background image

#46543 User Guide

HeatLink Digital Thermostat

L646543

November 6, 2007

Page 4

J4

: actuator type selection

(default: 

"NC" 

or normally 

closed)

J5

: perform a 1 minute 

J5

J5

pump exercise each day if 

system inactive

(default: 

"Pnp"

)

J6

: temperature sensor 

(default: 

"Air"

)

J7

: adjusts the type of 

system regulation

(default: 

"rEG"

)

Cp

: compensation value 

(default: 

2.0°C/3.6°F

)

Range: 0.00-12.7

DO NOT ADJUST

PRESS OK Button

to switch between

"NC"

 (normally closed) & 

"

NO"

 (normally open)

PRESS OK Button

to switch between

"Pnp"

 (exercise) and

"

no"

 (no)

PRESS OK Button

to switch between

"Air" 

(air sensor) and

"

FLr"

 (fl oor sensor)

For combined operation select 
"Air" and connect fl oor sensor.

PRESS OK Button

to switch between

"rEG"

 (proportional 

integral) &

"

HYs"

 on/off (parameters 

Cy, On, Of, bp & cp don't 

apply)

apply)

Ao

: Air sensor calibration; 

displays measured air 

temperature 

(default: no offset)

Range: ±10°

adjust to show actual room 

temperature

Fo

: Floor sensor calibration; 

displays measured fl oor 

temperature 

(default: no offset)

Range: ±10°

adjust to show actual fl oor 

temperature

FL

: fl oor temp. LOW limit

(default: 

18.0°C/64.0°F

)

Range:

5°C - 0.5° below 

FH

(41° - 0.5° below 

FH

)

FH

: fl oor temp. HIGH limit

(default: 

28.0°C/82.0°F

)

Range: 

0.5° above 

FL

 - 37°C

(0.5° above 

FL

 - 99°F)

CLr

: resets all parameters 

to factory defaults

PRESS OK Button

screen starts to blink 

indicating adjustment

PRESS OK Button

screen starts to blink 

indicating adjustment

PRESS OK Button

screen starts to blink 

indicating adjustment

PRESS OK Button

screen starts to blink 

indicating adjustment

PRESS & HOLD OK Button 

for 5 seconds

to reset all parameters

to reset all parameters

  

PRESS "

-

" or "

+

To change value

PRESS "

-

" or "

+

To change value

PRESS "

-

" or "

+

To change value

PRESS "

-

" or "

+

To change value

PRESS OK to validate
can only be reset by using  
the ‘Clr’ function

PRESS OK to validate 
can only be reset by using  
the ‘Clr’ function

PRESS OK to validate 

PRESS OK to validate 

�������������������������������������������������

������������

����������������������

��������������������

�������������������������������������������������

�������������������

�������������������

��������������������������

������������������������

�������������������������������������������������

�������������������

����������������������������������������

�������������������

�����������������

��������������������������

���������������������

�������������������

�����������������������

����������������������������������������������

������� ��������������

�������������������

���������������������

������

�����

�������

������

����������������������������������

�������������������������

�������������������

���