Heatilator LEGACY42-IFT Installation Manual Download Page 5

5

Heatilator  •  LEGACY42-IFT Installation Manual  •  4095-901 Rev. A

 

 •  12/17

G. Requirements for the Commonwealth of 

Massachusetts

For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in 

whole or in part for residential purposes, including those 

owned or operated by the Commonwealth and where the 

side wall exhaust vent termination is less than seven (7) 

feet above finished grade in the area of the venting, in

-

cluding but not limited to decks and porches, the following 

requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter 

shall observe that a hard wired carbon monoxide detector 

with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addi

-

tion, the installing plumber or gas fitter shall observe that 

a battery operated or hard wired carbon monoxide detec-

tor with an alarm is installed on each additional level of 

the dwelling, building or structure served by the side wall 

horizontal  vented  gas  fueled  equipment.  It  shall  be  the 

responsibility of the property owner to secure the services 

of  qualified  licensed  professionals  for  the  installation  of 

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu

-

eled equipment is installed in a crawl space or an attic, 

the hard wired carbon monoxide detector with alarm and 

battery  back-up  may  be  installed  on  the  next  adjacent 

floor level.

In the event that the requirements of this subdivision can 

not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply 

with the above requirements; provided, however, that dur-

ing said thirty (30) day period, a battery operated carbon 

monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor-

dance with the above provisions shall comply with NFPA 

720 and be ANSI/UL 2034 listed and IAS certified. 

Signage

A metal or plastic identification plate shall be permanent

-

ly mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with the 

exhaust vent terminal for the horizontally vented gas fu

-

eled heating appliance or equipment. The sign shall read, 

in print size no less than one-half (1/2) in. in size, 

“GAS 

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-

STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon

-

tally vented gas fueled equipment shall not approve the 

installation unless, upon inspection, the inspector ob-

serves carbon monoxide detectors and signage installed 

in accordance with the provisions of 248 CMR 5.08(2)(a)1 

through 4. 

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)

(a)1 through 4: 
•  The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition 

of NFPA 54 as adopted by the Board; and 

•  Product Approved side wall horizontally vented gas fu

-

eled equipment installed in a room or structure separate 

from the dwelling, building or structure used in whole or 

in part for residential purposes. 

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When  the  manufacturer  of  Product Approved  side  wall 

horizontally  vented  gas  equipment  provides  a  venting 

system design or venting system components with the 

equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system 

shall include:
•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system. 

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not pro

-

vide  the  parts  for  venting  the  flue  gases,  but  identifies 

“special  venting  systems”,  the  following  requirements 

shall be satisfied by the manufacturer:

•  The  referenced  “special  venting  system”  instructions 

shall be included with the appliance or equipment in-

stallation instructions; and 

•  The  “special  venting  systems”  shall  be  Product  Ap

-

proved by the Board, and the instructions for that sys-

tem shall include a parts list and detailed installation 

instructions. 

A copy of all installation  instructions for all Product Ap

-

proved  side  wall  horizontally  vented  gas  fueled  equip

-

ment, all venting instructions, all parts lists for venting 

instructions,  and/or  all  venting  design  instructions  shall 

remain with the appliance or equipment at the completion 

of the installation. 

See Gas Connection section for additional Common-

wealth of Massachusetts requirements.

Note: 

The following requirements reference various 

Massachusetts and national codes not contained in this 

document.

Summary of Contents for LEGACY42-IFT

Page 1: ...flam mable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in y...

Page 2: ...y Diagram 14 B Approved Pipe 16 C Use of Elbows 16 D Measuring Standards 17 E Vent Diagrams 18 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 20 B Wall Penetration Framing Firestops 2...

Page 3: ...____________ ___________________________ ___________________________ ___________________________ Gas Section 9 34 35 Proper appliance for fuel type Was a conversion performed Leak check performed and...

Page 4: ...cable electrical codes when it is installed in locations such as in bathrooms or near sinks NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemen tal...

Page 5: ...s fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local ga...

Page 6: ...ning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Hammer Phillips screwdriver Manometer Gloves Framing square Voltmeter El...

Page 7: ...er vented appliance uses room air for combus tion It is imperative that provisions for adequate com bustion and ventilation air be made Items to consider are While this appliance can operate in enviro...

Page 8: ...clearances refer to Section 5 Note All standoffs measure 1 inch Figure 3 1 Appliance Dimensions 34 5 8 in 879 mm 16 1 2 in 421 mm 27 1 2 in 700 mm 1 in 25 mm 43 1 2 in 1103 mm 73 1 8 in 1857 mm 28 1 2...

Page 9: ...ilator LEGACY42 IFT Installation Manual 4095 901 Rev A 12 17 Figure 3 2 Decorative Front Dimensions GV80BK Screen Front 28 3 8 in 721 mm 23 3 8 in 72 mm 2 in 51 mm 37 in 938 mm 42 in 1065 mm 2 1 2 in...

Page 10: ...4 in 1645 mm 64 3 4 in 1645 mm 68 1 2 in 1739 mm 68 1 2 in 1739 mm 9 6 7 8 i n 2 4 5 9 m m 51 3 8 in 1305 m m 64 3 4 in 1645 mm 64 3 4 in 1645 mm 20 7 8 in 530 mm 51 3 8 in 1305 m m 91 5 8 in 2326 m m...

Page 11: ...1302 mm 28 in 713 mm 51 3 8 in 1305 mm If the inside of the framed cavity is to be finished the framing dimensions must include the finished surface If dry wall is to be attached to the rear wall the...

Page 12: ...to model actual TV temperatures should be validated at the me of each installa on TVs should not be used in situa ons where the actual TV temperature exceeds the manufacturers maximum allowable opera...

Page 13: ...egions where cold air infiltration may be an issue the inside surfaces may be sheetrocked and taped or an equivalent method may be used to achieve maximum air tightness To further prevent drafts the w...

Page 14: ...soffit 18 Clearance below ventilated soffit 18 M Clearance under veranda porch deck balcony or overhang 18 Clearance below vinyl soffit 30 Clearance under veranda porch deck balcony or overhang vinyl...

Page 15: ...t system termination is NOT permitted in screened porches Vent system termination is permitted in porch areas with two or more sides open Hearth Home Technologies assumes no responsibility for the imp...

Page 16: ...igure 4 3 shows the vertical and horizontal offsets for SLG elbows B Approved Pipe This appliance is approved for use with Hearth Home Technologies SLG venting system Refer to Section 12 A for vent co...

Page 17: ...length is measured from the start of the vent run to the end of the vent run including straight pipe as well as elbows Horizontal pipe installed level with no rise Fire Risk LEGACY models must be pow...

Page 18: ...h of vent is a measurement of the total vent used Sample venting configurations shown above with dimensions for reference only Each 90 elbow whether installed vertically or horizontally counts as two...

Page 19: ...or LEGACY42 IFT Installation Manual 4095 901 Rev A 12 17 Elbow installed horizontally Elbow installed vertically WARNING Elbows may NOT be installed in a downward direction Figure 4 6 Elbow installati...

Page 20: ...one side of the interior walls See Section 7 E for information regarding the installation of a horizontal termination cap Non Combustible Wall Penetration If the hole being penetrated is surrounded by...

Page 21: ...305 mm 82 in 2083 mm CENTER LINE 67 3 8 in 1711 mm CENTER LINE 81 in 2056 mm CENTER LINE 66 3 8 in 1686 mm CENTER LINE Shows center of vent framing hole for top or rear venting The center of the hole...

Page 22: ...om the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield D Install Attic Insulation Shield WARNING Fire Risk DO NOT allow loose ma terials or in...

Page 23: ...of the appliance Remove the 8 screws that attach the solid cover plate and vent box to the top of the appliance Relocate the solid cover plate and vent box with insulation from the top of the applian...

Page 24: ...e appliance Secure the appliance to the framing by using nails or screws through the nailing tabs Install upper framing plug after unit is set in place Figure 6 6 Proper Positioning and Securing of an...

Page 25: ...of the methods listed below Apply aluminum foil tape 300 F minimum continuous exposure rated to the outside of the connecting joint after joining and securing sections On horizontal pipe runs it is re...

Page 26: ...een the SLG vent section and slip section is maintained 120 Figure 7 6 Securing Vertical Pipe Sections 120 Figure 7 7 Securing Horizontal Pipe Sections C Secure the Vent Sections Vertical runs origina...

Page 27: ...tire wall thickness DO NOT remove the heat shields attached to the wall shield or the termination cap shown in Figure 7 8 Heat shields must overlap 1 1 2 in 38 mm minimum Termination Cap Slip Section...

Page 28: ...ination must not be recessed in the wall Siding may be brought to the edge of the cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termin...

Page 29: ...ecure with 8 screws Figure 7 14 Position the cap base on exterior wall level and secure with 4 screws provided When properly in stalled the damper collar must extend into the wall shield a minimum of...

Page 30: ...th 8 screws See Figure 7 19 Figure 7 19 Retaining Clips Figure 7 20 Figure 7 21 Secure wire harness and motor wires with retaining clips 2 as shown See Figure 7 20 Reattach louvered cover 8 screws See...

Page 31: ...ge cannot be shared within the same wall box 8 Electrical Information Accessory Cable and Junction Box Installa tion The LEGACY product is a power vented appliance and therefore requires a 110 120VAC...

Page 32: ...rrors could cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105 C rated wire Wire must have high temperature insulat...

Page 33: ...MBLY LEGACY ONLY RED WIRE NOT USED 3 2 1 3 2 1 12V POWER SUPPLY SPEAKERS SOUND KIT PHOENIX OPTION CAPACITOR BLK POWER VENT ASSEMBLY SPEAKER WIRE ASSEMBLY 3 2 1 1 2 JUNCTION BOX JUMPER WIRE SOUND KIT S...

Page 34: ...to purge from lines When purging is complete the appliance will light and operate normally WARNING Risk of Fire Explosion or Asphyxiation Check all fittings and connections with a non corrosive commer...

Page 35: ...ve 4500 feet 1370 m Check with your local gas utility to determine proper orifice size MODEL GAS TYPE AIR SHUTTER LEGACY42 IFT NG Minimum LEGACY42 IFT Propane Open Removed E Air Shutter Setting Air sh...

Page 36: ...or all surfaces floor walls mantels etc will withstand temperatures up to 190 F B Mantel and Wall Projections WARNING Risk of Fire Comply with all minimum clear ances as specified Framing closer than...

Page 37: ...s appliance model may be used Contact your dealer for a list of dec orative fronts that may be used The finishing material thicknesses allowed are noted below Figure 10 4 Non Combustible Finishing Mat...

Page 38: ...ctory Brackets and Grate Assembly from Burner Cover for installation later C Power Vent Speed Control The LEGACY appliance comes equipped with a power vent speed control designed to maintain a preset...

Page 39: ...k Refractory Left Right Side Refractory Left Right Side Hearth Refractory Left Right Middle Front Hearth Refractory Refractory Retainer Note Reference the Homeowner s Manual for instruc tions about re...

Page 40: ...ance until they are tight against the left and right side refractories Tighten 2 screws per side to lock side extensions in place See Figure 11 6 Hearth Refractory Bracket Figure 11 7 Set Left Right S...

Page 41: ...pin See Figure 11 10 Right Front Log Install right front log on the two locating pins on the burner top See Figure 11 11 Left Middle Log Place left middle log on the locating pin on the burner top Se...

Page 42: ...igure 11 16 Figure 11 16 F Accent Light Installation The LEGACY appliance is equipped with an accent light ing feature This appliance is shipped without the halo gen bulb installed to prevent damage d...

Page 43: ...roper burner operation Mineral wool is shipped with this gas appliance Place a small amount of 1 2 in diameter pieces dime size mineral wool on the burner pan as shown in Figure 11 17 The mineral wool...

Page 44: ...ished Height 19 3 4 in 502 mm UNIV AS2 Attic Insulation Shield Tab 1 in 25 4 mm 20 3 4 in 527 mm 14 IN 356 MM 14 IN 356 MM 20 IN 508 MM 12 IN 305 MM DVP RDS ROOF DECK INSULATION SHIELD Effective Lengt...

Page 45: ...d to be used on a wall 4 in to 7 in 102 mm to 178 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 in 178 mm a DV...

Page 46: ...7 46 A Vent Components Diagrams continued Figure 12 3 Vent Components SLG BEK Brick Extension Kit DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield 13 7 8 in 353 mm 5 in 127 mm 26 in 600...

Page 47: ...all a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of reach of children See your dealer if you have questions Wire Ties Flexible Duct not supplie...

Page 48: ...S A Copyright 2017 Heatilator a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www heatilator com Please contact your Heatilator dealer with any questions or concerns For...

Reviews: