Heat & Glo • TRUE-36-IFT, TRUE-42-IFT, TRUE-50-IFT Installation Manual • 2461-980 Rev. Q • 11/20
24
Figure 4.9
Two Elbows
WARNING! Risk of Fire!
• TRUE-36(NG/P),TRUE-42(NG/P) and TRUE-50(NG/P) models require
a minimum of 36 inches of vertical venting before attaching any elbow
to the appliance for the venting configuration in Figure 4.7.
DO NOT attach elbow directly to the appliance.
H
2
H
1
INSTALLED
HORIZONTALLY
V
1
TRUE-36 (NG/P), TRUE-42 (NG/P),
TRUE-50 (NG/P)
V
1
Minimum
H
1
+ H
2
Maximum
3 ft
914 mm
18 in
457 mm
4 ft
1.2 m
3 ft
914 mm
5 ft
1.5 m
7 ft
2.1 m
6 ft
1.8 m
8 ft
2.4 m
7 ft
2.1 m
10 ft
3.0 m
8 ft
2.4 m
12 ft
3.7m
9 ft
2.7 m
14 ft
4.3 m
10 ft
3.0 m
16 ft
4.9 m
V
1
+ H
1
+ H
2
= 60 ft Maximum
H
1
+ H
2
= 20 ft Maximum