![Heatrae Sadia Megaflo Eco Solar Series Product Manual Download Page 12](http://html1.mh-extra.com/html/heatrae-sadia/megaflo-eco-solar-series/megaflo-eco-solar-series_product-manual_2117689012.webp)
12
Unvented Hot Water Cylinder
INST
ALLA
TION AND
COMMISSIONING INSTRUCTIONS (2)
General Installation
Pipe Fittings
All pipe connections to the MEGAFLO
Eco
Solar are made via 22mm compression fittings directly to the unit (nuts and olives supplied). The fittings
are also threaded
3
/
4
” BSP male parallel should threaded pipe connections be required.
Cold Water Supply
A 22mm cold water supply is recommended, however, if a 15mm (
1
/
2
”) supply exists which provides sufficient flow (see Section1 p.6 “Water
Supply”) this may be used. More flow noise may be experienced from small bore pipes due to the increased water velocity through them.
The Cold Water Inlet Control kit supplied with the MEGAFLO
Eco
Solar incorporates a full flow isolating valve which will enable the MEGAFLO
Eco
Solar to be isolated from the mains supply for maintenance or servicing. To close the valve the blue handle should be turned so that it lies at 90º to
the direction of flow. To open, turn the handle so that it lies parallel to the direction of flow.
3 Bar Pressure Reducing Valve (See Figure 4 below)
The 3 Bar Pressure Reducing Valve can be connected anywhere on the cold water mains supply prior to the MEGAFLO
Eco
Solar unit. There is no
requirement to site it close to the unit, it can be located at a point where the mains supply enters the premises if this is more convenient but you
must install a non-return valve just after the reducing valve for ease of maintenance.
The 3 Bar Pressure Reducing Valve can be installed as a complete one-piece unit or incorporating the stopcock (see Figure 6, p. 13). The valve
incorporates a factory set, non-adjustable Pressure Reducer and Strainer and a single Check Valve. The valve can be fitted in any orientation to
suit the installation, however, ensure that the Valve is installed with the direction of flow arrows (stamped on the side of the brass body) pointing
towards the MEGAFLO
Eco
Solar heater.
If a balanced pressure cold water supply is required to a thermostatic shower mixer valve this may be teed off the supply to the MEGAFLO
Eco
Solar
immediately after the 3 Bar Pressure Reducing Valve (See Figure 7, p. 14).
Figure 4 - 3 Bar Pressure Reducing Valve
Outlet to Megaflo
eco Solar
Mains in
22mm compression connection
Take note of flow
direction
Pressure reducing valve
cartridge (3 Bar)
Summary of Contents for Megaflo Eco Solar Series
Page 1: ...Unvented Direct Indirect Solar Megaflo Product Guide Hot Water Cylinders...
Page 10: ...10 Unvented Hot Water Cylinder NOTES PRODUCT SPECIFICATION 1...
Page 26: ...26 Unvented Hot Water Cylinder NOTES INSTALLATION AND COMMISSIONING INSTRUCTIONS 2...
Page 34: ...34 Unvented Hot Water Cylinder MAINTENANCE AND SERVICING 3...
Page 35: ...Unvented Hot Water Cylinder 35 MAINTENANCE AND SERVICING 3...
Page 37: ...Unvented Hot Water Cylinder 37 User Instructions Guarantee Customer Service USER GUIDE 4...