22
21
Slimline
Series
Model
: PRT-EN
Optional Settings - Feature Table
01
02
03
04
05
06
07
08
09
10
11
12
FEATURE
Temperature Format
Switching Differential
Frost Mode
Frost Protection Temperature
Output Delay
Communications ID No.
Up/Down Temperature Limit
Sensor Selection
Floor Temperature Limit
Optimum Start
Rate of Change
Program Mode
DESCRIPTION
00 =
o
C, 01 =
o
F (°C = Default)
01
o
- 03
o
C (01
o
C = Default)
00 = Enabled, 01 = Disabled (00 = Default)
07
o
- 17
o
C (12
o
C = Default)
00 - 15 Minutes (00 = Default)
Enter Comms number 01-32
00
o
- 10
o
C (00 = Default)
00 = Built in Sensor
01 = Remote Air Sensor
02 = Floor Sensor Only
03 = Built In & Floor Sensor
04 = Remote Air & Floor Sensor
20
o
- 45
o
C (28
o
C = Default)
00 - 03 Hours (00 = Default)
Minutes to raise by 1
o
C
00 = Weekday/Weekend
01 = 7 Day Programming
SETTING
Adjusting the Optional Settings
To adjust the optional settings, follow these steps.
•
Press and hold the Power button to turn the thermostat OFF ..............................
•
Press and hold the Clock key until the display appears as shown below ..........
•
Use the Clock key to cycle through the features ........................................................
•
Use the Up/Down keys to change the setting ....................................................
•
Press A to confirm settings .................................................................................................
•
Press the Power button once again to turn the thermostat back ON .................
Setting Value
Feature Number