16
STRAIGHT UP VERTICAL VENTING
V (FT.)
40' MAX.
Figure 8. Straight up Vertical Venting
Use SL D-Series
components only.
NOTE:
For vertical venting over 20 feet an
Extended Vertical Baffle Kit is recommended
for improved flame appearance.
STRAIGHT OUT HORIZONTAL VENTING
H
Max. Run
24" (610 mm)
Use D-Series
components only.
Figure 9. Straight Out Horizontal Venting
Note:
Use two 90
o
elbows for corner
installations on SL-350TRS.
Note: There MUST be a 25% reduction
in total H when using flex vent.