Heat-N-Glo SL-350DVT Installer'S Manual Download Page 18

22

!

STARTING

COLLAR

STOVE

SEALANT

BEAD

1 INCH

(25.4mm)

 FIRST VENT

COMPONENT

!

WARNING:  ENSURE  THAT  THE  FIBER

GASKET SUPPLIED WITH THE FIREPLACE

SEALS BETWEEN THE FIRST VENT COMPONENT

AND THE OUTER FIREPLACE WRAP.

If the installation is for a termination cap attached directly

to the fireplace, skip to the sections, 

Install Firestops

 and

Vent Termination

.

3/8”

(9.5mm)

B.  Installing Vent Components

After determining which set of starting collars will be used

(top or rear), follow venting instructions accordingly.

NOTE: 

The SL-350TRS and SL-350TRS LP are built with the

air shutter set for top vented configurations. If venting out the

rear of the unit adjust the air shutter per the following table.

Venting Out the Rear Vent (SL-350TRS)

 (See Figure 17)

Remove the installed rear seal cap from the rear starting collars

by cutting the strap at each end. Remove the insulation inside

the 5” collar. Follow the vent configuration tables accordingly.
Remove the 5” diameter heat shield from the 5” diameter collar

by sliding it out.

WARNING: THE TOP HEAT SHIELD (INSIDE

THE FIREBOX) MUST REMAIN ATTACHED IF

THE VENT SYSTEM IS ATTACHED TO THE

REAR STARTING COLLARS. SEE FIGURE 17.

Venting Out the Top Vent (SL-350TRS)

Remove the top vent collar seal cap by cutting the strap at

each  end.  Remove  the  insulation  inside 

BOTH

  the  4”

diameter and 6 5/8” diameter collars. (See Figure 17).
Remove the 4” diameter heat shield from the 4” diameter

collar by sliding it out.
You have to take the glass off for positioning the logs when

the unit is finally installed in place and finished around it. Attach

vent system to the top starting collars.

TOP VENTED

REAR VENTED

   SL-350TRS

1/4” open

3/16” open

   SL-350TRSLP

1/2” open

3/8” open

!

Figure 17

Insert  screwdriver

or  similar  object

here to remove cap.

CUT HERE

Venting

Out Rear

Venting

Out Top

!

WARNING:  THE REAR VENT COLLAR SEAL

CAP MUST REMAIN ATTACHED TO THE REAR

VENT COLLARS IF THE VENT SYSTEM IS ATTACHED

TO THE TOP STARTING COLLARS. SEE FIGURE 17.

!

WARNING: FAILURE TO REMOVE INSULATION

IN THE SET OF COLLARS YOU ARE USING

COULD CAUSE A FIRE.

!

WARNING: YOU MUST LEAVE THE INSULA-

TION IN PLACE IN THE SET OF COLLARS YOU

ARE NOT USING.

1.  Attach the First Vent Component to the

     Starting Collars

To attach the first vent component to the starting collars

of the fireplace:

• Apply a 3/8 inch (9.5mm) bead of stove cement around

the fireplace inner vent starting collar.

• Lock the vent components into place by sliding the con-

centric pipe sections with four (4) equally spaced interior

beads into the fireplace collar or previously installed com-

ponent end with four (4) equally spaced indented sections.

• When the internal beads of each outer pipe line up, ro-

tate the pipe section clockwise about one-quarter (1/4)

turn. The vent pipe is now locked together.

WARNING: A  3/8  INCH  (9.5  MM)  BEAD  OF

STOVE CEMENT MUST BE PLACED AROUND

THE FIREPLACE INNER VENT STARTING COLLAR

BEFORE ATTACHING THE FIRST VENT COMPO-

NENT. FAILURE TO SEAL THIS JOINT MAY CAUSE

THE FIREPLACE TO OPERATE IMPROPERLY. SEE

THE DIAGRAM .

    Figure 18.    Attaching the First Vent Component

                         to the Starting Collars

Summary of Contents for SL-350DVT

Page 1: ...WITH APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyforusewitht...

Page 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Page 3: ...tem 15 A Vent System Approvals 15 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 28 Step 5 The Gas Control Systems 28 Step 6 The Gas Suppl...

Page 4: ...National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1...

Page 5: ...ll void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following actions Installation of any damaged f...

Page 6: ...350DVT 22 5 8 576mm 1 2 13mm 16 1 4 413mm 8 3 4 222mm 6 5 8 168mm 15 3 4 400mm 11 3 8 288mm GAS LINE ACCESS 5 3 8 138mm 2 1 4 57mm 30 1 2 775mm 28 711mm 33 837mm 17 432mm 29 737mm 8 203mm ELECTRICAL A...

Page 7: ...11 Figure 2 Diagram of the SL 350TRS...

Page 8: ...ace facing material The dia gram below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Minimum Clearances fr...

Page 9: ...inch inner pipe 8 5 8 inch outer pipe DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Page 10: ...nch inner pipe 6 5 8 inch outer pipe 120 3048mm 24 610mm 36 914mm 60 1524mm 9 1 4 6 5 8 6 1 2 6 3 8 6 1 2 9 5 8 9 5 8 6 5 8 6 3 8 8 3 4 SL 09D 12 17 SL 12 17D SL12 17D SL 24D SL 36D SL 48D 47 3 4 35 3...

Page 11: ...tion Kits Vent System Components SL D SERIES D SERIES DVK 01D DVK TVCD DVK 01TRD SLK 01D SLK TVCD SLK 01TRD Identifying Vent Components Approved vent system components are labeled for identifi cation...

Page 12: ...g over 20 feet an Extended Vertical Baffle Kit is recommended for improved flame appearance STRAIGHTOUTHORIZONTALVENTING H Max Run 24 610 mm Use D Series components only Figure 9 Straight Out Horizont...

Page 13: ...ing with One 90 Elbow V MODEL SL 350TRS V MIN H MAX 90o Elbow on Top 2 5 863mm 1 305mm 3 914mm 2 610mm 4 1 22m 3 914mm 6 1 86m 4 1 22m 8 2 48m 5 1 52m 16 4 8m H MAX 16 4 8m V H MAX 40 12 2m Use SL D S...

Page 14: ...4 8m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 16 MAX 4 8m Figure 12 Venting with Two 90 Elbows V FT H H1 FT 1 MIN 305 mm 2 MAX 610 mm 2 MIN 610 mm 4 MAX 1 22 m 3 MIN 914 mm 6 MAX 1 86 m 4 MIN 1 22 m 8...

Page 15: ...1 86m 4 1 22m 8 2 48m 5 1 52m 16 4 8m H H1 MAX 16 4 8m V H H1 MAX 40 12 2m MODEL SL 350TRS V MIN H MAX 90o Elbow on Top 2 5 863mm 1 305mm 3 914mm 2 610mm 4 1 22m 3 914mm 6 1 86m 4 1 22m 8 2 48m 5 1 52...

Page 16: ...H1 40 MAX 12 4m H 8 MAX 2 48m H H1 16 MAX 4 8m V H H H1 1 MIN 305 mm 2 MAX 610 mm 4 MAX 1 22m 2 MIN 610 mm 4 MAX 1 22 m 8 MAX 2 48m 3 MIN 914 mm 6 MAX 1 86 m 12 MAX 3 72m 4 MIN 1 22 m 8 MAX 2 48 m 16...

Page 17: ...m 16 4 8m 5 1 52m 16 4 8m 16 4 8m VENTING WITH FOUR 4 90 ELBOWS NATURAL AND PROPANE GAS SL 350TRS V MIN H MAX 2 609mm 5 1 52m V1 MIN H1 MAX V2 MIN 5 1 52m 5 1 52m 4 5 1 37m V V1 V2 H H1 MAX 40 12 2m F...

Page 18: ...You have to take the glass off for positioning the logs when the unit is finally installed in place and finished around it Attach vent system to the top starting collars TOP VENTED REAR VENTED SL 350...

Page 19: ...ugh either interior or exterior walls Cut a 12 inch by 12 inch 305 mm X 305 mm hole through the wall for D series or a 10 inch by 10 inch 254 mm X 254 mm hole for SL D series pipe The distance from th...

Page 20: ...10 inch 254mm X 254mm hole through the ceiling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 24 Ceiling Firestop Ceiling Side If...

Page 21: ...ange of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges in the cap Figure 26 Round Trapezoi...

Page 22: ...or that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm f...

Page 23: ...MUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside of...

Page 24: ...this model Standing Pilot Ignition and Direct Spark Ignition DSI Standing Pilot Ignition System This system includes millivolt control valve standing pilot thermopile thermocouple flame sensor and pie...

Page 25: ...line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn After the gas line installation is complete use a...

Page 26: ...y installed Remote Wall Switch Position the remote wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace...

Page 27: ...rough the other tab into the pilot hole on the outer wrap Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box Figure 34 Direct Spa...

Page 28: ...ontal Dimensions of Combustibles above Fireplace CAUTION IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE J...

Page 29: ...2 inch apart near port holes in burner top Do NOT press embers into burner ports Cover the top of the burner with a single layer of ember material Then sprinkle GE 93 on top of the burner For best per...

Page 30: ...NGEROUS and voids all war ranties A small amount of air will be in the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once...

Page 31: ...annually By Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically B...

Reviews: