DHW Energy Saver Installation and Configuration Manual  

5

HT# 059106-00C

Boiler or Direct/Indirect Water Heater Wiring

•   The DHW Energy Saver can control a single boiler.  It turns on the 

boiler/water heater whenever the supply temperature drops below the 

Supply Set Point less the differential.

•   Just wire terminal 6 and 7 to the boiler TT terminals.

•   Heat-Timer recommends the installation of a bypass switch for 

maintenance and manual operation of the boiler/water heater.

•   Make sure to set the boiler limits higher than the DHW Energy Saver 

Supply Set Point.

DHW Energy Saver

Boiler

Pump

6

7

8

9

COM

3

4

5

A   GND   B

16VAC

1

2

~      ~

TT

Boiler/Water

Heater

Bypass

Switch

(Optional)

Domestic Hot Water Circulating Pump Wiring

•   When the DHW Return is activated, the DHW Energy Saver will 

energize the DHW circulating pump relay whenever the return 

temperature drops below the Return Set Point less the differential 

•   The DHW Energy Saver is equipped with a circulating pump relay 

output.  The relay can operate up to 

 HP pump at 120 VAC.

•   The Pump output relay does not source any power.  A separate power 

source is required for the pump.

•   Heat-Timer recommends the installation of a bypass switch for 

maintenance and manual operation of the pump.

DHW Energy Saver

Boiler

Pump

6

7

8

9

COM

3

4

5

A   GND   B

16VAC

1

2

~      ~

DHW

Pump

L  N

Bypass

Switch

(Optional)

Temperature Sensor Wiring

•   Only use a Standard Brass Tube sensor provided (HT #904250-00).

•   The sensor wires can be extended to 500 Ft by splicing it to 

2-conductor shielded cable (#18/2 Shielded) (HT# 703001-01).  

•   Connect the shield at the Platinum control circled terminal.  The shield 

MUST be cut at the sensor end.

•   The sensors must be inserted in ⅜”ID NPT well (HT# 904011-00 or 

equivalent).

AUX

TEMP 0

AUX

TEMP 1

A1

A2

A3

A4

A5

A6

A7

A8

A9

A10

A11

A12

AUX

TEMP 2

A13

A14

A15

A16

A17

A18

NETWORK

PROVE

SHUTDOWN

OUT

TEMP

T

T

T

T

PRESS

4-20 mA

S

+

S

Shield

Supply Sensor

Shield

Return Sensor

Platinum Control

Supply Temperature Sensor

•   The Supply Temperature Sensor is required to be connected to the 

Platinum Aux Temp 0 input terminals for the DHW Energy Saver to 

control the boiler/water heater relay.

•   The Supply sensor must be installed in any of the boiler or water 

heater aquastat fittings or no more than 10 Ft past the outlet of the 

boiler/water heater, before any takeoffs.

Return Temperature Sensor

•   The return Temperature Sensor is included but optional.  It should be 

connected to the Platinum Aux Temp 1 input terminals for the DHW 

Energy Saver to control the Pump relay.

•   The Return sensor should be installed less than 3 feet from the return 

circulator on the return line.

Summary of Contents for DHW Energy Saver

Page 1: ...y an operating control it should never be used as a primary limit or safety control All equipment must have its own certified limit and safety controls required by local codes The installer must verif...

Page 2: ...re Sensor 5 Return Temperature Sensor 5 PLATINUM CONTROL MENU SETTINGS 6 ICMS WEB MENU SETTINGS 6 Using the Supply or Return Sensor 7 Supply or Return Set Point 7 Supply or Return Peak and Light Diffe...

Page 3: ...the supply temperature drops below the Supply Set Point and differential the Control will energize the boiler output The boiler output will remain energized until the supply temperature reaches the Su...

Page 4: ...ol Connect the transformer outputs to the DHW Energy Saver s left most terminals Power polarity is not observed WARNING DO NOT share the DHW Energy Saver transformer with other devices This may cause...

Page 5: ...anual operation of the pump DHW Energy Saver Boiler Pump 6 7 8 9 COM 3 4 5 A GND B 16VAC 1 2 DHW Pump L N Bypass Switch Optional Temperature Sensor Wiring Only use a Standard Brass Tube sensor provide...

Page 6: ...HW SETTINGS Supply Settings Return Settings Demand Schedule Copy Schedule DHW Settings DHW SUPPLY SETTINGS Use Sensor Yes Setpoint 140 F Peak Diff 20 F Light Diff 40 F DHW RETURN SETTINGS Use Sensor Y...

Page 7: ...relay will de energize The circulating pump relay will energize whenever the return temperature drops below this set point less the differential See next setting DHW SUPPLY SETPOINT 140 F DHW RETURN S...

Page 8: ...on the ICMS web site Select Alarm Delivery Setup and then Add Delivery for the Sensor Fault WARNING The boiler water heater must have its operating and limit controls installed and wired in a way so...

Page 9: ...X CLOCK T T C O R P O R A T I O N R 2 3 4 5 5A 6 7 8 9 11 12 13 14 15 16 17 OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WI...

Page 10: ...ESS TO SELECT BACK MON 12 28 04 10 43Am ADJUST A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 AUX TEMP 2 DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS A13 A14 A15 A16 A17 A18 NETWORK PROVE SHUTDOWN SYSTEM TEMP...

Page 11: ...OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WIRE CLASS 1 WIRE ONLY ENCLOSED ENERGY MANAGEMENT EQUIPMENT 99RA PREV DEL OUT...

Page 12: ...ltage Input 16 VAC transformer provided minimum 10VA Output Relays 2 N O SPST Each a maximum HP pump or 6 Amp resistive load at 120 VAC 60 Hz Outputs DHW boiler water heater and DHW pump Communication...

Reviews: