Heatilator • RBV4236/RBV4842 • 4048-210 • Rev S • 6/10
23
10
Installing Vent Pipe
Three tabs
A. Assembly of Vent Sections
This B-Vent appliance requires 6 in. B-vent double-wall
pipe. Follow the pipe manufacturer’s installation guide-
lines when installing the unit. This will ensure proper
operation and prevent safety hazards.
WARNING! Risk of Fire/Exhaust Fumes!
Assemble
pipe sections per B-vent manufacturer’s instructions. Use
support tabs for screws.Pipe may separate if not properly
joined.
B. Attaching Vent to Firebox
Three tabs extend from appliance collar shield. Attach
tabs to first section of B-vent pipe using self-tapping 1/4 in.
screws supplied with appliance. See Figure 10.1.
Figure 10.1 Attaching Vent to Firebox
C. Securing Vent Sections
Secure vent sections with vent supports following B-vent
manufacturer’s instructions.
WARNING! Risk of Fire or Explosion!
Use vent run
supports per vent manufacturer’s installation instructions.
• Connect vent sections per vent manufacturer’s
installation instructions.
• Maintain all clearances to combustibles. Maintain
specified slope (if required).
• Improper support may allow vent to sag or separate.
D. Install Attic Insulation Shield
WARNING! Fire Risk. DO NOT
allow loose materials or
insulation to touch vent. Hearth & Home Technologies Inc.
requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 and NFPA 54
requires an attic shield constructed of 26 gauge minimum
metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet vent manufacturer’s specified
clearance and be secured in place per vent manufactur-
er’s instructions.