Heatilator • RAVE4013I • 2184-900 Rev. E • 8/09
26
H
2
H
1
V
2
V
1
Top Vent - Horizontal Termination
Venting with 3 elbows
Note
: Use SLP Series
components only.
1. Top Vent - Horizontal Termination - (continued)
Figure 7.6
RAVE4013I
V
1
Minimum
H
1
+ H
2
Maximum
V
2
V
1
+ V
2
Minimum
90° Elbow
6 ft.
1.8 m
*
*
1 ft.
305 mm
10 ft.
3.0 m
*
*
2 ft.
610 mm
12 ft.
3.7 m
*
*
3 ft.
914 mm
14 ft.
4.3 m
*
*
H
1
+ H
2
MAX. =14 ft. (4.3 m)
V
1
+ V
2
+ H
1
+ H
2
MAX. = 40 ft. (12.2 m)
*No specifi c restrictions on this value EXCEPT V
1
+ V
2
+ H cannot exceed 40 ft. (12.2 m)
Note
: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 7.3).
CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps are not approved for use with pro-
pane (LP) fuel. May lead to elevated glass temper-
ature that may cause tempered glass breakage.