background image

4

 

DHW Energy Saver Installation and Configuration Manual

HT# 059106-00C

Installation

The DHW Energy Saver communicates with the Heat-Timer Platinum control using RS485 (3-wire connection).  Thus, it 

needs to be installed in close proximity to the Platinum control to reduce long communication wire runs.

•   Mount the DHW Energy Saver on a flat surface next to the Platinum control.

•   The Module can be mounted horizontally or vertically.

•   Keep the control away from extreme heat, cold, or humidity.

•   Screw the module to the flat surface using the two side tabs with holes.

•   No need to remove the DHW Energy Saver cover.

Wiring

•   When wiring the DHW Energy Saver, make sure that the cover with the 

terminal labels is available.

•   All module terminals are of the removal type.  That facilitates easy 

wiring.  Just unscrew the terminal block side screws to remove the full 

terminal block.

DHW Energy Saver

Boiler

Pump

6

7

8

9

COM

3

4

5

A   GND   B

16VAC

1

2

~      ~

120VAC

16VAC

Dedicated

Transformer

Power Wiring

•   The DHW Energy Saver is powered using 16 VAC transformer.  

Transformer must be a minimum of 10 VA and is included with control.

•   Connect the transformer outputs to the DHW Energy Saver’s left most 

terminals.  Power polarity is not observed.

 WARNING

DO NOT share the DHW Energy Saver transformer with other 

devices.  This may cause problem in the control operation or 

permanent damage to the equipment.

Communication Wiring

•   The DHW Energy Saver communicates all of its information to the 

Platinum control using RS485 (3-wire connection).

•   The DHW Energy Saver RS485 terminals are wired to the Platinum 

main board’s RS485 (under the PCB board).

•   Follow the wiring as per the graph on the right.

 

ALERT

DO NOT connect the DHW Energy Saver to the RS485 on the 

Platinum RI board.  Instead, connect the DHW Energy Saver 

RS485 to the Platinum main board.

•   Maximum wiring length should not exceed 100 Feet.  Use 18 

gauge 2-conductor shielded wire (#18).  Connect the shield to the 

middle terminals on both of the RS485 connections.  To eliminate 

communication errors, DO NOT splice the communication cable wires.

•   When connecting the DHW Energy Saver and a Platinum Extension 

to the same connector, make sure to splice the cables externally before 

bringing them to the RS485 Plug Connector on the main Platinum 

Board.

DHW Energy Saver

Boiler

Pump

6

7

8

9

COM

3

4

5

A   GND   B

16VAC

1

2

~      ~

Use RS485

Communication

on the back of the

Platinum main board

PCB board

Shield

Summary of Contents for DHW Energy Saver

Page 1: ...y an operating control it should never be used as a primary limit or safety control All equipment must have its own certified limit and safety controls required by local codes The installer must verif...

Page 2: ...re Sensor 5 Return Temperature Sensor 5 PLATINUM CONTROL MENU SETTINGS 6 ICMS WEB MENU SETTINGS 6 Using the Supply or Return Sensor 7 Supply or Return Set Point 7 Supply or Return Peak and Light Diffe...

Page 3: ...the supply temperature drops below the Supply Set Point and differential the Control will energize the boiler output The boiler output will remain energized until the supply temperature reaches the Su...

Page 4: ...ol Connect the transformer outputs to the DHW Energy Saver s left most terminals Power polarity is not observed WARNING DO NOT share the DHW Energy Saver transformer with other devices This may cause...

Page 5: ...anual operation of the pump DHW Energy Saver Boiler Pump 6 7 8 9 COM 3 4 5 A GND B 16VAC 1 2 DHW Pump L N Bypass Switch Optional Temperature Sensor Wiring Only use a Standard Brass Tube sensor provide...

Page 6: ...HW SETTINGS Supply Settings Return Settings Demand Schedule Copy Schedule DHW Settings DHW SUPPLY SETTINGS Use Sensor Yes Setpoint 140 F Peak Diff 20 F Light Diff 40 F DHW RETURN SETTINGS Use Sensor Y...

Page 7: ...relay will de energize The circulating pump relay will energize whenever the return temperature drops below this set point less the differential See next setting DHW SUPPLY SETPOINT 140 F DHW RETURN S...

Page 8: ...on the ICMS web site Select Alarm Delivery Setup and then Add Delivery for the Sensor Fault WARNING The boiler water heater must have its operating and limit controls installed and wired in a way so...

Page 9: ...X CLOCK T T C O R P O R A T I O N R 2 3 4 5 5A 6 7 8 9 11 12 13 14 15 16 17 OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WI...

Page 10: ...ESS TO SELECT BACK MON 12 28 04 10 43Am ADJUST A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 AUX TEMP 2 DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS A13 A14 A15 A16 A17 A18 NETWORK PROVE SHUTDOWN SYSTEM TEMP...

Page 11: ...OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WIRE CLASS 1 WIRE ONLY ENCLOSED ENERGY MANAGEMENT EQUIPMENT 99RA PREV DEL OUT...

Page 12: ...ltage Input 16 VAC transformer provided minimum 10VA Output Relays 2 N O SPST Each a maximum HP pump or 6 Amp resistive load at 120 VAC 60 Hz Outputs DHW boiler water heater and DHW pump Communication...

Reviews: