Heat & Glo • SL-550/750TR-E, SL-550/750/950TR-IPI-E Installation Manual • 2118-910 Rev. C • 4/16
Figure 4.8
One Elbow
Top Vent - Horizontal Termination
H
1
V
1
V
1
Minimum
H
1
Maximum
SL-550TR-E
SL-550TR-IPI-E
SL-550TR-E
SL-750TR-IPI-E
SL-950TR-IPI-E
90 Elbow *
2 ft.
610 mm
2 ft.
610 mm
1 ft.
305 mm
1/2 ft.*
152 mm
2 ft.
610 mm
2 ft.
610 mm
2 ft.
610 mm
1-1/2 ft.* 457 mm
3 ft.
914 mm
3 ft.
914 mm
3 ft.
914 mm
2-1/2 ft.* 762 mm
5 ft.
1.5 m
5 ft.
1.5 m
5 ft.
1.5 m
3-1/2 ft.
1.1 m
7 ft.
2.1 m
7 ft.
2.1 m
7 ft.
2.1 m
4-1/2 ft.
1.4 m
14 ft.
4.3 m
14 ft.
4.3 m
14 ft.
4.3 m
H MAX. =14 ft. (4.3 m)
V + H MAX. = 40 ft. (12.2 m)
* See warning below
Note
: Use SLP Series
components only.
Note
: There MUST be a 25%
reduction in total H when using
fl
ex vent except when using the
simple up and out installation.
See Figure 4.6.
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps on top vented
fi
replaces, a one
foot minimum vertical vent section is required before
installing
fi
rst elbow.
WARNING *
• When using DVP-TB1 termination cap on top vented
fi
replaces,
a three foot minimum vertical vent section is required before
installing
fi
rst elbow.