58
|
059063–00 REV. C
13
BACNET
DESCRIPT
ID
OBJECT
TYPE
VALUE
NAME
UNITS
VALUE
MIN
VALUE
MAX
DEFINITION
Standby Delay
1700
Analog
Read /
Write
STNDLY
Minutes
1
60
Integer Values Only (1,2,…)
Last Stage Hold
1800
Analog
Read /
Write
LSTHD
Degree F
0
30
Integer Values Only (0,1,2…)
Lead Boiler
1900
MultiState
Value
Read
Only
LEAD
1
16
Represents the current lead boiler
Rotate Mode
2000
MultiState
R/W
ROT
Hours
1
3
Rotate Period
2100
Analog
Read /
Write
ROTPER
Hours
1
999
Hours since last rotation Interger
Values Only (1,2,3…)
Setback
2200
Analog
Read /
Write
SEATBAC
Degree F
0
80
Integer Values Only (0,1,2…)
Boost
2300
Analog
Read /
Write
BOOST
Degree F
0
80
Disable or 30 minutes
Boost Period
2400
Analog
R/W
BSTPER
Minutes
1
120
Time
2500
Analog
Read
TIME
Minutes
1
1440
Time since midnight Integer
Values Only (1,2,3…)
Day Schedule
2600
Analog
Read /
Write
DSCHED
Minutes
1
1440
Time since midnight Integer
Values Only (1,2,3…)
Night Schedule
2700
Analog
Read /
Write
NSCHED
Minutes
1
1440
Time since midnight Integer
Values Only (1,2,3…)
DHW Set Point
2800
Analog
Read /
Write
DHWSP
Degree F
140
200
Integer Values Only (0,1,2…)
DHW Differential
2900
Analog
R/W
DHWDIFF
Degree F
5
80
Run On
3000
Analog
Read /
Write
RUNON
Minutes
0
60
Integer Values Only (0,1,2,…)
System Relay
3100
Binary
Value
Read
Only
SYSRLY
True
False
True – Energized False =
De-Energized
DHW Pump
Relay
3200
Binary
Read
DHWRLY
Air Dump relay
3300
Binary
Read
DAMPRLY
Boiler A
Modulating
Output
3400
Analog
Read
Only
MODA
Percent
0
100
Modulation: = 0% -100%,
Boiler B
Modulating
Output
3500
Analog
Read
Only
MODB
Percent
0
100
Boiler C
Modulating
Output
3600
Analog
Read
Only
MODC
Percent
0
100
Boiler D
Modulating
Output
3700
Analog
Read
Only
MODD
Percent
0
100
Boiler E
Modulating
Output
3800
Analog
Read
Only
MODE
Percent
0
100