background image

Heat & Glo  •  6X-AU Installation Manual  •  2508-980  Rev. C

 

•  3/18

28

Rear Vent  - Vertical Termination - (continued)

Three Elbows

Figure 4.25

Three Elbows

Figure 4.26

INSTALLED

HORIZONTALLY

H

3

H

1

H

2

V

1

V

2

V

1

H

2

H

1

H

1

 Maximum  

  V

1

 Minimum

H

2

H

1

 + H

2

 Maximum

2 ft.

610 mm

6 in.

152 mm

2 ft.

610 

mm

4 ft.

1.2 m

3 ft.

914 mm

1 ft.

305 mm

4 ft.

1.2 m

7 ft.

 2.1 m

5 ft.

1.5 m

2 ft.

610 mm

6 ft.

1.8 m

11 ft.

3.4 m

7 ft.

 2.1 m

3 ft.

914 mm

8 ft.

2.4 m

15 ft.

 4.6 m

8 ft

2.4 m

4 ft.

1.2 m

10 ft.

3.1 m

18 ft.

5.5 m

H

1

= 8 ft (2.4 m) Max.      V

1

 + V

2

 + H

1

 + H

2

= 40 ft (12.2 m) Max.

H

1

 + H

2

 = 20 ft (6.1 m) Max.

H

1

H

2

H

3

V

1

 Minimum

H

1

 + H

2

 + H

3

  Maximum

*

*

*

8 ft.

2.4 m

6 ft.

1.8 m

*

*

*

9 ft.

2.7 m

7 ft.

 2.1 m

*

*

*

10 ft.

3.1 m

8 ft.

2.4 m

*

*

*

10 ft.

3.1 m

8 ft.

2.4 m

V

1

 + H

1

 + H

2

 + H

3

 = 40 ft. (12.2 m) Maximum

 *No specific restrictions on this value EXCEPT

 V

1

 + H

1

 + H

2

 + H

3

 cannot exceed 40 ft. (12.2 m) Maximum

H

1

 + H

2

 + H

3

 = 8 ft. (2.4 m) Maximum

Summary of Contents for 6X-AU

Page 1: ...her flam mable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire de...

Page 2: ...mney Diagram 14 C Approved Pipe 15 D Use of Elbows 15 E Measuring Standards 16 F Vent Diagrams 17 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 29 B Wall Penetration Framing Firestops 29 C Ceiling Firestop Floor Penetration Framing 30 D Install Attic Insulation Shield 30 6 Appliance Preparation A Vent Collar Preparation 31 B Installing Optional Heat Zone 240V 33 C Securing and Le...

Page 3: ...Section 9 Pg 43 44 Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure verified ___________________________ Verified proper air shutter setting for installation type ___________________________ Finishing Section 10 Pg 45 48 Combustible materials not installed in non combustible areas _____________...

Page 4: ...3 h Maximum Gas Consumption 40 60 MJ h 40 10 MJ h 30 60 MJ h Burner Injector 0 124 DMS 3 150 mm 49 DMS 1 854 mm 53 DMS 1 511 mm Pilot Injector Ø 023 584 mm Ø 014 356 mm Ø 010 254 mm The allowable Outlet Manifold Gas Pressure ranges are Natural Gas 80 95 kPa and ULPG 2 37 2 61 kPa Gas types only through field conversions NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and app...

Page 5: ...ng entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC 1382 F shall be con sidered non combustible materials F Combustible Materials Specification Materials made of or surfaced with wood compressed pa per plant fibers plasti...

Page 6: ...ric drill and bits 1 4 in 6 mm Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non corrosive leak check solution 1 2 3 4 in 13 19 mm length 6 or 8 Self drilling screws Caulking material 300 ºF 149 ºC minimum continuous exposure rating One 1 4 in 6 mm female connection for optional fan Improper installation adjustment alteration service or maintenance can cause injury or pr...

Page 7: ...ir safe operation DO NOT install damaged in complete or substitute components Keep appliance dry Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged appliance or vent system component Modification of the appliance or vent system Installation other than as instructed by Hearth Home Technologies Improp...

Page 8: ... Location Inches Millimeters K 11 11 16 297 L 28 1 2 724 M 14 1 4 362 N 8 1 2 216 O 2 7 8 73 P 8 1 2 216 Q 1 25 R 40 7 8 1038 S 14 3 16 360 T 15 3 8 391 Appliance Dimensions Table A B C D E FRONT VIEW TOP VIEW LEFT SIDE RIGHT SIDE F G H I J K L M O P GAS LINE ACCESS Q R N HEAT ZONE 240V ACCESS LEFT RIGHT SIDES S T ELECTRICAL ACCESS C L N Location Inches Millimeters A 41 1041 B 36 1 8 918 C 33 1 2 ...

Page 9: ...ont Dimensions Firescreen and Clean Face CLEAN FACE DECORATIVE FRONT A B F G E D C A B C D E F G 6X AU FS 7 in 34 28 3 4 35 15 16 1 5 8 2 5 8 30 5 8 32 1 4 mm 864 730 913 41 67 778 819 G A B C D E F A B C D E F G 6X AU CF 36 in 31 9 16 22 1 8 35 13 16 4 5 8 6 15 16 26 3 4 31 7 16 mm 802 562 910 117 176 679 799 ...

Page 10: ...dividual design preference Figure 3 3 Appliance Locations 1 2 IN REAR VENT HORIZONTAL TERMINATION TWO ELBOWS REAR VENT NO ELBOWS REAR VENT ONE ELBOW ALCOVE INSTALLATION TOP VENT ONE 90º ELBOW A B C B E B B B D D F G H D A D NOTE THE REAR STANDOFF MAY NEED TO BE REMOVED WHEN VENTING AT 45º Refer to Section 10 B for mantel and wall projection information Consider the mantel or cabinet system to be i...

Page 11: ...MUM FRAMING DIMENSIONS Models A B C D E F G H I J Rough Opening Width Rough Opening Height Rough Opening Depth Rough Opening Width Clearance to Ceiling Measured from top of appliance opening Combustible Floor Combustible Flooring Behind Appliance Sides of Appliance Front of Appliance 6X AU in 10 40 1 8 22 42 32 0 0 1 2 1 2 36 mm 254 1045 595 1070 813 0 0 13 13 914 COMBUSTIBLE FLOORING MAY BE INSTA...

Page 12: ... prevent drafts and air leakage the wall shield and ceiling firestops should be caulked with caulk with a minimum of 300 ºF 149 ºC continuous exposure rating to seal gaps Gas line holes and other openings should be caulked with caulk with a minimum of 300 ºF 149 ºC continuous exposure rating or stuffed with unfaced insula tion If the appliance is being installed on a cement surface a layer of plyw...

Page 13: ...h the decorative cap cover A B 6 in minimum up to 20 in 152 mm 508 mm 18 in minimum 457 mm 20 in and over 0 in minimum In a staggered installation with both gas and wood or fuel oil terminations the wood or fuel oil termination cap must be higher than the gas termination cap Figure 4 1 Minimum Height From Roof To Lowest Discharge Opening H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING V...

Page 14: ... a Below eaves balconies or other projections MIN CLEARANCE in mm Appliances up to 50 MJ h input 12 305 Appliances over 50 MJ h input 20 1 2 521 b From the ground or above a balcony 12 305 c From a return wall or external corner 20 1 2 521 d From a gas meter M 39 991 e From an electricity meter or fuse box P 20 1 2 521 f From a drain or soil pipe 6 152 g Horizontally from any building structure un...

Page 15: ... vertical and horizontal vent as pects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect See Figure 4 4 Two 45º elbows may be used in place of one 90º elbow On 45º runs one foot of diagonal is equal to 8 1 2 in 216 mm horizontal run and 8 1 2 in 216 mm vertical run A length of straight pipe is allowed between two 45º elbows See Figure 4 4 Figur...

Page 16: ...g the following standards Pipe measurements are shown using the effective length of pipe See Section 12 A for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap see Figure 4 6 Vertical terminations are measured to top of last section of pipe See Figure 4 7 Horizontal pipe installed level with no rise MEA...

Page 17: ...ld firestop must be installed When penetrating a combustible ceiling a ceiling firestop must be installed Horizontal runs of vent do not require vertical rise horizontal runs may be level Horizontal termination cap should have a 1 4 in 6 mm downward slant to allow any moisture in cap to be released See Figure 4 8 W A L L 1 4 in max 6 mm WARNING Fire Risk Explosion Risk Do NOT pack insulation or ot...

Page 18: ... and Terminations HORIZONTAL TERMINATION WALL FIRESTOP 90 DEGREE ELBOW VERTICAL TERMINATION STORM COLLAR ROOF FLASHING HORIZONTAL PIPE SUPPORT PIPE LENGTH WALL BRACKET CEILING FIRESTOP DVP SERIES DVP TRAP2 DVP TVHW Flue system termination kits DVP FBHT Flue Components and Terminations ...

Page 19: ...0 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 3 ft 914 mm 11 ft 3 4 m 4 ft 1 2 m 16 ft 4 9 m 5 ft 1 5 m 20 ft 6 1 m V1 H1 40 ft 12 2 m Maximum H1 20 ft 6 1 m Maximum 6X AU ULPG V1 Minimum H1 Maximum 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 6 ft 1 8 m 4 ft 1 2 m 8 ft 2 4 m 5 ft 1 5 m 10 ft 3 0 m V1 H1 40 ft 12 2 m Maximum H1 10 ft 3 0 m Maximum ...

Page 20: ... 305 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 8 ft 2 4 m 4 ft 1 2 m 12 ft 3 7 m 6 ft 1 8 m 20 ft 6 1 m V1 H1 H2 40 ft 12 2 m Maximum H1 H2 20 ft 6 1 m Maximum Figure 4 11 6X AU ULPG V1 Minimum H1 H2 Maximum 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 3 ft 914 mm 3 ft 914 mm 5 ft 1 5m 4 ft 1 2 m 7 ft 2 1 m 6 ft 1 8 m 11 ft 3 4 m V1 H1 H2 40 ft 12 2 m Maximum H1 H2 11 ft 3 4 m Maximum ...

Page 21: ... 610 mm 8 ft 2 4 m 2 ft 610 mm 8 ft 2 4 m 3 ft 914 mm 12 ft 3 7 m 3 ft 914 mm 12 ft 3 7 m 4 ft 1 2 m 16 ft 4 9 m 4 ft 1 2 m 16 ft 4 9 m H1 H2 20 ft 6 1 m Maximum V1 V2 H1 H2 40 ft 12 2 m Maximum 6X AU ULPG V1 Min H1 Max V2 Min H2 Max 1 ft 305 mm 2 ft 610 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 6 ft 1 8 m 3 ft 914 mm 6 ft 1 8 m 4 ft 1 2 m 8 ft 2 4 m 4 ft...

Page 22: ...mount of vertical you have in the system with the chart to find the appropriate position to set the flue restrictor See Figure 4 15 and 4 16 4 Center the two flue restrictor pieces on the vent at the setting selected in step 3 and secure in place by using two self tapping screws See Figure 4 14 5 Reinstall the refractory Figure 4 15 Vertical TOP VENT REAR VENT NG LP ULPG NG LP ULPG 4 ft 1 2 m 1 1 ...

Page 23: ...S TO THE RIGHT FLUE RESTRICTOR SET TO 4 4 4 5 5 4 3 2 1 Figure 4 16 Setting the Flue Restrictor Figure 4 17 Two Elbows H1 V1 V2 V1 H1 Maximum V2 V1 V2 Min Elbow only 2 ft 610 mm 6 in 152 mm 6 ft 1 8 m 2 ft 610 mm 11 ft 3 4 m 3 ft 914 mm 16 ft 4 9 m 4 ft 1 2 m 20 ft 6 1 m V1 V2 H1 50 ft 15 2 m Maximum No specific restrictions on this value EXCEPT V1 V2 H1 cannot exceed 50 ft 15 2 m ...

Page 24: ... Minimum H1 H2 Maximum Elbow only 1 ft 305 mm 1 ft 305 mm 6 in 152 mm 2 ft 610 mm 2 ft 610 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 3 ft 914 mm 9 ft 2 7 m 9 ft 2 7 m 4 ft 1 2 m 18 ft 5 5 m 18 ft 5 5 m H1 H2 20 ft 6 1 m Maximum V1 V2 H1 H2 40 ft 12 2 m Maximum No specific restrictions on this value EXCEPT V1 V2 H1 H2 cannot exceed 40 ft 12 2 m ...

Page 25: ...980 Rev C 3 18 Rear Vent Horizontal Termination Figure 4 19 Figure 4 20 No Elbow One 45º Elbow H1 H1 H1 Maximum NG LP 6X AU 16 in 406 mm Do not use a 45º elbow in corner installations Use two 90º elbows instead H1 Maximum ULPG 6X AU 12 in 305 mm ...

Page 26: ...7 ft 2 1 m 10 ft 3 0 m 3 ft 914 mm 4 ft 1 2 m 12 ft 3 7 m 15 ft 4 6 m 3 ft 914 mm 5 ft 1 5 m 17 ft 5 2 m 20 ft 6 1 m V1 H1 H2 40 ft 12 2 m Maximum H1 3 ft 914 mm Maximum H1 H2 20 ft 6 1 m Maximum H1 Maximum V1 Minimum H2 H3 H1 H2 H3 Max 0 ft 0 mm Back to Back 90º Elbows 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 6 in 152 mm 1 5 ft 457 mm 2 5 ft 762 mm 2 ft 610 mm 1 ft 305 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 9...

Page 27: ... 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 7 ft 2 1 m 4 ft 1 2 m 8 ft 2 4 m 5 ft 1 5 m 8 ft 2 4 m V1 H1 40 ft 12 2 m Maximum H1 8 ft 2 4 m Maximum V1 Minimum H1 H2 Maximum Back to Back 90º Elbows 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 4 ft 1 2 m 9 ft 2 7 m 6 ft 1 8 m 12 ft 3 7 m 8 ft 2 4 m 15 ft 4 6 m V1 H1 H2 40 ft 12 2 m Maximum H1 H2 15 ft 4 6 m Maximum Figure 4 24 ...

Page 28: ... ft 1 2 m 7 ft 2 1 m 5 ft 1 5 m 2 ft 610 mm 6 ft 1 8 m 11 ft 3 4 m 7 ft 2 1 m 3 ft 914 mm 8 ft 2 4 m 15 ft 4 6 m 8 ft 2 4 m 4 ft 1 2 m 10 ft 3 1 m 18 ft 5 5 m H1 8 ft 2 4 m Max V1 V2 H1 H2 40 ft 12 2 m Max H1 H2 20 ft 6 1 m Max H1 H2 H3 V1 Minimum H1 H2 H3 Maximum 8 ft 2 4 m 6 ft 1 8 m 9 ft 2 7 m 7 ft 2 1 m 10 ft 3 1 m 8 ft 2 4 m 10 ft 3 1 m 8 ft 2 4 m V1 H1 H2 H3 40 ft 12 2 m Maximum No specific ...

Page 29: ...rances are maintained by using a DVP WS DVP pipe See Figure 5 2 for framing instructions For external walls The wall shield firestop is included with the termination cap assembly For internal walls A wall shield firestop must be pur chased and installed The opening must be framed on all four sides using the same size framing materials as those used in the wall construction DVP pipe A wall shield f...

Page 30: ...erheating Figure 5 3 Installing Ceiling Firestop Generic Fireplace Shown Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING ATTIC ABOVE A PIPE DVP A 10 in 254 mm A D Install Attic Insulation Shield WARNING Fire Risk DO NOT allow loose materials or insul...

Page 31: ...pliance Shown Cut the seal ap strap across the rectangles next to the disk For rear vent skip this step Figure 6 2 Generic Appliance Shown Remove the white gasket material covering the seal cap Figure 6 4 Generic Appliance Shown Remove the in sulation basket and white insulation from the center vent pipe Figure 6 5 Generic Appliance Shown Remove the insulation from the outer vent pipe For rear ven...

Page 32: ... band out and use to remove the seal cap Figure 6 10 GenericAppliance Shown Discard the vent cap remove and discard the insulation basket NOTICE Once the seal cap has been removed it CANNOT be reattached Figure 6 6 Generic Appliance Shown To attach the first section of vent pipe make sure to use the fiberglass gasket in the manual bag to seal between the first vent component and the outer fireplac...

Page 33: ... Installing Optional Heat Zone 240V Remove the knockout from the fireplace and discard it See Figure 6 12 Center the duct collar around the exposed hole and attach it to the fireplace with 3 screws Note Do this BEFORE final positioning of fireplace Determine the location for the air register fan housing assembly Reference the appropriate instructions included with the kit for the remaining install...

Page 34: ...ming members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Level the appliance from side to side and front to back Square the unit by securing diagonal dimensions to within 1 4 in 6 mm of each other See Figure 6 13 Shim the appliance as necessary It is acceptable to use wood shims underneath the appliance Secure the appliance to the f...

Page 35: ...ng Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from slip pipe If slip section seals are broken during removal of the termination cap vent could leak Figure 7 4 Seams Note Make sure that the seams are not aligned to prevent unintent...

Page 36: ...with no offsets must be supported every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal runs must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 7 5 and 7 6 Wall shield f...

Page 37: ...emble and Install Storm Collar CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are sharp Slide the storm collar onto the exposed pipe section and align brackets Insert a bolt provided through the brackets and install nut Do not completely tighten Slide the assembled storm collar down the pipe section until it rests on...

Page 38: ...ust overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 16 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall thickness is less than 4 in 102 mm DVP the heat ...

Page 39: ...IN OVERLAP SHEATHING VENT DEPTH FROM BACK OF APPLIANCE TO OUTSIDE SURFACE OF EXTERIOR WALL SEE CHART BELOW SLIP SECTION CAN BE EXTENDED INNER VENT OUTER VENT EXTERIOR Note When using termination caps with factory supplied heat shield attached no additional wall shield firestop is required on the exterior side of a combustible wall Install Horizontal Termination Cap WARNING Risk of Fire The telesco...

Page 40: ...Installation If installed in a windy environment over 50KPH with a SLP TRAP SLP TRAP2 or DVP TRAP2 horizontal termination cap the provided wind diverter may be bent and installed as show in Figures 7 14 and 7 15 Figure 7 14 Wind Diverter Figure 7 15 Wind Diverter Installed ...

Page 41: ...in bathrooms or near sinks Low voltage and 220 240 VAC voltage cannot be shared within the same wall box 8 Electrical Information Electrical Service and Repair WARNING Risk of Shock Label all wires prior to dis connection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105 ...

Page 42: ...he appliance junction cord to supply power to the unit OR install 4 AA cell batteries not included into the battery pack before use B Wiring Requirements NOTICE Batteries should only be used as a power source in the event of an emergency power outage Batteries should not be used as a primary long term power source Battery polarity must be correct when installing batteries When using batteries as a...

Page 43: ...2 psig WARNING D High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction When installing above 2000 ft 610 m elevation Reduce input rate 4 for each 1000 ft 305 m above 2000 ft 610 m Note This appliance does include a manual gas shutoff valve that is located in the valve compart...

Page 44: ... be adjusted by a qualified ser vice technician at the time of installation The air shutter is set at the factory for minimum vertical vent run Adjust air shutter for longer vertical runs See Figure 9 1 Loosen the wing nut Move the air handle to the left to open the air shutter Move the air handle to the right to close the air shutter Tighten the wing nut NOTICE If sooting occurs provide more air ...

Page 45: ...earances Comply with all minimum clearances to combustibles as specified in this manual Overlapping materials could ignite and will interfere with proper operation of doors and louvers NOTICE Surface temperatures around the appliance will become warm while the appliance is in operation Ensure finishing materials used for all surfaces floor walls mantels etc will withstand temperatures up to 190 F ...

Page 46: ..._____ A Inches 2 7 16 3 7 16 4 7 16 5 7 16 6 7 16 7 7 16 Millimeters 62 87 113 138 164 189 B Inches 1 2 3 4 5 Millimeters 25 51 76 102 127 Note Measurement is taken from top of the opening NOT the top of the fireplace Mantels Combustible or Painted Surfaces Mantel Legs or Wall Projections Figure 10 5 Clearances to Mantel Leg or Wall Projections Acceptable on both sides of opening Figure 10 4 Minim...

Page 47: ...is going to be used on the fireplace you may use the table below which shows the decorative front models and the finishing material thickness allowed Note Finishing strips may be used to aid in positioning of non combustible facing materials for some of the facing and decorative front combinations specified in the table below They must be removed following finishing work These can be ordered from ...

Page 48: ...rial to Bottom of Fireplace A Outside decorative front width B C Includes 1 8 in 3 mm opening each side of decorative front D NON COMBUSTIBLE FINISHING MATERIAL Figure 10 8 CF Inside Fit NON COMBUSTIBLE FINISHING MATERIAL Figure 10 7 Finishing Material Thickness Greater Than 1 in 25 mm DECORATIVE FRONT FINISHING MATERIAL FINISHING MATERIAL 6X AU Inches Millimeters A 37 1 16 941 B 34 1 16 865 C 37 ...

Page 49: ...emoved before appliance is fired WARNING Risk of Fire Close the ball valve before in stalling the splatter guard to prevent accidental lighting Remove the splatter guard before lighting the appliance Figure 11 1 Fixed Glass Assembly Removing Fixed Glass Assembly Pull the four glass assembly latches out of the groove on the glass frame Remove glass door from the appliance See Figure 11 1 GLASS ASSE...

Page 50: ...position back towards rear glass panel as shown in Figure 11 3 Figure 11 4 Install Side Glass Retention Bracket 3 Install side glass panel in front of insulation board 4 Install side refractory bracket between the insulation board and the side of the firebox Secure with screw as shown in Figure 11 4 5 Bend side refractory tab over glass panel See Fig ure 11 4 6 Slide other insulation board on oppo...

Page 51: ...aken not to block the lighting trail of ports Embers may only be placed in areas as shown in Figure 11 7 and Figure 11 8 LP ULPG Only LP ULPG Only Using dime size pieces of Glowing Embers overlap the burner ports as shown in Figure 11 9 The impingement created by the embers will help blend the fire Save the remaining ember materials for use during appliance servicing The embers provided should be ...

Page 52: ... Technologies part number TUP GBK 12 See below for fogging tips Prior to painting take precautions to prevent any overspray from reaching the pilot assembly Fogging Tips Apply paint with the ember lights turned on This will help you avoid over fogging or under fogging Reduce the lighting in the room while applying the paint Fog the Teco Sil to create a realistic coal bed appear ance Allow the pain...

Page 53: ... tabs engaged see Figure 6 Figure 5 Figure 1 LOG PLACEMENT TABS Figure 3 LOG PLACEMENT SLOTS LOG PLACEMENT TABS Figure 6 Figure 6 shows the log placement tabs located on the top of Log 1 The tabs will be mated with the slots located on the bottom of Log 2 and Log 3 see Figure 7 Log 2 and Log 3 also have grooves that allow the logs to be seated properly on the grate see Figure 7 Hold Log 1 upright ...

Page 54: ...ntation see Figure 10 Nose of log 4 should be pulled to fit securely against right hand side of log indentation Log 4 SRV2164 704 ULPG FUEL Place Log 4 in the left log indentation on the burner top see Figure 4 Slide Log 4 to the rear and to the left under Log 2 to fit securely against the rear of the indentation and left until it stops RIGHT GRATE TINE 4 2 1 Figure 10 NOSE Log 2 SRV2164 702 Mate ...

Page 55: ...crew on the top of the burner see Figure 3 Log 6 SRV2164 706 Mate the groove located on the lower end of Log 6 with the fourth grate tine from left to right as shown in Figure 12 Set the other end of Log 6 on the flat area located on top of Log 4 see Figure 11 Log 6 will also rest against center grate tine When properly installed Log 6 will rest securely on all 3 contact points not allowing moveme...

Page 56: ...appliance Pull out and latch the four glass assembly latches into the groove on the glass frame See Figure 11 1 J Install Decorative Front WARNING Risk of Fire Install ONLY doors or fronts approved by Hearth Home Technologies Unapproved doors or fronts could cause fireplace to overheat This fireplace has been supplied with an integral barrier to prevent direct contact with the fixed glass panel DO...

Page 57: ...m 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 124 mm 13 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm DVP WS Wall Shield Firestop Finished Heigh...

Page 58: ... mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield A Vent Components Diagrams continued Figure 12 2 DVP Vent Components Term Cap Minimum Effective Length Maximum Effective Leng...

Page 59: ...of Flashing Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield A Vent Components Diagrams continued Figure 12 3 DVP Vent Components ...

Page 60: ...14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap A Vent Components Diagrams continued Figure 12 4 DVP Vent Components 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm DVP HRC SS 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC ZC SS ...

Page 61: ...ne 240V Kit Follow the instruction supplied with the kit for operation Preparation of the appliance for installation of the kit is discussed in Section 6 B Contact your dealer if you have questions Optional Fiber Refractory Kit Follow the instructions supplied to install the kit Contact your dealer if you have questions Printed in U S A Copyright 2018 Heat Glo a brand of Hearth Home Technologies 7...

Reviews: