Service diagnosis
32
Domestic air conditioner
10.3.1 Thermistor or Related Abnormality
Indoor Display E1: Room temperature sensor failure
E2: Heat-exchange sensor failure
Outdoor display LED1 flash 10 times
:
Defrost temperature sensor failure
LED1 flash 11 times
:
Suction temperature sensor failure
LED1 flash 12 times
:
Ambient temperature sensor failure
LED1 flash 13 times
:
Discharge temperature sensor failure
Method of The temperatures detected by the thermistors are used to determine thermistor errors
Malfunction
Detection
Malfunction When the thermistor input is more than 4.92V or less than 0.08V during compressor
Decision operation.
Conditions
Note: The values vary slightly in some models
Supposed ■ Faulty connector connection
Causes ■ Faulty thermistor
■ Faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Thermistor resistance check method:
●
Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester.The
●
relationship between normal temperature and resistance is shown in the value of indoor thermistor.
Thermistor resistance check
Is it normal?
Yes
NO
Yes
Is it normal?
NO
Check the connector connection.
Replace the thermistor
Replace the indoor unit PCB
Correct the connection
Summary of Contents for 2P Series
Page 11: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV...
Page 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40...
Page 30: ...Dimensional drawing 28 Domestic air conditioner 8 Dimensional drawings 9 Center of gravity...
Page 38: ...Service diagnosis 36 Domestic air conditioner...
Page 60: ...Sincere Forever...