background image

Heatilator  •  AVEO Series DV  •  4058-210 Rev P  •  1/13

17

B. Design and Installation Considerations

Heatilator direct vent gas appliances are designed to op-
erate with all combustion air siphoned from outside of the 
building and all exhaust gases expelled to the outside. No 
additional outside air source is required.

Installation MUST comply with local, regional, state and 
national codes and regulations. Consult insurance carrier, 
local building inspector, fi re offi cials or authorities having 
jurisdiction over restrictions, installation inspection and 
permits.

Before installing, determine the following:

•  Where the appliance is to be installed.

•  The vent system confi guration to be used.

•  Gas supply piping.

•  Electrical wiring requirements.

• Framing and fi nishing details.

•  Whether optional accessories—devices such as a fan, 

wall switch, or remote control—are desired.

D. Inspect Appliance and Components

•  Carefully remove the appliance and components from 

the packaging. 

• 

The vent system components and decorative doors and 
fronts may be shipped in separate packages. 

•  If packaged separately, the log set and appliance grate 

must be installed. 

•  Report to your dealer any parts damaged in shipment, 

particularly the condition of the glass. 

• 

Read all of the instructions before starting the installation. 
Follow these instructions carefully during the installation 
to ensure maximum safety and benefi t.

C. Tools and Supplies Needed

Before beginning the installation be sure that the following 
tools and building supplies are available.

Tape measure 

Framing material

Pliers 

Flat blade screwdriver

Hammer Phillips 

screwdriver

Gloves Framing 

square

Voltmeter 

Electric drill and bits (1/4 in.)

Plumb line 

Safety glasses

Level Reciprocating 

saw

Manometer 

Non-corrosive leak check solution

1/2 - 3/4 in. length, #6 or #8 Self-drilling screws 

Caulking material (300ºF minimum continuous expo-

sure rating)

One 1/4 in. female connection (for optional fan).

Hearth & Home Technologies disclaims any responsibility for, 
and the warranty will be voided by, the following actions:

•  Installation and use of any damaged appliance or vent system 

component.

• Modifi cation of the appliance or vent system.

•  Installation other than as instructed by Hearth & Home 

Technologies.

•  Improper positioning of the gas logs or the glass door.

•  Installation and/or use of any component part not approved 

by Hearth & Home Technologies.

Any such action may cause a fi re hazard.

WARNING! Risk of Fire, Explosion or Electric Shock! 
DO NOT 
use this appliance if any part has been under wa-
ter. Call a qualifi ed service technician to inspect the appli-
ance and to replace any part of the control system and/or 
gas control which has been under water.

Improper installation, adjustment, alteration, service or 
maintenance can cause injury or property damage. For 
assistance or additional information, consult a qualifi ed 
service technician, service agency or your dealer.

WARNING! Risk of Fire or Explosion! 

Damaged parts 

could impair safe operation. DO NOT install damaged, in-
complete or substitute components. Keep appliance dry.

Summary of Contents for Aveo ADVR3428

Page 1: ...d the manufactured home construction and safety standard Title 24 CFR Part 3280 or Standard for Installation in Mobile Homes CAN CSA Z240MH This appliance is only for use with the type s of gas indica...

Page 2: ...Welcome to the Heatilator family of fireplace products We recommend that you record the following pertinent information about your fireplace The model information regarding your specific fireplace can...

Page 3: ...ponents 17 5 Framing and Clearances A Select Appliance Location 18 B Construct the Appliance Chase 19 C Clearances 19 D Mantel and Wall Projections 20 6 Termination Locations A Vent Termination Minimu...

Page 4: ...e Rockwool 56 H Place the Lava Rock 56 I Place the Vermiculite 56 J Remove Screen Protector 56 K Unpackage the Hood Floor Cover 57 L Install Hood 57 M Install Floor Cover 57 N Fixed Glass Assembly 57...

Page 5: ...purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT deal...

Page 6: ...QRUPDO XVH V D KHDWLQJ DSSOLDQFH VRPH FKDQJHV LQ FRORU RI LQWHULRU DQG H WHULRU VXUIDFH ILQLVKHV PD RFFXU 7KLV LV QRW D IODZ DQG LV QRW FRYHUHG XQGHU ZDUUDQW DPDJH WR SULQWHG SODWHG RU HQDPHOHG VXUID...

Page 7: ...primary heat in residential heating calculations D High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or au...

Page 8: ...d heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspect...

Page 9: ...nintended operation when not using your fireplace for an extended period of time summer months vacations trips etc Remove batteries from remote controls Turn off wall controls Unplug 3 volt adapter pl...

Page 10: ...ols Wall Controls and Wall Switches Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protectio...

Page 11: ...oor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your buildi...

Page 12: ...ease refer to www fireplaces com A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these in structions exactly B BEFORE LIGHTING smell all around the appliance...

Page 13: ...be released from finishing materials and adhesives used near the appliance These circumstances may require additional curing related to the installation environment Film on the glass This is a normal...

Page 14: ...erly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds Fronts Frequency Annually By Homeowner To...

Page 15: ...y Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged Replace as necessary Burner Ignition and Operation Frequency Annually By Qualified Service...

Page 16: ...top on floor of attic SECTION 8 Vent Pipe SECTIONS 7 8 10 Framing Header SECTION 5 Gas Line SECTION 11 Framing Headed off in Ceiling Joists SECTION 8 Mantel Mantel Leg SECTION 13 Surround Hearth Exten...

Page 17: ...nning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Flat blade screwdriver Hammer Phillips screwdriver Gloves Framing squar...

Page 18: ...l installation may vary due to individual design preference Figure 5 1 Appliance Locations In addition to these framing dimensions also reference the following sections Clearances and Mantel Projectio...

Page 19: ...steps Chases should be constructed in the manner of all out side walls of the home to prevent cold air drafting prob lems The chase should not break the outside building envelope in any manner Walls c...

Page 20: ...s Measured from top of hood in inches 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 5 5 1 2 6 1 4 7 7 3 4 8 1 2 9 1 4 10 10 3 4 11 1 2 12 1 4 13 13 3 4 14 1 2 15 1 4 16 30 in minimum to ceiling Figure 5 3...

Page 21: ...5 Over 20 12 to 21 12 8 0 3 ft minimum in snow regions Storm Collar Roof Flashing 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with in...

Page 22: ...Vertical clearance between two horizontal termination caps 12 in 30 cm minimum O Horizontal clearance between two horizontal termination caps 12 in 30 cm minimum P 6 Non vinyl sidewalls 12 Vinyl sidew...

Page 23: ...A length of straight pipe is allowed between two 45 elbows see Figure 7 1 Figure 7 1 Using Two 45 Elbows 7 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table...

Page 24: ...s may be placed back to back anywhere in the system as long as the first 90 elbow is a starter elbow except as shown in Figure 7 4 When penetrating a combustible wall a wall shield firestop must be in...

Page 25: ...Horizontal Termination continued Figure 7 4 Two 45 Elbows replacing One 90 Elbow V1 min V1 max H1 H2 max H1 H2 H3 max 6 in 152 mm x 6 ft 1 83 m x 1 ft 305 mm x 11 ft 3 35 m 11 ft 3 35 m 1 1 2 ft 457 m...

Page 26: ...8 210 Rev P 1 13 26 Figure 7 6 1 Top Vent Horizontal Termination continued Three Elbows V1 min V1 V2 max H1 H2 max 1 ft 305 mm 24 ft 7 32 m 19 ft 5 79 m Note The first elbow used in the system must be...

Page 27: ...lbow Figure 7 7 Figure 7 7b 12 ft to 30 ft Vertical Run Figure 7 7c 31 ft to 60 ft Vertical Run Install Baffle Remove screws from flue firebox top Usingthescrewsremoved Installbaffleaccordingtoyour in...

Page 28: ...AVEO Series DV 4058 210 Rev P 1 13 28 Figure 7 8 Two Elbows 2 Top Vent Vertical Termination continued 12 ft 3 66 m min 60 ft 18 29 m max Maximum horizontal run is 100 of vertical but cannot exceed 26...

Page 29: ...AVEO Series DV 4058 210 Rev P 1 13 29 Figure 7 9 2 Top Vent Vertical Termination continued Three Elbows 12 ft 3 66 m min 60 ft 18 29 m max Maximum horizontal run is 100 of vertical but cannot exceed 2...

Page 30: ...Heatilator AVEO Series DV 4058 210 Rev P 1 13 30 3 Rear Vent Horizontal Termination Figure 7 10 Figure 7 11 No Elbow One 45 Elbow 18 in 457 mm max 18 in 457 mm max...

Page 31: ...V Min Total Horiz H1 H2 H3 ADVR ft 0 2 1 3 m 0 61 0 31 0 91 ft 4 2 6 m 1 22 0 61 1 83 ft 6 3 9 m 1 83 0 91 2 74 ft 8 4 12 m 2 44 1 22 3 66 ft 8 5 15 m 2 44 1 52 4 57 ft 8 6 18 m 2 44 1 83 5 49 Model H...

Page 32: ...ent Vertical Termination One Elbow Figure 7 14 Two Elbows Figure 7 15 12 ft 3 66 m min 60 ft 18 29 m max 0 min 6 ft 1 83 m max 12 ft 3 66 m min 60 ft 18 29 m max 0 min 6 ft 1 83 m max Maximum horizont...

Page 33: ...V 4058 210 Rev P 1 13 33 4 Rear Vent Vertical Termination continued Three Elbows Figure 7 16 12 ft 3 66 m min 60 ft 18 29 m max 0 min 6 ft 1 83 m max Maximum horizontal run is 100 of vertical but can...

Page 34: ...Combustible Materi als Non Combustible Wall Penetration If the hole being penetrated is surrounded by non combus tible materials such as concrete a hole with diameter one inch greater than the pipe i...

Page 35: ...a ceiling floor see Figure 8 3 SLP pipe only Frame opening 9 in x 9 in 229 mm x 229 mm whenever the vent penetrates a ceiling floor see Figure 8 3 Frame the area with the same sized lumber as used in...

Page 36: ...the air space between the pipe and the shield Set the shield on the ceiling firestop and attach to the firestop Bend all tabs inward 90 around the top of the shield These tabs must be used to prevent...

Page 37: ...roperly position and secure the appliance see Figure 9 1 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position K...

Page 38: ...op heat shield Figure 9 2 Remove back screws holding top heat shield Figure 9 3 Bend heat shield up See Figure 9 4 Install first piece of vent pipe Figure 9 5 Figure 9 2 Top Heat Shield Figure 9 3 Rem...

Page 39: ...penetrate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent t...

Page 40: ...termination cap Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections See Figure 10 1 Only outer pipes need to be sealed All unit collar pipe slip section elbo...

Page 41: ...runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal runs must be supported every 5 feet 1 52 m Wall shield firestops may be used to provide...

Page 42: ...k the center line of the venting system on the ceiling and drill a small hole through the ceiling and roof at this point Locate the hole and mark the outline of the cathedral ceiling support box on th...

Page 43: ...Over 11 12 to 12 12 4 0 Over 6 12 to 7 12 1 25 Over 12 12 to 14 12 5 0 Over 7 12 to 8 12 1 5 Over 14 12 to 16 12 6 0 Over 8 12 to 9 12 2 0 Over 16 12 to 18 12 7 0 Over 9 12 to 10 12 2 5 Over 18 12 to...

Page 44: ...6 Wrap the storm collar around the exposed pipe section closest to the roof and align brackets Insert a bolt provided through the brackets and tighten the nut to complete the storm collar assembly Fig...

Page 45: ...the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall thickness is less than 4 in 102 mm DVP or 4 3 8 in 111 mm SLP the heat shields on the c...

Page 46: ...outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of...

Page 47: ...gies fireplace systems and termination caps The shrouds must be constructed from a minimum 018 in 26 ga thick aluminized steel The wire mesh is optional but recommended and must be 018 in thick minimu...

Page 48: ...th Min Base Dimension Minimum Height Figure 11 2 Roofed Style Shroud Dimensions Roofed Style Shroud may be used with DVP TV DVP TVHW SLP TVHW Mailbox Style Shroud may be used with DVP TV DVP TVHW SLP...

Page 49: ...ormation Gas Pressure Natural Gas Propane Minimum inlet pressure 5 0 in w c 11 0 in w c Maximum inlet pressure 10 0 in w c 13 0 in w c Manifold pressure 3 5 in w c 10 0 in w c Note Have the gas supply...

Page 50: ...ms or near sinks Low voltage and 110 120 VAC voltage cannot be shared within the same wall box WARNING Risk of Shock or Explosion DO NOT wire 110V to the valve or to the appliance wall switch Incorrec...

Page 51: ...Box To Junction Box Battery Pack 3V Adapter BLK BRN RED RED Valve WHT Wall Switch WHT GRN GRN wire only used with optional wall switch WSK MLT HTL Ignitor Flame Sensor Pilot Assembly E Electrical Ser...

Page 52: ...unction box as shown Add a 1 4 in insulated female connector to the red switch leg wire route it through the knockout in the face of the junction box and connect to the top fan switch connector 1 4 in...

Page 53: ...4 8 1 2 9 1 4 10 10 3 4 11 1 2 12 1 4 13 13 3 4 14 1 2 15 1 4 16 30 in minimum to ceiling 14 14 Finishing A Mantel and Wall Projections WARNING Risk of Fire Comply with all minimum clear ances to comb...

Page 54: ...or access for service Facing and or finishing materials must never overhang into the glass opening Observe all clearances when applying combustible materials Seal joints between the finished wall and...

Page 55: ...rials Remove the shipping materials from inside or underneath the firebox D Remove Fixed Glass Assembly See Section 15 N E Clean the Appliance Clean vacuum any sawdust that may have accumulated inside...

Page 56: ...p of lava rock J Remove Screen Protector Tear the corrugated as shown in Figure 15 6 The corrugated must be separated along the entire top edge of the protector Slide the screen protector off the scre...

Page 57: ...l the floor cover as shown in Figure 15 10 N Fixed Glass Assembly Removing Fixed Glass Assembly WARNING Risk of Asphyxiation Handle fixed glass assembly with care Inspect the gasket to ensure it is un...

Page 58: ...the firebox assembly Figure 15 14 The air shutter is factory set for the mini mum vertical vent run If your installation has more than the minimum required vertical vent length adjustment of the air...

Page 59: ...mocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Verify proper voltage output from the thermocouple to the valve Place one millivolt meter lead wire on the t...

Page 60: ...tank B Improper gas inlet pressure Verify with manometer NG should read 5 14 inches w c LP should read 10 14 inches w c C Inner vent pipe leaking exhaust gases back into the system Check venting syst...

Page 61: ...pply is installed and plugged into module Check voltage of power supply under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good power supply are betwee...

Page 62: ...rod should glow shortly after ignition Verify correct pilot orifice is installed and gas inlet is set to pressure specifications C Module is not grounded Verify module is securely grounded to metal ch...

Page 63: ...s and clearances refer to Section 5 Figure 17 1 Appliance Dimensions 11 1 2 in 292 mm 33 in 838 mm 28 in 711 mm 22 3 8 in 568 mm 5 1 2 in 140 mm 2 in 51 mm 6 in 152 mm 3 1 8 in 79 mm 30 1 2 in 775 mm...

Page 64: ...fective Height Length 10 1 2 in 267 mm 10 7 8 in 276 mm DVP45 45 Elbow 45 4 7 8 in 124 mm Assembled Height 24 in 610 mm Diameter 10 in 254 mm DVP AS2 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop 7...

Page 65: ...m 13 1 4 in 337 mm RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in...

Page 66: ...mination Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT Fire Brick Termination Cap 7 1 4 in 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP T...

Page 67: ...ngth Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm t...

Page 68: ...1 4 in 235 mm SLP 45 45 Elbow SLP 90ST 90 Elbow Effective Height Length Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 1...

Page 69: ...P adapter when used with SLP Pipe SLP TRAP1 Horizontal Termination Cap SLP CCS BK Cathedral Ceiling Sup port Box Black SLP TRAP2 Horizontal Termination Cap 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm SL...

Page 70: ...T overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields m...

Page 71: ...wing page 3 2 1 Log Set Assembly Aveo 28 Gas Fireplace DV 01 13 ADVR3428 ADVR3428i ADVR3428iL Beginning Manufacturing Date April 2008 Ending Manufacturing Date Active 6 7 9 10 11 12 13 14 17 1819 16 1...

Page 72: ...t 4058 127 12 Pilot Bracket Gasket 4058 194 13 Burner Assembly NG 4058 020 Y Burner Assembly LP 4058 021 Y 14 Front Air Baffle 4058 118 15 Valve Bracket 4058 125 16 Glass Frame Assembly 4058 010 Y 17...

Page 73: ...on following page 3 2 1 Log Set Assembly Aveo 28 Gas Fireplace DV 01 13 ADVT3428 ADVT3428i ADVR3428iL Beginning Manufacturing Date April 2008 Ending Manufacturing Date Active 6 7 9 10 11 12 13 14 17 1...

Page 74: ...94 13 Burner Assembly NG 4058 020 Y Burner Assembly LP 4058 021 Y 14 Front Air Baffle 4058 118 15 Valve Bracket 4058 125 16 Glass Frame Assembly 4058 010 Y 17 Screen Face 4058 004 Y 18 Thumb Screw 402...

Page 75: ...2 320A Y 22 5 Valve NG 750 500 Y Valve LP 593 501 Y 22 6 Brass Fitting Pkg of 5 303 315 5 Y 22 7 Bulkhead Flexible 4021 428 Y 22 8 Gasket Bulkhead 4021 429 22 9 Module 593 592 Y 22 10 Module Wire Asse...

Page 76: ...4021 042 22 3 Valve Bracket 4058 192 22 4 Flex Ball Valve Assembly 302 320A Y 22 5 Valve NG 230 0710 Y Valve LP 230 0720 Y 22 6 Piezo Ignitor 291 513 Y 22 7 Bulkhead Flexible 4021 428 Y 22 8 Gasket B...

Page 77: ...238 mm TCG375 Terra Cotta Cap LDSCP M Shroud Leg Multipack not shown See your Heatilator dealer for a complete listing of optional components D Optional Components continued Catalog A B C D in mm in...

Page 78: ...__ ________________________________________________________________________________ ________________________________________________________________________________ ___________________________________...

Reviews: