35
Heat & Glo • 6X-AU Installation Manual • 2508-980 Rev. C
• 3/18
7
Venting and Chimneys
A. Assemble Vent Sections
(DVP Pipe Only)
Attach Vent to the Firebox Assembly
Note:
The end of the pipe sections with the lanced tabs will
face toward the appliance.
Attach the first pipe section to the starting collar:
• Lanced pipe end of the starting collar.
• Inner pipe over inner collar.
• Push the pipe section until all lanced tabs snap in place.
• Lightly tug on pipe to confirm it has locked.
Figure 7.1 High Temperature Silicone Sealant
Figure 7.2
A
B
Figure 7.3
Assemble Pipe Sections
Per Figure 7.2:
• Start the inner pipe on the lanced end of section A into
the flared end of section B.
• Start the outer pipe of section A over the outer pipe of
section B.
• Once both vents sections are started, push firmly until
all lanced tabs lock into place.
• Lightly tug on the pipe to confirm the tabs have locked.
It is acceptable to use screws no longer than 1/2 in. (13
mm) to hold outer pipe sections together. If predrilling holes,
DO NOT
penetrate inner pipe.
For 90º and 45º elbows that are changing the vent direction
from horizontal to vertical, one screw minimum should be
put in the outer flue at the horizontal elbow joint to prevent
the elbow from rotating. Use screws no longer than 1/2
in. (13 mm). If predrilling screw holes,
DO NOT
penetrate
inner pipe.
WARNING! Risk of Fire or Explosion! DO NOT
break
silicone seals on slip sections. Use care when remov-
ing termination cap from slip pipe. If slip section seals
are broken during removal of the termination cap, vent
could leak.
Figure 7.4 Seams
Note:
Make sure that the seams are not aligned to prevent
unintentional disconnection.
INCORRECT
CORRECT
Lances
Required Commercial, Multi-family (Multi-level exceeding
two stories), or High-Rise Applications
All outer pipe joints must be sealed with 100% silicone
(300º F minimum continuous exposure rating), including
the slip section that connects directly to the horizontal ter-
mination cap.
• Apply a bead of silicone sealant (300 ºF (149 °C) mini-
mum continuous exposure rating) inside the female
outer pipe joint prior to joining sections. See Figure
7.1.
OR
Apply a bead of silicone sealant (300 ºF (149 °C) mini-
mum continuous exposure rating) to the outside of
connecting joint after joining sections
OR
Apply aluminum foil tape (300 ºF (149 °C) minimum
continuous exposure rating) to the outside of connect-
ing joint after joining sections. On horizontal pipe runs,
it is recommended that the tape seam is positioned on
the bottom side of the vent pipe.
• Only outer pipes need to be sealed. All unit collar, pipe,
slip section, elbow and cap outer flues shall be sealed
in this manner, unless otherwise stated.