Heatrae Sadia Megaflo Eco Solar Series Product Manual Download Page 38

Unvented Hot Water Cylinder

38

 

IMPORTANT LEGAL REQUIREMENT FOR INSTALLERS

MEGAFLO Eco Solar, a trading name of Heatrae Sadia, a licensed member of the 

Benchmark

TM

 Scheme which aims to 

improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to 
encourage regular servicing to optimise safety, efficiency and performance.  is managed and promoted by the Heating 
and Hotwater Industry Council. For more information visit www.centralheating.co.uk.  Please ensure that the installer 
has fully completed the Checklist on Page 34 of this manual and that you have signed it to say that you have received 
a full and clear explanation of its operation. The installer is legally required to complete a commissioning checklist 
as a means of complying with the appropriate Building Regulations (England and Wales).  All installations must be 
notified to Local Area Building Control either directly or through a Competent Persons Scheme. A Building Regulations 
Compliance Certificate will then be issued to the customer who should, on receipt, write the Notification Number 
on the  Checklist.  This product should be serviced regularly to optimise its safety, efficiency and performance. The 
service engineer should complete the relevant Service Record on the  Checklist after each service.  The Checklist may be 
required in the event of any warranty work.

User Instructions

Warnings                                                                                                                                                                                                  
IF WATER DISCHARGES FROM THE TEMPERATURE / PRESSURE RELIEF VALVE ON THE MEGAFLO Eco SOLAR UNIT REFER 
TO PAGE 29 (TABLE 6) FIRST FOR GUIDANCE. IF THIS DOES NOT RECTIFY THE FAULT SWITCH OFF ELECTRICAL SUPPLY TO 
THE IMMERSION HEATER(S) [ DIRECT UNITS ] OR SHUT DOWN THE BOILER [ INDIRECT UNITS ]. DO NOT TURN OFF THE 
WATER SUPPLY. CONTACT A COMPETENT INSTALLER FOR UNVENTED WATER HEATERS TO CHECK THE SYSTEM.

DO NOT TAMPER WITH ANY OF THE SAFETY VALVES FITTED TO THE MEGAFLO Eco  SOLAR SYSTEM, IF A FAULT IS 
SUSPECTED CONTACT A COMPETENT INSTALLER.

SOLAR PRIMARY CIRCUIT

Temperature control when heating by the solar primary circuit will be controlled by the external solar differential temperature 
controller. The controller should be set to give a water storage temperature of approx. 60

o

C, however it can be set to other 

temperatures. This will usually have been done during installation. A maximum of 70

o

C is recommended to avoid nuisance 

operation of the thermal cut-outs fitted to the unit. Adjustment is made at the solar differential temperature controller, refer to the 
manufacturer’s instructions for details of how to make any adjustments.

Changes to the operating temperature differential set points can affect the efficiency of the operation of the solar heating circuit, it is 
recommended that any changes made are carried out by a competent solar water heating installation engineer.

Immersion Heaters

                                                                                                                                                                                                                                                

A combined thermostat and thermal cut-out is provided for each immersion heater. The thermostat is factory set to give a water 
storage temperature of approx. 60ºC, however it can be set to control between 12ºC and 68ºC. This will usually have been done 
during installation. Adjustments can only be made by opening the terminal cover(s), 

DO NOT remove the cover(s) without first 

switching off the electrical supply. 

The temperature adjustment is made by inserting a flat bladed screwdriver in the slot in the 

disc on top of the thermostat and rotating (see Figure 16, p. 23).

If in any doubt consult a competent electrician.

 

Indirect units

 (CL models) are fitted with an Indirect Thermostat which controls a 2-port motorised valve and hence the temperature 

of the water in the MEGAFLO 

Eco

 Solar unit. The thermostat is factory set to give a water storage temperature of approx. 60ºC, 

however it can be set to control between 12ºC and 68ºC, this will usually have been done during installation. Adjustments can only 
be made by opening the terminal cover. 

DO NOT REMOVE THE COVER WITHOUT FIRST SWITCHING OFF THE ELECTRICAL 

SUPPLY.

 Temperature adjustment is made by inserting a flat bladed screwdriver in the adjustment knob located on the front of the 

thermostat mounting bracket (see Figure 16, p. 23 ) and rotating. At the minimum position the temperature will be approx. 12ºC.

If in any doubt consult a competent electrician.

Flow Performance

                                                                                                                                                                                                                    

When initially opening hot outlets a small surge in flow may be noticed as pressures stabilise. This is quite normal with unvented 
systems and does not indicate a fault. In some areas a cloudiness may be noticed in the hot water. This is due to aeration of the 
water, is quite normal and will quickly clear.

Operational Faults

 

Operational faults and their possible causes are detailed in Table 6, p. 29 

.

 It is recommended that faults should be checked by a 

competent installer.

The air volume within the expansion vessel will periodically require re-charging to ensure expanded water is accommodated within 
the hot water system. A discharge of water INTERMITTENTLY from the Expansion Valve will indicate the air volume in the Expansion 
Vessel has reduced to a point where it can no longer accommodate the water expansion. 

If after following the above actions water still discharges from the Expansion Relief Valve further advice should be sought from a 
competent installer or the BAXI CUSTOMER SUPPORT on Tel: 0844 871 1535.

USER GUIDE (4)

Summary of Contents for Megaflo Eco Solar Series

Page 1: ...Unvented Direct Indirect Solar Megaflo Product Guide Hot Water Cylinders...

Page 2: ...Contents Product Specification Page 3 Installation and Commissioning Instrucions Page 11 Maintenance and Servicing Page 27 User Guide Page 36...

Page 3: ...Introduction Checklist General Requirements Water Supply Power Supply The Environment Specification and Dimensions 3 Unvented Hot Water Cylinder PRODUCT SPECIFICATION 1...

Page 4: ...levels exceed the latest requirements of Building Regulation Part L The MEGAFLO Eco Solar unvented water heater can be fed directly from the cold water mains supply to the property without the need f...

Page 5: ...are subject to freezing must be avoided Ensure that the floor is of sufficient strength to support the full weight of the unit refer to Tables 3 and 4 on page 9 for unit weights Pipe runs should be k...

Page 6: ...opriate Building Regulations either The Building Regulations England The Building Regulations Scotland or Building Regulations Northern Ireland The Water Fittings Regulations England and Wales or Wate...

Page 7: ...ns All connections accept 22mm outside diameter pipe compression nuts and olives supplied Thread rate is 3 4 BSP male parallel to accept standard 3 4 BSP female fittings if required Safety features Di...

Page 8: ...8 Unvented Hot Water Cylinder PRODUCT SPECIFICATION 1 Fig 2 Megaflo eco Solar Direct A D 373 454 414 C B 47 27 30 45 73 600 Fig 3 Megaflo eco Solar Indirect A 373 454 414 E D F C 7 3 600 47 27 30 45...

Page 9: ...IGHT kg SIZE EMPTY FULL AUXILLARY VOLUME L AUXILLARY COIL SPECIFICATIONS SURFACE sqm HEAT UP mins RECOVERY mins RATING kW 170 210 260 300 37 8 42 5 47 3 61 5 207 8 252 5 307 3 361 5 N A 60 60 60 N A 7...

Page 10: ...10 Unvented Hot Water Cylinder NOTES PRODUCT SPECIFICATION 1...

Page 11: ...General Installation Indirect Model Direct Model Commissioning Unvented Hot Water Cylinder 11 PRODUCT SPECIFICATION 1 INSTALLATION AND COMMISSIONING INSTRUCTIONS 2...

Page 12: ...Figure 4 below The 3 Bar Pressure Reducing Valve can be connected anywhere on the cold water mains supply prior to the MEGAFLO Eco Solar unit There is no requirement to site it close to the unit it c...

Page 13: ...Valve 3 Bar Pressure Reducing Valve Stopcock 8 Bar Pressure Relief Valve See Figure 5 below This should be installed between the 3 bar Pressure Reducing Valve and the MEGAFLO Eco Solar cylinder Shoul...

Page 14: ...o Kitchen unbalanced cold mains supply Incoming Cold Water Main KEY MCWS Mains Cold Water Supply HWS Hot water Service SC Stop Cock Isolating Valve DOC Drain Off Cock Discharge pipe to atmosphere see...

Page 15: ...o SOLAR FOR ANY OTHER PURPOSE IT MUST NOT BE USED IN PLACE OF THE SOLAR PRIMARY SYSTEM EXPANSION VESSEL Secondary Circulation The secondary return pipe should be in 15mm pipe and incorporate a check v...

Page 16: ...mains water supply to the MEGAFLO Eco Solar unit iii No control or safety valves should be tampered with iv Water may drip from the discharge pipe of the pressure relief device Expansion Valve and thi...

Page 17: ...the safety device between 18 and 27m at least 3 sizes larger and so on bends must be taken into account in calculating the flow resistance See Diagram 1 Table 1 and the worked example Note An alterna...

Page 18: ...r discharge pipe D2 for common T P Relief Valve sizes Figure 10 Schematic discharge pipe arrangement INSTALLATION AND COMMISSIONING INSTRUCTIONS 2 Discharge Pipework It is a requirement of Building Re...

Page 19: ...control thermostat and thermal cut out If in doubt consult the boiler manufacturer Solid fuel boilers or any other boiler in which the energy input is not under effective thermostatic control unless a...

Page 20: ...see p 21 However other systems may be suitable refer to the controls manufacturers instructions supplied with the controls selected for alternative system wiring schemes Immersion Heater s The MEGAFL...

Page 21: ...N N L N L Bl W G O GY 1 2 3 L N HTG ON DHW ON PUMP BOILER 3 PORT MID POSITION VALVE MEGAFLO ECO DHW 2 PORT VALVE SUPPLIED WIRING CENTRE SUPPLIED PROGRAMMER MEGAFLO ECO INDIRECT THERMAL CONTROLS SUPPL...

Page 22: ...tighten the brass backnut Secure the immersion heater in position by tightening with the key spanner provided Replace the thermostat capillaries spiral one in first making sure capillary tubes do not...

Page 23: ...MPERATURE DECREASE TEMPERATURE ADJUSTING SPINDLE Figure 16 Adjustment details INSTALLATION AND COMMISSIONING INSTRUCTIONS 2 Safety DO NOT BYPASS THE THERMAL CUT OUT S IN ANY CIRCUMSTANCES DISCONNECT F...

Page 24: ...The solar controller and solar primary circulation pump must be wired via the over temperature cut out mounted in the lower solar controls housing Figure 17 below This will ensure that the heat input...

Page 25: ...med to give a maximum storage temperature in the MEGAFLO Eco Solar of 70o C although 60o C is recommended to minimise scaling Direct Units Switch on the electrical supply to the immersion heater s and...

Page 26: ...26 Unvented Hot Water Cylinder NOTES INSTALLATION AND COMMISSIONING INSTRUCTIONS 2...

Page 27: ...Maintenance Fault Finding Servicing Spares Benchmark Unvented Hot Water Cylinder 27 MAINTENANCE AND SERVICING 3...

Page 28: ...ar to relieve the system pressure Open drain cock If water fails to drain from the MEGAFLO Eco Solar vent the unit by manually opening the Temperature Pressure Relief Valve Descaling immersion heater...

Page 29: ...educing Valve If greater than 3 bar replac e P res s ure Reduc er c artridge b E x pans ion V alve s eat dam aged M ilk y water 1 O x y genated water No hot water flow W ater from hot taps is c old W...

Page 30: ...k 95 605 885 Immersion Heater Backnut 95 607 940 Immersion Heater Gasket 95 611 822 Immersion Heater Key 95 607 861 Immersion Heater Blanking Plug 95 605 881 Titanium Immersion Heater Upper 95 606 989...

Page 31: ...Stopcock Can Be Used Either with 3 Bar Inlet Control Valve or 8 Bar Pressure Relief Valve 95605885 MAINTENANCE AND SERVICING 3 Expansion Relief Cartridge 95 605 888 8 Bar Pressure Relief Valve Complet...

Page 32: ...95 612 716 Direct Combined Thermostat and Thermal Cut Out 95 612 717 Incoloy Immersion Heater Lower 95 606 984 6 Way Terminal Block 95 607 933 Terminal cover 95 614 118 Terminal cover 95 614 118 Back...

Page 33: ...Terminal cover 95 614 119 Titanium Immersion Heater Lower 95 606 988 Three Way Terminal Block 95 607 932 C Titanium Immersion Heater Upper 95 606 989 Direct Combined Thermostat and Thermal Cut Out 95...

Page 34: ...34 Unvented Hot Water Cylinder MAINTENANCE AND SERVICING 3...

Page 35: ...Unvented Hot Water Cylinder 35 MAINTENANCE AND SERVICING 3...

Page 36: ...on Units 9 10 Hexagon Business Centre Springfield Road Hayes Middlesex UB4 0TY Tel 020 8606 3567 Parts Center Tel 0845 270 9800 www partscenter co uk Newey Eyre Unit 3 5 Wassage Way Hampton Lovett Ind...

Page 37: ...Unvented Hot Water Cylinder 37 User Instructions Guarantee Customer Service USER GUIDE 4...

Page 38: ...adjustments Changes to the operating temperature differential set points can affect the efficiency of the operation of the solar heating circuit it is recommended that any changes made are carried out...

Page 39: ...een tampered with or been subjected to misuse or neglect No factory fitted parts have been removed for unauthorised repair or replacement The BenchmarkTM Commissioning Checklist and Service Record inc...

Page 40: ...lation legal requirements regulations building regulations benchmark spares stockists guarantees and warranty are ONLY APPLICABLE WITHIN THE UK For local legislation legal requirements regulations bui...

Reviews: