mm
80A
2
2 X 25mm
2
25mm
100A
2
2 X 25mm
2
25mm
125A
2
2 X 35mm
2
35mm
160A
2
2 X 50mm
2
50mm
225A
2
2 X 70mm
2
70mm
250A
2
2 X 95mm
2
95mm
280A
10~16A
16~25A
25~32A
32~40A
40~63A
63~75A
75~101A
101~123A
123~148A
148~186A
186~224A
Nameplate
maximum
current
Phase line
Earth line
MCB
Creepage protector
Signal line
No more
than 10A
2
3 X 1.5mm
2
1.5mm
20A
30mA less than 0.1 sec
2
n X 0.5mm
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
2
3 X 2.5mm
2
2.5mm
32A
2
3 X 4mm
2
4mm
40A
2
3 X 6mm
2
6mm
40A
2
3 X 10mm
2
10mm
63A
2
3 X 16mm
2
16mm
80A
2
3 X 25mm
2
25mm
100A
2
3 X 25mm
2
25mm
125A
2
3 X 35mm
2
35mm
160A
2
3 X 50mm
2
50mm
225A
2
3 X 70mm
2
70mm
250A
2
3 X 95mm
2
95mm
280A
10~16A
16~25A
25~32A
32~40A
40~63A
63~75A
75~101A
101~123A
123~148A
148~186A
186~224A
(2) Three phase unit
When the unti will be installed at outdoor , Pleas use the cable which can against UV.