For Vertical Runs -

 The vent system must be supported

every eight (8) feet (2.4m) above the fireplace flue outlet by

wall brackets. To install support brackets for vertical runs:
• Attach wall brackets to the vent pipe and secure the wall

bracket to the framing members with nails or screws.

• Position the firestops on both sides of the hole previ-

ously cut and secure the firestops with nails or screws.

• The heat shields of the firestops 

MUST BE

 placed to-

wards the top of the hole.

• Continue the vent run through the firestops.

Figure 21.  Hole and Vent Pipe

   Figure 22.  Heat Shield, Interior & Exterior Firestops

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO 
SHIELD IF TOO
SHORT

EXTERIOR
FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD

    Figure 20.  Installing Support Brackets

4.  Install Firestops
For Horizontal Runs -

 Firestops are 

REQUIRED

 on both

sides of a combustible wall through which the vent passes.

NOTE: Model DVK-01TRD or SLK-01TRD does not need

an exterior firestop on an exterior combustible wall.

To install firestops for horizontal runs that pass through

either interior or exterior walls:
Cut a 12-inch by 12-inch (305 mm X 305 mm) hole through

the wall for D-series or a 10-inch by 10-inch (254 mm X 254

mm) hole for SL-D-series pipe.
The distance from the floor to the center of the framing hole

should match dimensions D or E in Figure 4 (page 12). The

center of the framing hole is one (1) inch (25.4mm) above

the center of the horizontal vent pipe.

2. Continue Adding Vent Components

• Continue adding vent components, locking each succeed-

ing component into place.

• Ensure that each succeeding vent component is secure-

ly fitted and locked into the preceding component.

• 90° elbows may be installed and rotated to any point

around the preceding component’s vertical axis. If an el-

bow does not end up in a locked position with the pre-

ceding component, attach with a minimum of two (2)

sheet metal screws.

Figure 19.  Adding Venting Components

3.  Install Support Brackets
For Horizontal Runs - 

The vent system must be supported

every five (5) feet of horizontal run by a horizontal pipe support.
To install support brackets for horizontal runs:
•  Place the pipe supports around the vent pipe.
•  Nail the pipe supports to the framing members.

VENT PIPE

1" (25.4 mm)

12" or 10"

(305mm or

254mm)

12" or 10"

(305mm or 254mm)

Summary of Contents for SL-350DVT

Page 1: ...WITH APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyforusewitht...

Page 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Page 3: ...tem 15 A Vent System Approvals 15 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 28 Step 5 The Gas Control Systems 28 Step 6 The Gas Suppl...

Page 4: ...National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1...

Page 5: ...ll void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following actions Installation of any damaged f...

Page 6: ...350DVT 22 5 8 576mm 1 2 13mm 16 1 4 413mm 8 3 4 222mm 6 5 8 168mm 15 3 4 400mm 11 3 8 288mm GAS LINE ACCESS 5 3 8 138mm 2 1 4 57mm 30 1 2 775mm 28 711mm 33 837mm 17 432mm 29 737mm 8 203mm ELECTRICAL A...

Page 7: ...11 Figure 2 Diagram of the SL 350TRS...

Page 8: ...ace facing material The dia gram below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Minimum Clearances fr...

Page 9: ...inch inner pipe 8 5 8 inch outer pipe DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Page 10: ...nch inner pipe 6 5 8 inch outer pipe 120 3048mm 24 610mm 36 914mm 60 1524mm 9 1 4 6 5 8 6 1 2 6 3 8 6 1 2 9 5 8 9 5 8 6 5 8 6 3 8 8 3 4 SL 09D 12 17 SL 12 17D SL12 17D SL 24D SL 36D SL 48D 47 3 4 35 3...

Page 11: ...tion Kits Vent System Components SL D SERIES D SERIES DVK 01D DVK TVCD DVK 01TRD SLK 01D SLK TVCD SLK 01TRD Identifying Vent Components Approved vent system components are labeled for identifi cation...

Page 12: ...g over 20 feet an Extended Vertical Baffle Kit is recommended for improved flame appearance STRAIGHTOUTHORIZONTALVENTING H Max Run 24 610 mm Use D Series components only Figure 9 Straight Out Horizont...

Page 13: ...ing with One 90 Elbow V MODEL SL 350TRS V MIN H MAX 90o Elbow on Top 2 5 863mm 1 305mm 3 914mm 2 610mm 4 1 22m 3 914mm 6 1 86m 4 1 22m 8 2 48m 5 1 52m 16 4 8m H MAX 16 4 8m V H MAX 40 12 2m Use SL D S...

Page 14: ...4 8m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 16 MAX 4 8m Figure 12 Venting with Two 90 Elbows V FT H H1 FT 1 MIN 305 mm 2 MAX 610 mm 2 MIN 610 mm 4 MAX 1 22 m 3 MIN 914 mm 6 MAX 1 86 m 4 MIN 1 22 m 8...

Page 15: ...1 86m 4 1 22m 8 2 48m 5 1 52m 16 4 8m H H1 MAX 16 4 8m V H H1 MAX 40 12 2m MODEL SL 350TRS V MIN H MAX 90o Elbow on Top 2 5 863mm 1 305mm 3 914mm 2 610mm 4 1 22m 3 914mm 6 1 86m 4 1 22m 8 2 48m 5 1 52...

Page 16: ...H1 40 MAX 12 4m H 8 MAX 2 48m H H1 16 MAX 4 8m V H H H1 1 MIN 305 mm 2 MAX 610 mm 4 MAX 1 22m 2 MIN 610 mm 4 MAX 1 22 m 8 MAX 2 48m 3 MIN 914 mm 6 MAX 1 86 m 12 MAX 3 72m 4 MIN 1 22 m 8 MAX 2 48 m 16...

Page 17: ...m 16 4 8m 5 1 52m 16 4 8m 16 4 8m VENTING WITH FOUR 4 90 ELBOWS NATURAL AND PROPANE GAS SL 350TRS V MIN H MAX 2 609mm 5 1 52m V1 MIN H1 MAX V2 MIN 5 1 52m 5 1 52m 4 5 1 37m V V1 V2 H H1 MAX 40 12 2m F...

Page 18: ...You have to take the glass off for positioning the logs when the unit is finally installed in place and finished around it Attach vent system to the top starting collars TOP VENTED REAR VENTED SL 350...

Page 19: ...ugh either interior or exterior walls Cut a 12 inch by 12 inch 305 mm X 305 mm hole through the wall for D series or a 10 inch by 10 inch 254 mm X 254 mm hole for SL D series pipe The distance from th...

Page 20: ...10 inch 254mm X 254mm hole through the ceiling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 24 Ceiling Firestop Ceiling Side If...

Page 21: ...ange of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges in the cap Figure 26 Round Trapezoi...

Page 22: ...or that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm f...

Page 23: ...MUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside of...

Page 24: ...this model Standing Pilot Ignition and Direct Spark Ignition DSI Standing Pilot Ignition System This system includes millivolt control valve standing pilot thermopile thermocouple flame sensor and pie...

Page 25: ...line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line installation is complete use a...

Page 26: ...y installed Remote Wall Switch Position the remote wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace...

Page 27: ...rough the other tab into the pilot hole on the outer wrap Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box Figure 34 Direct Spa...

Page 28: ...ontal Dimensions of Combustibles above Fireplace CAUTION IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE J...

Page 29: ...2 inch apart near port holes in burner top Do NOT press embers into burner ports Cover the top of the burner with a single layer of ember material Then sprinkle GE 93 on top of the burner For best per...

Page 30: ...NGEROUS and voids all war ranties A small amount of air will be in the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once...

Page 31: ...annually By Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically B...

Reviews: