background image

Parallel Compressor Systems Installation & Operations Manual, October 2004  

31

Parallel Compressor Systems

Liquid Drain Control Method

This method is ideal for large capacity systems since a smaller 

regulator is required for liquid line than for discharge line.
During warm ambient temperature conditions valves A and 

C will be open and Valve B will be closed. When the ambient 

temperature at the condenser drops, the condenser pressure 

will tend to become lower. As this pressure is reduced, when 

the pressure becomes as low as its setting, Valve A will begin 

to close, thus causing the refrigerant to back up inside the 

condenser tubes, reducing the condensing surface and allowing 

the pressure to be maintained. As Valve A closes, the receiver 

pressure may be reduced by the cold entering liquid to a level 

below the setting of Valve B, which will begin to open to bypass 

sufficient gas to maintain the receiver pressure at the set point 

of Valve B. Check valve C will prevent the high pressure from 

backing up to the condenser when the receiver pressure is 

higher than the condenser pressure, as would be the case 

during shutdown in a system with a warm receiver.
When the condenser pressure builds up to the setting of Valve 

A, it will open allowing liquid to flow to the receiver.
To  describe  it  again,  during  cold  ambient  temperature 

conditions this liquid will be considerably subcooled and will 

tend to lower the receiver pressure. Valve B will sense the drop 

in pressure and open to admit hot gas into the drain line, thus 

pressurizing  and  warming  the  liquid  and  maintaining  the 

receiver pressure.

Recommended Valve Settings

Regulators ordered for a Condenser Pressure Control system for 

use with common refrigerants will be furnished with the ranges 

and factory settings shown in Table 29. Turning the adjusting 

stem in (clockwise) will raise the set point; turning the stem 

out (counterclockwise) will lower the set point. See Table 29 for 

ranges and amount of pressure change per turn.

Valve

Type

Range

Factory

Set Point

Change Per 

Turn

psig kg/cm

2

psig kg/cm

2

psig kg/cm

2

A4A

ARA0 D

75 to

280

5.2 to

19.7

140

9.8

53

3.7

A7A

A7A1

A72

D 75 to

280

5.3 to

19.7

120

8.4

75

5.3

A9

B 80 to

220

5.6 to

15.5

120

8.4

25

1.8

Field Adjustment

Before  final  field  adjustment  of  regulators  for  Condenser 

Pressure Control, the following should be done:
1.   Install gauges to read compressor discharge, condenser and 

receiver pressures.

2.   Fully charge the system.
3.   Have  other  controls  and  components  functioning 

properly.

4.   Have the system as fully loaded as possible.

5.   Final  adjustments  should  be  made  when  the  outdoor 

ambient is below 65°F. Ideally the ambient should be near 

minimum system outdoor temperature to allow the system 

pressures to drop below the regulator pressure settings. 

Before adjusting make sure that all manual opening stems 

on the regulators are set for automatic operation. It may 

be necessary to temporarily deactivate the low pressure 

cut out controls to keep the compressors running during 

adjustment.

6.   The regulators should be preset using information in Table 

29.

7.   When the valves are adjusted with the system operating, 

enough time must be allowed for the system to stabilize. 

Check  the  sight  glass  to  make  sure  sufficient  liquid  is 

supplied to the evaporators.

8.  Turn the condenser fans off to allow the discharge pressure 

to build up. The regulator A should be adjusted to open 

when the pressure reaches the desired control point. Listen 

for flow through regulator A while watching the pressure 

gauge.

To determine the final setting of regulator B, allow the condenser 

fans to run long enough to subcool the liquid supplied to the 

receiver. Adjust the regulator until the desired receiver pressure 

is obtained. Flow through the valve can be determined by 

listening at the valve for gas flow or by feeling the outlet for 

change in temperature. The setting of regulator B should be at 

least 10 psi lower than the setting of regulator A.

Hot Gas Bypass Regulator Adjustment

Discharge  Bypass  Valves  (DVB)  respond  to  changes  in 

downstream  or  suction  pressure. When  the  evaporating 

pressure is above the valve setting, the valve remains closed. 

As the suction pressure drops below the valve setting, the valve 

responds and begins to open. As with all modulating type 

valves, the amount of opening is proportional to the change in 

the variable being controlled - in this case the suction pressure. 

As the suction pressure continues to drop, the valve continues 

to open farther until the limit of the valve stoke is reached.
On refrigeration systems discharge bypass valves are used to 

prevent the suction pressure from going below the minimum 

value determined by the job requirements.

Sporlan Valve Company

   

 

 

Valve Setting and Adjustment
A complete discussion on valve settings is given in Sporlan 

Application Bulletin 90-40. The fully adjustable models ADRS(E)-

2, ADRP(E)-3, and ADRH(E)-6 are available with two adjustment 

ranges - 0/30 and 0/80 psig. The standard factory settings 

for these are 20 and 60 psig, respectively. The ADRI(E)-1-1/4 

is available with a 0/55 psig range and the standard factory 

setting is 28 psig. 
To adjust these valves, remove the cap an turn the adjustment 

nut  with  a  5/16”  hex  wrench  for  fully  adjustable  models 

ADRS(E)-2,  ADRP(E)-3,  and  ADRH(E)-6.  The  ADRI(E)-1-

1/4  model  has  a  3/8”  adjustment  screw  on  top  of  the 

adjustment  housing.  A  clockwise  rotation  increases  the 

setting and a counterclockwise rotation decreases the setting.  

Adjusting these valves can be complicated because the load 

Table 29. Pressure Range, Set Point & 

Charge Per Turn

Summary of Contents for H-IM-PCS

Page 1: ...Parallel Compressor Systems Bulletin No H IM PCS October 2004 Part Number 25000102 Replaces H IM 72B October 2004 Installation and Operation Manual...

Page 2: ...peland Lubricants Carlyle Compressors Approved Carlyle Lubricants Oil Pressure Table 13 O6D E Oil Pressure History Table 14 Oil Safety Switch 22 Table 15 Part Load Performance Multipliers Table 16 Req...

Page 3: ...tive and the carrier of the damage immediately Request an immediate joint inspection with the carrier Do not repair the unit until inspected by carrier s representative Care should be exercised when u...

Page 4: ...es at the rear and 42 inches in the front of panel or as required by National or Local Codes For parallel system units placed end to end 24 inches between units is suggested Floor Foundation Requireme...

Page 5: ...e ground level provides some protection from ground water and wind blown matter The concrete slab should be isolated from the building structure Finally before tightening mounting bolts recheck the le...

Page 6: ...whenever possible Care should be taken to see that ample room is left for maintenance work through access doors and panels When the unit is in an area where it is enclosed by three walls the unit mus...

Page 7: ...ment Before starting up a parallel unit insure that all fuses and motor protective devices are in place and that all wiring is secure A complete wiring diagram for troubleshooting the unit will be fou...

Page 8: ...ed a maximum of 2 feet in each direction Pipingattachedtoavibratingobject suchasacompressor or compressor base must be supported in such a manner that will not restrict the movement of the vibrating o...

Page 9: ...ially on hot gas lines to prevent line breakage This is critical on long straight runs of generally 70 or more where expansion loops must be provided and hangers should allow for longitudinal movement...

Page 10: ...04A R 507 4 1 1 1 6 1 1 6 8 2 2 1 10 2 2 7 12 2 3 3 16 3 4 1 20 4 5 6 30 6 8 3 40 8 11 8 Table 2 Pressure Loss of Liquid Refrigerants In Liquid Line Risers Expressed in Pressure Drop PSIG and Subcooli...

Page 11: ...2 57 3 50 4 98 14 27 40 26 42 58 40 64 95 61 93 1 32 1 91 1 33 1 87 1 5 8 12 134A 22 R 507 502 404A 90 9 90 0 78 0 3 65 4 96 7 07 20 37 56 37 59 82 57 90 1 35 87 1 33 1 86 1 30 1 88 2 64 2 1 8 12 134...

Page 12: ...8 2 1 8 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 1 5 8 1 5 8 1 5 8 84 000 1 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 1 3 8 1 3 8 1 5 8 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8...

Page 13: ...8 5 8 5 8 72 000 1 5 8 2 1 8 2 1 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 5 8 5 8 5 8 5 8 5 8 7 8 78 000 2 1 8 2 1 8 2 1 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 1 5 8 1...

Page 14: ...1 5 8 1 5 8 1 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 1 3 8 1 3 8 1 5 8 84 000 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 1 5 8 1 1 8 1 3 8 1 3 8 1 3 8 1 5 8 1 5 8 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 1 3 8 1 5 8 1 5 8...

Page 15: ...5 8 5 8 72 000 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 1 2 1 2 5 8 5 8 5 8 7 8 78 000 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 1 3 8 1 5...

Page 16: ...1 8 1 3 8 1 1 8 1 1 8 180 000 50 100 1 5 8 2 1 8 1 3 8 1 3 8 1 3 8 1 3 8 1 3 8 1 3 8 1 3 8 1 5 8 1 3 8 1 3 8 1 3 8 1 5 8 1 3 8 1 3 8 240 000 50 100 1 5 8 2 1 8 1 5 8 1 5 8 1 5 8 1 5 8 1 3 8 1 3 8 1 5...

Page 17: ...e pull down The wiring diagramfortheunitwillhavetobeconsultedtodetermine how to best force the fans to operate for this step 4 With all compressor and control breakers and toggle switches turned off a...

Page 18: ...eturned into the liquid manifold the Priority I design returns the liquid to the condenser through a liquid drain manifold Hot discharge gas is injected into the suction line at the parallel rack and...

Page 19: ...igerant being returned to the compressor This will cause dilution of the oil and eventual failure of the bearings and piston rings In extreme cases the compressor will fail as a result of the diluted...

Page 20: ...est The compressors are solid mounted to a base frame or mounted on the refrigerant receiver All reciprocating compressors incorporate oil floats Crankcase heaters will be installed and wired Cylinder...

Page 21: ...1 24 to 1 8 18 to 34 1 24 to 2 3 Carlyle Compressors Approved Carlyle Lubricants For CFC and HCFC Refrigerants Use Totaline 150 Suniso 3GS Shrieve Zerol 150 Texaco WFI 32 150 IGI Petroleum Cryol 150...

Page 22: ...eactivated after a specified trip delay The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time Restart Delay The trip delay prevents nuis...

Page 23: ...Vessel is exposed to excessive heat When a Vessel containing liquid refrigerant is shut off from otherpartsofthesystemariseintemperaturewillcausearisein pressure If theVessel is completely filled wit...

Page 24: ...let 350 400 425 450 Angle 526E 3 8 MPT 3 8 FLARE 10 2 11 6 12 3 13 0 527E 1 2 MPT 5 8 FLARE 28 5 32 4 34 4 36 3 Straight Through 5231 3 8 MPT 3 8 FLARE 11 2 12 7 13 5 14 3 5231 A 3 8 MPT 1 2 FLARE 18...

Page 25: ...cannot be reset until the pressure drops to a predetermined level The latching mechanism inside the manual reset model is trip free The electrical contacts will cutout even if the reset button is hel...

Page 26: ...d to insure the system will work properly Low Pressure Oil System This type system is normally used for parallel compressors and uses three basic components Oil Separator Oil Reservoir and Oil Level R...

Page 27: ...pressure expansion valve with a range of 0 to 90 psig Temprite Part No is 67070000 An alternative valve manufactured by Sporlan is Model ADRI 11 4 0 90 Oil Level Regulators The AC R adjustable oil re...

Page 28: ...n the motor cavity on semi hermetic models the compressor will overfill The oil line sight glass is a good way to see how the separator is working Look for movement in the glass If the separator is no...

Page 29: ...strainers and filter driers 3 Install a replacement compressor and make a complete electrical check 4 Make sure the suction line adjacent to the compressor is clean Install a liquid line filter drier...

Page 30: ...r pressure The regulator closes as the condenser pressure drops below the set point thus back flooding the condenser and reducing the inside surface area available for condensing Valve B is and Outlet...

Page 31: ...utdoor temperature to allow the system pressures to drop below the regulator pressure settings Before adjusting make sure that all manual opening stems on the regulators are set for automatic operatio...

Page 32: ...0psig withonecompleteturnequal toapproximately4psichange Adjustmentsshouldbemade insmallincrements allowingforthesystemtostabilizeafter each turn 6 Vary the evaporator load to test at various conditio...

Page 33: ...connections Checkoperationandconditionofcontactsoncompressor fan motor contactors Check appearance of control panel interior Check appearance of exterior conduit junction boxes Check appearance of ins...

Page 34: ...tor Check stator If leads are all right replace stator Eliminate cause of excessive pressure Check oil level Correct binding Unit Operates Long Or Continuously 1 2 3 4 5 6 Control contacts sticking in...

Page 35: ...ters Check and reset for proper superheat Check means for regulating condensing temperature Check for proper sizing Little or No Oil Pressure 1 2 3 4 5 6 7 8 9 Clogged suction oil strainer Excessive l...

Page 36: ..._ Group __________________ Group _________________ Compressor Model Serial No __________________ __________________ Group __________________ Compressor Model Serial No __________________ _____________...

Reviews: