INSTALLER MENU SEQUENCE
SET POINT
(NOT ADJUSTABLE IN EMS MODE)
Adjustable -10ºF/-23ºC - 230ºF/110ºC
Default:
70ºF/21ºC
Button:
MENU/Set Point
In Set Point or EMS 4–20mA
•
The Set point is the temperature value the SQ-Elite-8T will use to control the system.
•
The SQ-Elite-8T will add, subtract, or hold the stages of the heating or cooling units to
maintain the system temperature around the Set point.
•
The system temperature can be expected to fluctuate around the set point. The amount
of fluctuation depends on the System Settings and Stage Settings.
•
If the EMS Mode was Enabled, the Set Point will be set by the EMS/BMS system and will
be available to be only read.
•
The range of Set Point in the EMS is set in the Startup menu at 4mA and 20mA.
•
Any reading below the 2mA or above 22mA will indicate a “
Shutdown by EMS
”
message on the Message Line.
RESET RATIO
Custom, 1(8.00ºOD : 1.00ºSys) to 12 (4.00ºOD : 1.00ºSys)
Default:
1(1.00ºOD : 1.00ºSys)
Button:
MENU/Outdoor Reset/Reset Ratio
In Outdoor Reset Only
•
The Reset Ratio applies only to Heating applications.
•
The Reset Ratio determines how the System water temperature will vary with the outside
temperature. With any of the ratios, the colder it becomes outside, the hotter the
temperature of the system water. (See Understanding Operation Concept on page 6).
•
With a 1.00 (OD):4.00 (SYS) ratio, the System water temperature (SYS) will increase
rapidly as the outside temperature falls, hitting the Maximum of 240°F at 35°F outside
temperature. With a 4.00 (OD):1.00 (SYS) ratio, the System water temperature (SYS) will
increase slowly as the outside temperature falls. Even at -30°F, the system water will only
be 125°F, and at 22°F outside, the system water will be 112°F. Such a low Reset Ratio
might be used with radiant floor heating applications.
•
With most baseboard heating applications, a 1.00 (OD):1.00 (SYS) setting is a good place
to start. With a 1.00 (OD):1.00 (SYS) ratio, for every degree the outside temperature falls,
the system water temperature is increased one degree.
•
If required:
Adjust the Reset Ratio in cold weather
. If the ambient building Warmer
temperatures are too cold in cold weather, move the ratio to a higher selection. That is, if
1.00 (OD):1.00 (SYS) was initially selected, change the selection to 1.00 (OD):1.25 (SYS).
If the building temperatures are too warm in cold weather, move the ratio to a lower
selection. That is, if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to
1.25 (OD):1.00 (SYS).
----- SET POINT -----
70 F
[
]
BACK
SAVE
---- RESET RATIO ---
Custom
1(8.00 OD:1.00 SYS)
2(4.00 OD:1.00 SYS)
3(3.00 OD:1.00 SYS)
4(2.00 OD:1.00 SYS)
5(1.50 OD:1.00 SYS)
6(1.25 OD:1.00 SYS)
7(1.00 OD:1.00 SYS)
8(1.00 OD:1.25 SYS)
9(1.00 OD:1.50 SYS)
10(1.00 OD:2.00 SYS)
11(1.00 OD:3.00 SYS)
12(1.00 OD:4.00 SYS)
BACK
SAVE
Outdoor Temperature
W
at
er
T
em
per
at
ur
e
70
40
50
60
130
120
110
100
Outdoor Temperature
W
at
er
T
em
per
at
ur
e
70
40
50
60
110
100
90
80
Outdoor Temperature
W
at
er
T
em
per
at
ur
e
70
40
50
60
150
140
130
120
1:4
With a 0° Offset, the
ratio curves begin at
100° Water Temperature.
With a -20° Offset, the
ratio curves begin at
80° Water Temperature.
With a +20° Offset, the
ratio curves begin at
120° Water Temperature.
1:4
1:4
1:1
1:1
1:1
4:1
4:1
4:1
90
100
+20 Offset
-20 Offset
Water Temperature
70
60
50
40
Outdoor Temperature
130
120
110
100
1:4
1:1
4:1
Colder
Warmer
----- SET POINT -----
70 F
[
]
BACK
SAVE
---- RESET RATIO ---
Custom
1(8.00 OD:1.00 SYS)
2(4.00 OD:1.00 SYS)
3(3.00 OD:1.00 SYS)
4(2.00 OD:1.00 SYS)
5(1.50 OD:1.00 SYS)
6(1.25 OD:1.00 SYS)
7(1.00 OD:1.00 SYS)
8(1.00 OD:1.25 SYS)
9(1.00 OD:1.50 SYS)
10(1.00 OD:2.00 SYS)
11(1.00 OD:3.00 SYS)
12(1.00 OD:4.00 SYS)
BACK
SAVE
Outdoor Temperature
W
at
er
T
em
per
at
ur
e
70
40
50
60
130
120
110
100
Outdoor Temperature
W
at
er
T
em
per
at
ur
e
70
40
50
60
110
100
90
80
Outdoor Temperature
W
at
er
T
em
per
at
ur
e
70
40
50
60
150
140
130
120
1:4
With a 0° Offset, the
ratio curves begin at
100° Water Temperature.
With a -20° Offset, the
ratio curves begin at
80° Water Temperature.
With a +20° Offset, the
ratio curves begin at
120° Water Temperature.
1:4
1:4
1:1
1:1
1:1
4:1
4:1
4:1
90
100
+20 Offset
-20 Offset
Water Temperature
70
60
50
40
Outdoor Temperature
130
120
110
100
1:4
1:1
4:1
Colder
Warmer