059063–00 REV. C
|
25
10
INSTALLER MENU SEQUENCE
----- SETTINGS ------
Season
Winter
<Outdoor Rst>
135 F
Set Point
135 F
EMS Set Point
135 F
Min Return
110 F
<System Settings>
<Maintenance>
<System Startup>
BACK
SELECT
---- SEASON ---
Winter
Summer
BACK
SAVE
-- OUTDOOR RESET -
Reset Ratio
7
Target 0 F
Outdoor Cutoff
65 F
Min.Target
120 F
Max.Target
120 F
BACK
SELECT
---- RESET RATIO ---
Custom
1(8.00 OD:1.00 SYS)
2(4.00 OD:1.00 SYS)
3(3.00 OD:1.00 SYS)
4(2.00 OD:1.00 SYS)
5(1.50 OD:1.00 SYS)
6(1.25 OD:1.00 SYS)
7(1.00 OD:1.00 SYS)
8(1.00 OD:1.25 SYS)
9(1.00 OD:1.50 SYS)
10(1.00 OD:2.00 SYS)
11(1.00 OD:3.00 SYS)
12(1.00 OD:4.00 SYS)
BACK
SAVE
-- SET SYS TEMP.1 -
100 F
[
]
BACK
SAVE
-- AT OD TEMP.1 ---
70 F
[
]
BACK
SAVE
-- SET SYS TEMP.2 -
170 F
[
]
BACK
SAVE
-- AT OD TEMP.2 ---
0 F
[
]
BACK
SAVE
-- TARGET OFFSET ---
+0 F
[
]
BACK
SAVE
-- OUTDOOR CUTOFF --
70 F
[
]
BACK
SAVE
---- MIN TARGET ----
70 F
[
]
BACK
SAVE
---- MAX TARGET ----
240 F
[
]
BACK
SAVE
----- SET POINT -----
70 F
[
]
BACK
SAVE
-- EMS SET POINT --
140 F
BACK
SAVE
- SYSTEM SETTINGS -
<Stage Settings>
<Setback Schedule>
<DHW Settings>
Setback
0 F
Run-On
2min
Pump Exercise Off
BACK
SELECT
---- MIN RETURN ----
120 F
[
]
BACK
SAVE
---- RETURN LAG ----
2min
[
]
BACK
SAVE
--- PUMP EXERCISE --
Off
On
BACK
SAVE
------- RUN-ON -------
2min
[
]
BACK
SAVE
------ SETBACK -------
0 F
[
]
BACK
SAVE
-- DHW SETTINGS ---
DHW Temp.
120 F
DHW
Prior
Tmr 60min
DHW Set Point
120 F
DHW Diff.
5 F
BACK
SELECT
DHW PRIORITY TIMER
30min
[
]
BACK
SAVE
-- DHW SET POINT --
120 F
[
]
BACK
SAVE
DHW DIFFERENTIAL
10 F
[
]
BACK
SAVE
SYS=
168
F OD=
45
F
TGT=172 F
ABC
<EFG >
----
LO
BOILER
MENU
DHW SETTINGS
SET POINT
RESET RATIO