INSTALLATION AND OPERATION INSTRUCTIONS

HWE-SS DIGI-E

lItE

Hydronic Single-Stage Boiler Control

R

Blue (Boiler Output)

White (DHW Pump Output )

Yellow (System Pump Output )

Boiler

SYS

Pump

DHW

Pump

SET

®

C  O  R  P  O  R  A  T  I  O  N

R

SYSTEM =  

147F

TARGET = 

150F

2 Line Alphanumeric Display

Displays sensor values and 

menu settings

Output Lights indicate

output status

Display Section Locking Screws

Black (120VAC power)

3 Buttons to operate

the control

®

Elite Series

 WARNING

This Heat-Timer control is strictly an operating control; it should never be used as a primary limit or safety 

control. All equipment must have its own certified limit and safety controls required by local codes. The installer 

must verify proper operation and correct any safety problems prior to the installation of this Heat-Timer control.

Hot Water Control with Outdoor Reset, Set Point, 

and DHW for Hydronic Heating Applications

The HWE-Single Stage (HWE-SS) DIGI-SPAN Elite establishes 

ambient comfort by varying the temperature of the heating 

system’s circulating hot water in response to changes in the outdoor 

temperature.  In addition, it provides an outdoor temperature based 

cutoff, heating system pump control, and domestic hot water (DHW) 

pump control.  Two new features have been added to this control 

including a customized reset ratio curve.  A Set Point option was 

added for applications where outdoor reset will not apply.

Two sensors are used, one to monitor the outdoor temperature, and 

one to monitor the circulating hot water temperature in the heating 

system. When the outdoor temperature falls below the Outdoor 

Cutoff setting, the heating system is activated and the hot water 

temperature is increased proportionally to satisfy the load. Should 

it get warmer outdoors, the hot water temperature is automatically 

lowered by the control. If the outdoor temperature continues to rise 

to the outdoor cutoff setting then the heating system is turned off.

Summary of Contents for Digi-Span Elite Series HWE-SS

Page 1: ...ydronic Heating Applications The HWE Single Stage HWE SS DIGI SPAN Elite establishes ambient comfort by varying the temperature of the heating system s circulating hot water in response to changes in...

Page 2: ...HW tank to be satisfied quickly Mounting the Controller The HWE SS DIGI Elite is designed to mount on a 1900 4 x4 deep electrical box If additional room is needed for wiring use the extension skirt pr...

Page 3: ...M The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode from the Startup menu However in Set Point mode the Outdoor Sensor is optional When connected in that mode it will...

Page 4: ...to the next level Display Unit Options F C Default F SET System Startup Display Unit The HWE SS will offer two different temperature displays If F is selected all temperatures will display in Fahrenh...

Page 5: ...etermine the operating status of the output relays when a sensor reads Short or Open On sensor fault the Set Point will indicate FAULT TGT ON or OFF to indicate the condition of the output and the fau...

Page 6: ...nu Options Click SET Button SYSTEM 148 F TARGET 150 F SET SET SET SET SET S SET SET SET SET SET S Outdoor 48 F Cutoff 65 F Set Point Available when Startup Control Mode Set Point Options From 10 F 23...

Page 7: ...Reset Ratio Max Target Min Target Reset Ratio 10F Offset Min Target 120 F Max Target 170 F Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C...

Page 8: ...or temperature increases 2 F above the Outdoor Cutoff and after the boiler relay has de energized the SYS relay will stay on for a period set by the System Run On This allows the Pump to dissipate the...

Page 9: ...existing system The System and Outdoor Trim values adjust the System Sensor and Outdoor Sensor readings using positive or negative values System Trim 0 F Outdoor Trim 0 F Enable Disable Input The HWE...

Page 10: ...temperature is below the Target water temperature minus the Differential If not wait until the System temperature falls and then the stage LED should come on and the boiler should fire Otherwise remov...

Page 11: ...ED WITH 24VAC T1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor DHW Call Enable Dry Contact Setback Timer Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 1...

Page 12: ...P 6Amp resistive at 120 VAC 60 Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Offset from 40 F 22 C to 40 F 22 C Minimum Water...