MODBUS Installation and Operation Manual

 

 

11

HT# 059266-00A

note:

   All variables are stored as ‘Holding Registers’ .  MODBUS functions :

   

• ‘Read Holding Registers’ (function code 3), 

   

• ‘Write Single Register' (function code 6), 

   

• and ‘Write Multiple Registers’ (function code 16) are supported .

note:

   All variables with multiple UOM’s depend upon the value of ‘Input Mode’ to determine which to use .

note:

   Use 'District Steam Delay' when 'Operating Mode' is set to District Steam .  Use 'System Setpoint', 

'System Differential' and 'Thermal Lockout Enable' when 'Operation Mode' is set to Burner/valve .

note:

   Use 'Vari-Boost Adjustment' when 'Boost Mode' is set to Vari-Day or Vari+ESD .  Use 

'Manual Boost Time' when 'Vari-Boost Adjustment' is set to Manual Boost .

note:

   The MPC Platinum has a schedule, which is 7-days, 4 day/night pairs per day .  For example: Register 

38 is the first DAY schedule of Monday; Register 39 is the first NIGHT schedule of Monday; Register 46 

is the first DAY schedule of Tuesday; Register 47 is the first NIGHT schedule of Tuesday and so on .

note:

   Use MPC Platinum Installation and Operation manual for supplementary information .

MPCQ PlaTInUM MODBUS VarIaBle lIST

MPCQ reg / 

VarIaBle#

DeSCrIPTIOn

MUlT

 ♦1

(if not 1)

UOM

range / STaTeS / SPeCIal 

ValUeS

reaD 

Only

1 – 3

Model

6 Character string 

♦3

X

4 – 13

Serial Number

20 Character string 

♦3

X

14

Firmware Version

100

X

15

Vari-Boost Adjustment

10

0 .1 – 6 .4

16

Boost Mode

0=Disabled, 1=Manual, 

2=Vari, 3=Vari+ESD

17

Manual Boost Time

Minutes

0 – 120

18,19

Bypass Time

Minutes

0 – 2,147,483,647 

♦4

X

20 through 51

Boiler Status

(BTYPE=0)®

(BTYPE=1)®

(BTYPE=2)®

(BTYPE=3)®

0=Off, 1=On0=Off, 1=Low, 

2=High, 0=Off, 1=Low, 2=Med, 

3=High, 0=Off, 1=Low, 

2=MLow, 3=Mhigh, 4=High

X

52

Boiler Type  See "MPCQ Platinum 

Boiler Type Table" on page 12

0=On/Off, 1=2-Stage2=3-

Stage, 3=4-Stage

53

Bypass Mode

0=AUTO, 1=ON

54

Cycle Length

Minutes

10 – 240

55 through 86

Extension Panel Stage 

Communication Error

0=“”, 1=C/E

X

87

Day Heat Adjustment

0 – 15 = A – P

88

Outdoor Day Cutoff

°C, °F

-6 - 38°C, 20 - 100°F

89

Day Light Saving

0=Enable, 1=Disable

90

Sensor Fault Mode

0=OutputOn,1=OutputOff

91

Sensor Mode

0=°F, 1=°C

92

Lead Boiler

See "MPCQ Platinum Boiler 

Type Table" on page 12

93 through 124

Lockout Input

0=(inactive), 1=L/O

X

125

Logic Mode

0-PID, 1-OSS

126

Last Stage Hold

10

psi

0 .0 – 5 .0 

127

Min Runtime

Minutes

1 – 60

128 through 159 Boiler Mode

0=Auto, 1=Standby, 2=Off, 3=On

160

Total Boilers

1 – 32/(BTYPE+1)

161

Night Heat Adjustment

0 – 15 = A – P

Summary of Contents for MODBUS RTU RS485

Page 1: ...or safety control all equipment must have its own certified limit and safety controls required by local codes The installer must verify proper operation and correct any safety problems prior to the in...

Page 2: ...Configuration 3 MODBUS Communication Options 3 MAC Address 3 Baud 3 Troubleshooting 3 HWr Platinum MODBUS Variable list 4 HWrQ Platinum MODBUS Variable list 6 Multi MOD Platinum MODBUS Variable list...

Page 3: ...US COMMUnICaTIOn OPTIOnS SELECT MENU Maintenance Network Settings Multi MOD Platinum SELECT MENU Settings More Settings Remote Interface Network Settings All Other Platinum Controls Before connecting...

Page 4: ...f 27 Sensor Type 0 F 1 C 28 Minimum Water Temp C F 21 71 C 70 170 F 29 Outdoor Sensor C F 40 122 C 40 250 F 32000 Open 32001 Shorted 2 X 30 Outdoor Sensor Trim C F 3 3 C 5 5 F 31 Offset Temperature C...

Page 5: ...Single Register function code 6 and Write Multiple Registers function code 16 are supported note All variables with multiple UOM s depend upon the value of Input Mode to determine which to use note Us...

Page 6: ...Cut off C F 0 25 C 30 75 F 87 DHW Call Mode 0 No Priority 1 Priority 88 Day Light Saving 0 Enable 1 Disable 89 Sensor Fault Mode 0 Stages On 1 Stages Off 90 Fast Cool Down 0 Minimum Target Temp 1 Off...

Page 7: ...are packed 2 characters per register most significant byte first 4 Multi register values are stored big endian first register x 65536 second register value note All variables are stored as Holding Re...

Page 8: ...0 60 79 Input Mode 0 F 1 C 2 15psi 3 30psi 4 100psi 5 200psi 6 300psi 7 HWR 8 Reset F 9 Reset C X 80 Lead Stage 0 19 A T 81 Pre purge Delay 10 Minutes 0 0 10 0 82 through 101 Lockout Input Stages 1 20...

Page 9: ...ecified divide a read value by this to obtain the actual value Multiply desired value by this before writing 2 For variables that specify them if a read value is a special value 32000 32005 do not div...

Page 10: ...ted 2 X 31 Outdoor Sensor Trim C F 3 3 C 5 5 F 32 Operation Mode 0 Burner valve 1 District Steam 33 Output Relay 0 Off 1 On X 34 Panel Date Days since 1 1 1981 0 36500 35 Panel Time Minutes since 0 00...

Page 11: ...mation MPCQ PlaTInUM MODBUS VarIaBle lIST MPCQ reg VarIaBle DeSCrIPTIOn MUlT 1 if not 1 UOM range STaTeS SPeCIal ValUeS reaD Only 1 3 Model 6 Character string 3 X 4 13 Serial Number 20 Character strin...

Page 12: ...tem Run on Minutes 0 60 237 System Relay 0 Off 1 On X 238 Throttle Range 2 psi 0 5 5 0 239 Heat Establish Pressure 10 psi 0 5 5 0 MPCQ Platinum Boiler Type Table Boiler Type LEAD Special value Up to T...

Page 13: ...o 0 note Use Setback if Operation Mode is set to 1 note Use Last Stage Hold Min Runtime Purge Reaction Time Standby Delay when Logic Mode is set to 0 note Use Reaction Time when Lead Stage Rotation Mo...

Page 14: ...6 Day Light Saving 0 Enable 1 Disable 27 Sensor Fault Mode 0 OutputOn 1 OutputOff 28 Valve at Freezing 0 100 29 Sensor Mode 0 F 1 C X 30 Motor Time Seconds 120 600 31 Manual Valve Target 0 100 32 Nigh...

Page 15: ...gister value note All variables are stored as Holding Registers MODBUS functions Read Holding Registers function code 3 Write Single Register function code 6 and Write Multiple Registers function code...

Page 16: ...building systems including but not limited to the heating system boilers or electrical power system that is required for proper operation of any controls or other equipment installed by Heat Timer Co...

Reviews: