D. Vertical Termination Requirements
• Vertical vent terminations are NOT permitted on the
LEGACY product. If a vertical vented installation is
necessary, a chase must be constructed, that maintains
minimum clearances to combustible materials, to allow
the horizontal termination cap to be used.
Note
: Proper termination clearances to windows,
doors, electrical service, etc. must be maintained as
shown in Section 4 of this manual.
Figure 7.8
When properly installed the damper collar must overlap
into the wall shield vent pipe. A minimum of 1-1/2 in. (38
mm) overlap is required for both the damper collar and
heat shields. The damper collar and heat shields are
designed for use on finished wall thicknesses ranging
from 4 in. minimum to 7 in. maximum. If the wall thickness
is greater than 7 in., a damper collar extension and
extended heat shield must be used.
WARNING! Risk of Fire! To prevent overheating and
fire, heat shields must extend through the entire wall
thickness.
• DO NOT remove the heat shields attached to the wall
shield or the termination cap (shown in Figure 7.8).
• Heat shields must overlap 1-1/2 in. (38 mm) minimum.
Termination Cap
Slip Section
Exterior Wall Shield
Heat Shields
E. LEGACY Termination Requirements
WARNING! Risk of Fire!
The LEGACY product is
safety tested and listed for use with the SLG vent
system
ONLY!
The SLG vent system and power vent
termination cap, are unique to the LEGACY product
and
CANNOT
be used on any other appliance.
The LEGACY appliance includes a termination cap,
exterior wall shield and slip section. The termination cap
and wall shield MUST to be used together. See Figure
7.8.
Note:
When using termination caps with factory-supplied
heat shield attached, no additional wall shield firestop is
required on the exterior side of a combustible wall.
Figure 7.9 Venting Through the Wall
Note
:Do not use screws to secure the wall shield
slip section to the exterior wall shield. Aluminum
foil tape or a bead of 100% silicone sealant (300° F
minimum continuous exposure rated) may be used
to seal this joint.
Sheathing
Heat Shield or Extended Heat Shield
1-1/2 in (38 mm) min. overlap
Slip Section
Exterior
Wall Shield
4 in. Min
7 in. Max.