2
PRODUCT INFORMATION
Model Saf-T Liner system is intended for use in conjunction with any residential building, heating appliance burning gas, liquid
or solid fuels, such as a woodstove, fireplace insert, or an oil or gas fired central heating furnace, vented through masonry
chimneys only. These heating appliances may not exceed the maximum continuous flue-gas outlet temperatures of 1000°F
or cause condensation of corrosive acids on the liner, or create positive pressures in the chimney system. Saf-T Liner is not
intended for Category II, III or IV burning appliances. See Table 1 for Technical Specifications.
Saf-T Liner is listed to UL 1777 and is a high quality stainless steel lining system designed for relining existing masonry
chimneys. It satisfies code requirements as a substitute for 5/8” fireclay liners and has undergone extensive testing to make
it the leader in the stainless steel chimney lining industry. The installation of Saf-T Liner should be performed by an experienced
professional who works with chimney and woodstove related products on a regular basis.
Saf-T Liner is intended for use in accordance with the following National Fire Protection Association Standards, 211, 54 and 31.
GENERAL INFORMATION
Ensure your installation will conform with all federal and municipal building code requirements. Before commencing your
installation, contact your local building or fire officials about restrictions and installation in your area. Obtain any necessary
building permits. If you choose to have your liner professionally installed, have it installed by professionals who are certified by
N.F.I. or CSIA.
Authorities require that the masonry chimney extend not less than 3 feet above the highest point where it passes through the
roof of a building and not less than 2 feet above any portion of the building within ten feet (see Fig. 1).
Materials:
.024 304 Stainless Steel
.024” 316L Stainless Steel
Includes:
1/8” Stainless Steel Blind Rivets (4 per
lengths/components)
Table 1
TECHNICAL SPECIFICATIONS
Diameters:
4” to 12”
Maximum Height:
80 Feet
Used with:
Saf-T Wrap - 8 lb. density ceramic fiber insulation
adhered to a .024” aluminum jacket
Installed Length:
Minus 2” for the overlap
Tested and Listed to:
UL 1777
Maximum Operating Temperature:
1000°F
Usage:
Connector Pipe and Masonry Chimney Liner System
suited for use with solid fuel and older oil or gas fired
equipment that does not produce condensation in the vent.
Seams:
Continuous-Resistance Welded Seams
ASSEMBLY MATERIALS REQUIRED:
The following tools and supplies may be needed to complete the installation of the Saf-T Liner.
- Safety Work Gloves
- Eye Protection
- Dust Respirator (3M 9900, 3M8710 or equiv.)
- Ladder(s)/Scaffolding
- Shop Vac
- Drop Cloth
- 1/8” or #30 High Speed Drill Bit
- Masonry Drill Bits 3/8” or 1/2”
- Measuring Tape
- Utility Knife
- Screwdriver w/ Hex Head
- Hammer
- Pliers
- Cold Chisel
- Caulking Gun
- Silicone Caulk/High Temperature
- Bag of Mortar Mix
- Trowel
- Mortar Pan
- Metal Foil Duct Tape
- Rope (10 feet longer than chimney including a wire hook at one end)
- Chimney Brushes and Rods
- Extension Cords / Work Light
- Reversible Electric or Cordless Drill
- Hacksaw/Reciprocating Saw & Blades
- Small Adjustable Wrench/Ratchet Set
- Awl/Chalk/Felt Tipped Markers
- Tin Snips/Side Cutter/Shears
- Metal Folder
- Pop Rivet Gun for 1/8” Rivets
- Extra Pop Rivets
Saf-T Liner should not extend more than 6 inches above the masonry chimney. Any additional flue liner height above the
masonry chimney will create condensation resulting in the buildup of excessive creosote.
Do not connect more than one solid fuel burning appliance to a single chimney flue and do not connect gas or liquid fired
appliances to chimney flues serving a solid fuel burning appliance.