IOM Instructions
HKV LArge CommerCiAL
Heat Controller, Inc.
Blower Performance
HKV 120 Blower Performance
4600
RPM
668
694
721
745
768
791
816
838
860
883
904
925
945
967
987
1007
4600
Turns Open
4.5
4
3
2.5
2
1.5
1
6
5.5
5
4.5
4
3.5
3
2.5
2
4700
BHP
1.74
1.84
1.89
1.94
2.04
2.14
2.24
2.34
2.44
2.54
2.64
2.69
2.74
2.84
2.94
4700
Sheave/Mtr
A
A
A
A
D
D
E
E
E
E
E
E
E
E
E
4700
RPM
683
711
735
758
782
806
828
850
871
894
915
935
955
977
997
4700
Turns Open
4
3.5
2.5
2
2
1
6
6
5.5
5
4.5
3.5
3.5
3
2
4800
BHP
1.84
1.94
1.99
2.04
2.14
2.24
2.34
2.44
2.54
2.64
2.74
2.84
2.94
4800
Sheave/Mtr
A
A
A
D
D
D
E
E
E
E
E
E
E
4800
RPM
698
725
749
772
795
819
836
862
883
906
926
946
968
4800
Turns Open
3.5
3
2.5
2
1.5
1
6
5.5
5
4.5
4
3.5
3
4900
BHP
1.94
2.04
2.14
2.24
2.34
2.44
2.49
2.54
2.64
2.74
2.84
2.94
4900
Sheave/Mtr
A
D
D
D
D
E
E
E
E
E
E
E
4900
RPM
715
739
762
785
810
831
853
874
896
917
937
956
4900
Turns Open
3
3
2.5
2
1
6
5.5
5.5
5
4
3.5
3
5000
BHP
2.04
2.14
2.24
2.34
2.44
2.54
2.64
2.74
2.84
2.94
5000
Sheave/Mtr
D
D
D
D
E
E
E
E
E
E
5000
RPM
730
753
776
798
822
844
865
885
908
928
5000
Turns Open
3
2.5
2
1.5
6
6
5.5
5
4.5
4
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All airflow in rated at lowest
Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance first calculate the face velocity of the air coil (Face Velocity [FPM] = Airflow [CFM] / Face Area [sqft]).Then use preceding wet coil to dry coil conversion table.
All Data is Wet Coil
Table Continued from Previous Page
Airflow
(SCFM)
ESP
Airflow (cfm) at External Static Pressure (in. wg)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50