Heat & Glo SL-5F Installation Manual Download Page 27

27

Heat & Glo  • SL-5F, SL-7F Installation Manual  •  2499-980 Rev. L  •  10/19 

Rear Vent - Vertical Termination

Figure 4.23

Figure 4.24

V

1

 MIN.

H

MAX.

1 ft.

305 mm

3-1/2 ft.

1.1 m

2 ft.

610 mm

5-1/2 ft.

1.7 m

3 ft.

914 mm

7-1/2 ft.

2.3 m

H MAX. = 7-1/2 ft. (2.3 m)

V

+ H

1

 MAX. = 40 ft. (12.2 m)

H

+ H

2

 MAX

V

MIN.

Back to back elbows

1/2 ft.

152 mm

2-1/2 ft.

762 mm

1 ft.

305 mm

4-1/2 ft.

1.4 m

2 ft.

610 mm

6-1/2 ft.

2.0 m

3 ft.

914 mm

H MAX. = 6-1/2 ft. (2 m)

V

 

+ H+ H

1

 MAX. = 40 ft. (12.2 m)

Note

: Use DVP Series 

components only.

Note

: Use DVP Series 

components only.

Two Elbows

One Elbow

H

1

V

1

INSTALLED

HORIZONTALLY

H

1

H

2

V

1

Summary of Contents for SL-5F

Page 1: ...d on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used DANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN T...

Page 2: ...t Information A Vent Termination Minimum Clearances 12 B Vent Terminal Clearances 13 C Approved Pipe 14 D Use of Elbows 15 E Measuring Standards 16 F Use of Flex Vent 17 G Vent Diagrams 17 5 Vent Clea...

Page 3: ...moved inside outside of appliance ___________________________ Refractories logs media and embers installed correctly ___________________________ Glass assembly installed and secured __________________...

Page 4: ...ed with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations such as in bathrooms or near sinks NOT INTENDED FOR USE AS A PR...

Page 5: ...fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas...

Page 6: ...or remote control are desired Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information consult a qualified servic...

Page 7: ...ers Hammer Phillips screwdriver Manometer Gloves Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non corrosive leak che...

Page 8: ...4 41 1041 B 31 1 8 791 36 1 8 918 C 27 3 16 691 32 1 16 814 D 18 1 16 459 21 1 2 546 E 34 1 16 865 37 5 8 956 F 3 9 16 90 3 9 16 90 G 6 7 8 175 6 7 8 175 H 23 3 8 594 26 7 8 683 I 34 3 8 873 37 7 8 96...

Page 9: ...in 30 5 16 27 1 4 29 1 2 25 7 8 28 3 4 2 3 16 1 1 2 mm 770 692 749 657 730 56 38 SL 7F in 35 13 16 31 1 8 34 3 8 29 5 8 32 1 2 2 1 8 1 5 16 mm 910 791 873 752 826 54 33 FIRESCREEN DECORATIVE FRONTS Fa...

Page 10: ...n to scale Actual installation may vary due to individual design preference Figure 3 3 Appliance Locations K C A L F I B G E D J J G A F C A H M N Refer to Section 10 B for mantel and wall projection...

Page 11: ...nt accidental contact The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney Failure to maintain airspace may c...

Page 12: ...Fuel Oil Termination Cap B Gas Termination Cap A If using decorative cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decorative cap cover A...

Page 13: ...d air supply inlet All mechanical air intakes within 10 feet of a horizontal termination cap must be a minimum of 3 feet below termination 3 ft 914 mm 6 ft 1 8 m J On public property clearance above p...

Page 14: ...or vent component information and dimensions DO NOT mix pipe fittings or joining methods from differ ent manufacturers The pipe is tested to be run inside an enclosed wall There is no requirement for...

Page 15: ...I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1...

Page 16: ...ure 12 1 for DVP Figure 12 6 for SLP for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap see Figure 4...

Page 17: ...runs may be level Horizontal termination cap should have a 1 4 inch downward slant to allow any moisture in cap to be released See Figure 4 10 G Vent Diagrams Top Vent Horizontal Termination Two 45 E...

Page 18: ...X 40 ft 12 2 m See Warning Figure 4 11 Top Vent Horizontal Termination One Elbow Fire Risk When using SLP HRC SS termination cap on top vented fireplaces a one foot minimum vertical vent section is re...

Page 19: ...1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m See Warning Below Fire Risk When using SLP HRC SS termination cap on top vented fireplaces a one foot minimum...

Page 20: ...t 4 3 m H1 H2 MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 CANNOT exceed 40 ft 12 2 m See Warning Below Fire Risk When using SLP HRC SS termin...

Page 21: ...manual bag Note Be sure to rein stall the exhaust baffle after exhaust restrictor installation Exhaust restrictor Exhaust restrictor Exhaust restrictor Instructions 1 Install the exhaust restrictor ov...

Page 22: ...2 ft 457 mm 1 2 ft 152 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 15 ft 4 6 m H1 MAX 15 ft 4 6 m V1 V2 H1 MAX 40 ft 12 2 m No speci...

Page 23: ...2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 CANNOT exceed 40 ft 12 2 m Note Us...

Page 24: ...4 18 V1 MIN H1 MAX V2 MIN H2 MAX V3 MIN 1 1 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 1 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m Note Use SLP Series components only V1 H1 V2 V3 H2 Note The...

Page 25: ...980 Rev L 10 19 Rear Vent Horizontal Termination Figure 4 20 Figure 4 19 No Elbows H1 9 in 229 mm Maximum Rear Vent Horizontal Termination One 45 Elbow Note Use DVP Series components only Note Use DVP...

Page 26: ...12 2 m Figure 4 21 H1 MAX V1 MIN H2 H3 MAX H1 H2 H3 MAX 1 1 2 ft 457 mm Back to back elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 2 ft 610 mm 5 1 2 ft 1 7 m 5 1 2 ft 1 7 m 2 ft 610 m...

Page 27: ...7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m H1 H2 MAX V1 MIN Back to back elbows 1 2 ft 152 mm 2 1 2 ft 762 mm 1 ft 305 mm 4 1 2 ft 1 4 m 2 ft 610 mm 6 1 2 ft 2 0 m 3 f...

Page 28: ...t 914 mm 6 1 2 ft 2 0 m 2 ft 610 mm 5 1 2 ft 1 7 m 5 ft 1 5 m 10 1 2 ft 3 2 m 3 ft 914 mm 7 1 2 ft 2 3 m 7 ft 2 1 m 14 1 2 ft 4 4 m H1 MAX 7 1 2 ft 2 3 m H1 H2 MAX 14 1 2 ft 4 4 m V1 V2 H1 H2 MAX 40 f...

Page 29: ...Fire Coaxial to colinear venting con figuration may only be used in existing non combustible chimney Installation in any other venting application could cause fire Prior to installing the gas applian...

Page 30: ...appliance starting collar with 3 1 2 in self tapping screws See Figure 4 28 Rear Vent Remove the rear seal cap and insulation if equipped Connect the DVP 2SL adapter to the vertically positioned elbow...

Page 31: ...in 25 mm clearance around vertical sections B Wall Penetration Framing Firestops Combustible Wall Penetration Whenever a combustible wall is penetrated you must frame a hole for the wall shield firest...

Page 32: ...und the vent Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR...

Page 33: ...tical position as shown above The heat shield must remain in the vertical position Figure 6 5 Remove the seal cap Figure 6 6 Remove the insulation basket and white insula tion from the center vent pip...

Page 34: ...er parts of the retaining band toward the center as shown Remove the seal cap Figure 6 11 Discard the seal cap remove and discard the insulation basket Note Once the seal cap has been removed it CANNO...

Page 35: ...agram shows how to properly position and secure the appliance See Figure 6 13 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appl...

Page 36: ...rom rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when...

Page 37: ...connecting joint after joining sections On horizontal pipe runs it is recom mended that the tape seam is positioned on the bottom side of the vent pipe Only outer pipes need to be sealed All unit coll...

Page 38: ...very 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal ru...

Page 39: ...ROOF TO LOWEST DISCHARGE OPENING NOTICE Failure to properly caulk the roof flashing and pipe seams could permit entry of water Caulk the gap between the roof flashing and the outside diameter of the...

Page 40: ...n Figure 7 16 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attac...

Page 41: ...des may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures which require superior resistance to wind driven rain penetration a f...

Page 42: ...ceptacle and reattach the junction box receptacle to the outer shell Electrical Service and Repair WARNING Risk of Shock Label all wires prior to dis connection when servicing controls Wiring errors c...

Page 43: ...8 2 Intellifire Pilot Ignition IPI Wiring Diagram TRANSFORMER WALL SWITCH 3 VAC PLUG IN BLACK RED BATTERY PACK ORANGE TO BROWN TO BROWN GREEN GROUND TO FIREPLACE CHASSIS WHITE ORANGE IGNITION MODULE 3...

Page 44: ...d connect to the top fan switch connector 1 4 in male as shown Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3 AWG with Ground Junct...

Page 45: ...and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure could cause exp...

Page 46: ...e opening the air shutter To adjust loosen the wing nut Care should be taken when adjusting the air shutter so as not to cause the appliance to soot If sooting occurs the air shutter will need to be o...

Page 47: ...nd louvers 0 IN 0 IN 0 IN SHEETROCK FINISH WALL MATERIAL UP TO 1 2 IN THICK MAY BE COMBUSTIBLE TOP AND SIDES HIGH TEMPERATURE SEALANT 300 F 149 C MIN TOP AND SIDE SEAL JOINT Figure 10 1 Noncombustible...

Page 48: ...NING 4 12 13 11 32 CEILING Figure 10 7 Non Combustible Zone 1 2 in SHEETROCK OR COMBUSTIBLE MATERIAL 3 1 2 in 1 2 in NON COMBUSTIBLE ZONE Figure 10 6 Non Combustible Mantel Leg or Wall Projections Acc...

Page 49: ...ed glass panel DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one 1 Remove de...

Page 50: ...xed Glass Assembly B Remove the Shipping Materials Remove shipping materials from inside or underneath the firebox The splatter guard is a piece of corrugated material used to protect the appliance du...

Page 51: ...n in Figure 4 Figure 3 Log 1 Bottom View Log 2 2033 709 Log 2 has holes on the bottom side that will be used for positioning them in the firebox See Figure 5 Place Log 2 on the pins in the front of th...

Page 52: ...rock jig to prevent the rock from going in between the base pan and burner DO NOT allow any lava rock to fall in the slot and onto the burner Figure 10 Lava Rock and Rock Jig LAVA ROCK ROCK JIG WARNIN...

Page 53: ...d grooves Figure 12 shows the left side Log 5 in position The right side Log 5 is located by placing the Y Shaped end on the locating grooves of Log 1 and setting the other end on the right side log 2...

Page 54: ...gure 4 Figure 3 Log 1 Bottom View Log 2 2033 709 Log 2 is used twice in this log set Log 2 also has holes on the bottom side that will be used for positioning them in the firebox See Figure 5 Locate t...

Page 55: ...he locating pin on the basepan There should be approx a 1 4 inch gap between the end of the log and the firebox The other Log 3 will be placed on the right in a position to mirror the first Log 3 Plac...

Page 56: ...urner op eration Delayed ignition may occur Remove the burner tube slot cover by removing the shipping screw on the back Keep the burner tube slot cover and screw in the lower cavity of the appliance...

Page 57: ...a of Log 1 See Figure 15 The Y Shaped section will rest on the left side Log 2 See Figure 16 The left branch of the Y should rest where the burned area of the left Log 2 begins See Figure 17 Figure 15...

Page 58: ...glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Replace the glass door on the appliance Pull out and latch the four glass assembly latches...

Page 59: ...mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height Lengt...

Page 60: ...38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickn...

Page 61: ...Roof Flashing Multi pak Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap...

Page 62: ...133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Ca...

Page 63: ...m 8 1 8 in 206 mm SLP HRC SS HORIZONTAL TERMINATION CAP When using DVP TB1 termination cap on top vented fireplaces a three foot minimum vertical vent section is required before installing first elbow...

Page 64: ...s PVI WH60 80 FT PV Wire Harness PVI WH80 100 FT PV Wire Harness PVI WH100 PVI SLP B Power Vent Inline SLP LPC SLP Low Profile Cap Approved for use with PVI SLP B only Note Wire harnesses required to...

Page 65: ...NUMBER 10 FT PV Wire Harness PVI WH10 20 FT PV Wire Harness PVI WH20 40 FT PV Wire Harness PVI WH40 60 FT PV Wire Harness PVI WH60 80 FT PV Wire Harness PVI WH80 100 FT PV Wire Harness PVI WH100 Note...

Page 66: ...LP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 1...

Page 67: ...he existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Tra...

Page 68: ...14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLP TVHW Vertical Termination Cap DVP FBHT Horizontal T...

Page 69: ...on Manual 2499 980 Rev L 10 19 LINK DV30B Flex Liner Kit DV 46DVA GCL Coaxial Colinear Appliance Connector 768 380A Stainless Steel Flex Pipe DVP 2SL Adapter COAXIAL to COLINEAR VENTING Figure 12 11 C...

Page 70: ...ied with the fan kit to operate your fan See your dealer if you have questions Printed in U S A Copyright 2019 Heat Glo a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 ww...

Reviews: