![Heat Controller HKV Installation, Operation & Mainenance Manual Download Page 4](http://html1.mh-extra.com/html/heat-controller/hkv/hkv_installation-operation-and-mainenance-manual_2115768004.webp)
3
IOM Instructions
HKV LArge CommerCiAL
Heat Controller, Inc.
HKV Physical Data
Model
084
096
120
150
168
192
240
300
Compressor Quantity
Scroll (1)
Scroll (2)
Factory Charge R410a (oz) [kg] per
circuit
140 [3.97]
156 [4.42]
224 [6.35]
248 [7.03]
140 [3.97]
156 [4.42]
224 [6.35]
248 [7.03]
Blower Motor
Blower Motor Quantity
1
Standard Motor (hp) [kw]
1 [.75]
1.5 [1.12]
2 [1.49]
3 [2.24]
2 [1.49]
3 [2.24]
5 [3.73]
5 [3.73]
Large Motor (hp) [kw]
1.5 [1.12]
2 [1.49]
3 [2.24]
5 [3.73]
3 [2.24]
5 [3.73]
7.5 [5.60]
7.5 [5.60]
Blower
No. of Blowers
1
2
Blower Wheel Size D x W (in0 [cm]
15 x 11 [38.1 x 38.1]
15 x 15 [38.1
x 38.1]
15 x 11 [38.1 x 38.1]
15 x 15 [38.1
x 38.1]
Water Connection Size
FPT (in) [mm]
1-1/2" [38.1]
2" [50.8]
2-1/2" [63.5]
Coax Volume
Volume (US Gallons) [liters]
2.19 [8.28]
2.48 [9.37]
3.46 [13.11]
4.83 [18.29]
6.36 [24.08]
7.39 [27.98]
Condensate Connection Size
FPT (in) [mm]
1" [25.4]
Air Coil Data
Air Coil Dimensions H x W (in) [cm]
36 x 48 [91.4 x 121.9]
2 - 36 x 48 [91.4 x 121.9]
Air Coil Total Face Area (ft2) [m2]
12 [1.11]
24 [2.22]
Air Coil Tube Size (in) [cm]
3/8" [0.953]
Air Coil Fin Spacing (fpi) [fins per cm]
14 [5.5]
12 [4.72]
14 [5.5]
12 [4.72]
Air Coil Number of Rows
2
3
4
2
3
4
Miscellaneous Data
Filter Standard - 1" [25.4mm] Throw-
away (qty) (in) [cm]
(QTY.4) 18 x 25 [45.74 x 63.5]
(QTY.8) 18 x 25 [45.74 x 63.5]
Weight - Operating (lbs) [kg]
650 [294]
696 [316]
700 [318]
1300 [589]
1346 [611]
1404 [637]
Weight - Packaged (lbs) [kg]
665 [301]
711 [322]
715 [324]
1330 [603]
1376 [624]
1434 [650]
All units have grommet & spring compressor mountings, and 1/2" & 1-3/4" electrical knockouts.