background image

Heat & Glo •  SL-750TRS-IPI-D, SL-550TRS-IPI-D, SL-350TRS-C •  InD  •  2065-985  Rev. o • 3/07  

34

Installing Wall Shield Firestops and Horizontal Termination Cap 

(SL Series Pipe ONLY)

Do NOT connect a pipe section to a termination cap without 
using the telescoping 

À

 ue section found on the termination 

cap.

WARNING

NOTE: 

Where required, an exterior wall 

À

 ashing is 

available.

When penetrating a brick wall, a brick extension kit 
is available for framing the brick.

Installing the Horizontal Termination Cap

Vent termination must not be recessed in the wall. Siding 
may be brought to the edge of the cap base. 

Flash and seal as appropriate for siding material at out 
side edges of cap.

When installing a horizontal termination cap, follow the cap 
location guidelines as prescribed by current 

ANSI Z223.1 

and 

CAN/CGA-B149

 installation codes.

Burn  Risk

•  Local codes may require installation of a 

cap shield to prevent anything or anyone 
from touching the hot cap.

WARNING

Figure 8.14  Hole and Vent Pipe

   Figure 8.15  Heat Shield, Interior & Exterior Firestops

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT

WALL SHIELD

FIRESTOP

(EXTERIOR)

WALLSHIELD

FIRESTOP

(INTERIOR)

HEAT SHIELD

Fire Risk
Exhaust Fumes Risk
Impaired Performance of Appliance

 

WARNING

•  Ensure vent components are locked together correctly.
•  Pipe may separate if not properly joined.

•  Position the wall shield 

¿

 restops on both sides of the 

hole previously cut and secure the wall shield 

¿

 restops 

with nails or screws. 

•  The heat shields of the wall shield 

¿

 restops 

MUST BE

 

placed towards the top of the hole.

•  Continue the vent run through the wall shield 

¿

 restops.

WARNING

•  ALWAYS maintain speci

¿

 ed clearances around venting 

and 

¿

 restop systems.

• Install 

¿

 restops as speci

¿

 ed.

Failure to keep insulation or other material away from 
vent pipe may cause 

¿

 re.

VENT PIPE

1 in. (25.4 mm)

10 in.

(254mm)

10 in.

(254mm)

For Horizontal Runs 

- Wall shield 

¿

 restops are 

REQUIRED

 on 

both sides of a combustible wall through which the vent passes.

NOTE: Model SLK-01TRD does not need an exterior 
wall shield 

¿

 restop on an exterior combustible wall.

To install wall shield 

¿

 restops for horizontal runs that pass 

through either interior or exterior walls:

Cut a 10 in. x 10 in. (254mm x 254mm) hole for SL-D-
series pipe. The center of the framing hole is one (1) inch 
(25.4mm) above the center of the horizontal vent pipe.

Fire Risk.   
Explosion Risk.
Do NOT pack insulation or other 
combustibles between 

¿

 restops.

Summary of Contents for SL-350TRS-C

Page 1: ...e room as appliance Alert children and adults to hazards of high temperatures Do NOT operate with protective barriers open or removed Keep clothing furniture draperies and other combustibles away Glass and other surfaces are hot during operation and cool down Keep children away Owner s Manual Installation and Operation DO NOT DISCARD THIS MANUAL CAUTION This appliance may be installed as an OEM in...

Page 2: ...ce you ll want to read and carefully follow all of the instructions contained in this Owner s Manual Pay special attention to all Cautions and Warnings This Owner s Manual should be retained for future reference We suggest that you keep it with your other important documents and product manuals The information contained in this Owner s Manual unless noted otherwise applies to all models and gas co...

Page 3: ...iance 28 Section 8 Installing Vent Pipe A Assembly of Vent Sections for DVP Pipes 29 B Disassembly of Vent Sections 31 C Installing Heat Shield and Horizontal Termination Cap 33 D Installing Roof Flashing and Vertical Termination Cap 35 Section 9 Gas Information A Fuel Conversions 37 B Gas Pressures 37 C Gas Connection 37 Section 10 Electrical Information A Recommendation for Wire 39 B Connecting ...

Page 4: ...t an elevation above 2000 feet it may be necessary to decrease the input rating by changing the existing burner ori ce to a smaller size Input rate should be reduced by 4 for each 1000 feet above a 2000 foot elevation in the U S A or 10 for elevations between 2000 and 4500 feet in Canada If the heating value of the gas has been reduced these rules do not apply To identify the proper ori ce size ch...

Page 5: ...ll read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5 08 2 a...

Page 6: ...d components from the packaging The vent system components and trim doors are shipped in separate packages The gas logs may be packaged separately and must be eld installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the in stallation Follow these instructions carefully dur ing the installation to ensure m...

Page 7: ...iance it is important to consider the required clearances to walls see Figure 3 1 Figure 3 1 Appliance Locations NOTE For actual appliance dimensions refer to Sec tion 16 In addition to these framing dimensions also reference the following sections Clearances and Mantel Projections Section 3 C and 3 D Vent Clearances and Framing Section 6 A B C D E F G H I SL 750TRS IPI D Inches 45 42 63 3 4 See S...

Page 8: ...ess To further prevent drafts the wall shield and ceiling restops should be caulked with high temperature caulk to seal gaps Gas line holes and other openings should be caulked with C Clearances Figure 3 2 Clearances to Combustibles Fire Risk Odor Risk Install appliance on hard metal or wood surfaces extending full width and depth of appliance Do NOT install appliance directly on carpeting vinyl t...

Page 9: ...ances to Mantels or other Combustibles above Appliance Figure 3 4 Clearances to Mantel Legs or Wall Projections Acceptable on both sides of opening 2 4 5 6 7 8 9 2 3 4 5 12 11 10 9 8 7 6 TOP FRONT EDGE OF FIREPLACE 3 11 12 10 31 CEILING 1 1 If A minimum is ____ then B maximum is_____ A Inches 3 4 5 6 7 8 Millimeters 76 102 127 152 178 203 B Inches 1 2 3 4 5 f Millimeters 25 51 76 102 127 f ...

Page 10: ...0 Figure 4 1 Figure 4 2 Minimum Height from Roof to Lowest Discharge Opening Termination Locations 4 Measure horizontal clearances from this surface Measure vertical clearances from this surface Figure 4 3 Multiple Vertical Termination Figure 4 2 speci es minimum vent heights for various pitched roofs See Figure 4 4 for speci c clearances 3 foot minimum in snow regions HORIZONTAL OVERHANG VERTICAL...

Page 11: ...iveway deck porch veranda or balcony use of a listed cap shield is suggested See vents components page NOTE 2 Termination in an alcove space spaces open only on one side and with an overhang are permitted with the dimensions speci ed for vinyl or non vinyl siding and sof ts 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap must...

Page 12: ...nches vertical run A length of straight pipe is allowed between two 450 elbows see Figure 5 1 Figure 5 1 A Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams C Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards 1 Pipe measurements are shown using the effective length of pipe see Figu...

Page 13: ...xceeding 4 feet with no more than inch sag between supports A support is required at each change in venting direction and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 5 3 requires only enough support to maintain the necessary clearance to combustibles However the vent attachment point and the restop location are c...

Page 14: ... D 90 Elbow 1 5 ft 457 mm 1 ft 305 mm 0 5 ft 152 mm 2 ft 610 mm 2 ft 610 mm 1 5 ft 457 mm 3 ft 914 mm 3 ft 914 mm 2 5 ft 762 mm 5 ft 1 5 m 5 ft 1 5 m 3 5 ft 1 1 m 7 ft 2 1 m 7 ft 2 1 m 4 5 ft 1 4 m 15 ft 4 6 m 15 ft 4 6 m H Maximum 15 ft 4 6 m V H Maximum 40 ft 12 2 m H1 V1 Note Use SL D Series components only NOTE There MUST be a 25 reduction in total H when using Àex vent except when using the s...

Page 15: ...inimum H1 Maximum SL 350TRS SL 550TRS D SL 750TRS D 90 Elbow NOT ALLOWED 0 5 ft 152 mm 1 ft 305 mm 1 5 ft 457 mm 2 ft 610 mm 2 5 ft 762 mm 4 ft 1 2 m 3 5 ft 1 1 m 6 ft 1 8 m 4 5 ft 1 4 m 14 ft 4 3 m H H1 Maximum 14 ft 4 3 m V H H1 Maximum 40 ft 12 2 m Propane V Minimum H1 Maximum 90 Elbow Not Allowed 1 ft 305 mm 1 ft 305 mm 1 5 ft 457 mm 2 ft 610 mm 2 5 ft 762 mm 4 ft 1 2 m 3 5 ft 1 1 m 6 ft 1 8 m...

Page 16: ... m 10 ft 3 0 m 5 ft 1 5 m 10 ft 3 0 m 3 5 ft 1 1 m 7 ft 2 1 m 14 ft 4 3 m 7 ft 2 1 m 14 ft 4 3 m 4 5 ft 1 4 m 14 ft 4 3 m 14 ft 4 3 m 14 ft 4 3 m 14 ft 4 3 m V1 H1 V2 H2 Maximum 40 ft 12 2 m Note Use SL D Series components only NOTE There MUST be a 25 reduction in total H when using Àex vent except when using the simple up and out installation see Figure 5 3 Natural Gas Propane V1 Minimum ALL MODE...

Page 17: ...et in the rebox see Figure 5 8 2 Center the exhaust opening in the open end of the bafÀe and secure through the slots on the bafÀe with the 2 1 4 in self tapping screws provided BafÀes are recommended for these vertically terminated products which have excessive draft BafÀes compensate for high draft restore visual Àame height and limit exces sive cooling resulting from too much secondary air Refe...

Page 18: ...1 2 m 3 ft 914 m 6 ft 1 8 m 4 ft 1 2 m 8 ft 2 4 m 5 ft 1 5 m 15 ft 4 6 m H Maximum 15 ft 4 6 m V1 V2 HMaximum 40 ft 12 2 m V1 Minimum H1 Maximum H1 Maximum V2 V1 V2 Minimum SL 350TRS SL 550TRS D SL 750TRS D 90 Elbow 1 5 ft 457 mm 1 ft 305 mm 5 ft 152 mm 2 ft 610 mm 2 ft 610 mm 1 ft 305 mm 2 5 ft 762 mm 2 5 ft 762 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 3 ft 914 m 6 ft 1 8 m 6 ft 1 8 m 4 ft 1 2 m 8 ft...

Page 19: ...t 1 4 m 14 ft 4 3 m HMaximum 14 ft 4 3m No speci c restrictions on this value EXCEPT V1 V2 H1 H2 CANNOT exceed 40 ft 12 2 m Note Use SL D Series components only NOTE There MUST be a 25 reduction in total H when using Àex vent except when using the simple up and out installation see Figure 5 3 ALL MODELS V1 H1 H2 Maximum V2 V1 V2 Minimum 90 Elbow NOTALLOWED 5 ft 152 mm 0 ft 0 mm 1 5 ft 457 mm 2 ft ...

Page 20: ...tion in total H when using Àex vent except when using the simple up and out installation see Figure 5 3 Note Use SL D Series components only V1 H1 V3 V2 H2 2 Top Vent Vertical Termination continued Four 90 Elbows Figure 5 17 V1 H1 V2 H2 V3 1 5 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 5 ft 1 0 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m Natural Gas and Propane NOTE There MUST be a 25 reduction in tot...

Page 21: ... V1 Minimum H2 H1 H2 Maximum 1 5 ft 457 mm Back to Back Elbows 1 5 ft 457 mm 2 5 ft 762 mm 3 5 ft 1 1 m 1 ft 305 mm 3 ft 914 mm 6 5 ft 2 0 m 5 5 ft 1 7 m 2 ft 610 mm 5 ft 1 5 m 10 5 ft 3 2 m 7 5 ft 2 3 m 3 ft 914 mm 6 5 ft 2 1 m 14 ft 4 3 m H Maximum 7 5 ft 2 3 m H1 H2 Maximum 14 ft 4 3 m V1 H1 H2 40 ft 12 2 m Figure 5 11 Use two 90 elbows for corner installations The use of two 90 elbows in a cor...

Page 22: ... 1 1 m 1 ft 305 mm 2 ft 610 mm 5 5 ft 1 7 m 5 5 ft 1 7 m 2 ft 610 mm 4 ft 1 2 m 9 5 ft 2 9 m 7 5 ft 2 3 m 3 ft 914 mm 6 ft 1 8 m 13 5 ft 4 1 m H1 Maximum 7 5 ft 2 3 m H1 H2 H3 Maximum 13 5 ft 4 1m V1 H1 H3 40 ft 12 2m Note Use DVP Series components only V1 H1 One Elbow V1 Minimum H1 Maximum Elbow Only 1 5 ft 457 mm 1 ft 305 mm 3 5 ft 1 1 m 2 ft 610 mm 5 5 ft 1 7 m 3 ft 914 mm 7 5 ft 2 3 m H Maximu...

Page 23: ...914 mm 6 5 ft 2 0 m 5 5ft 1 2 m 2 ft 610 mm 5 ft 1 5 m 10 5 ft 3 2 m 7 5 ft 2 3 m 3 ft 914 mm 7 ft 2 1 m 14 5 ft 4 4 m H Maximum 7 5 ft 2 3 m V1 V2 H1 H2 Maximum 40 ft 12 2 m Note Use DVP Series components only 4 Rear Vent Vertical Termination continued V1 H2 V 2 H1 H1 H2 Maximum V1 Minimum 5 ft 152 mm Back to Back Elbows 2 5 ft 762 mm 1 ft 305 mm 4 5 ft 1 4 m 2 ft 610 mm 6 5 ft 2 0 m 3 ft 914 mm ...

Page 24: ...tration Framing Figure 6 1 Pipe Clearances 1 in CLEARANCE AROUND VERTICAL SECTIONS 3 in TOP CLEARANCE 1 in SIDE AND BOTTOM CLEARANCE Figure 6 3 Exterior Wall Hole Shows center of vent framing hole for top or rear venting The center of the hole is one 1 inch 25 4mm above the center of the horizontal vent pipe Figure 6 2 Horizontal Venting Clearances to Combustible Materials WALL HEAT SHIELD HEAT SH...

Page 25: ...RNING Fire Hazard Keep loose materials or blown insulation from touching the vent pipe Installing Attic Shield Note An additional ceiling restop is not required if attic shield is used Frame opening for attic shield Attic shield may be installed above or below ceiling see Figure 6 5 Secure with three fasteners on each side Fold tabs at top of attic shield in toward vent pipe Tabs must keep vent pi...

Page 26: ...loves and safety glasses dur ing installation Figure 7 4 Remove the seal cap Figure 7 5 Remove the insulation basket and white insu lation from the center vent pipe Figure 7 1 For top vent remove the two screws holding the elbow heat shield in place Use this heat shield over the rst elbow if applicable For rear vent skip this step Figure 7 6 Remove the insulation from the outer vent pipe For rear ...

Page 27: ...ap has been re moved it CANNOT be reattached Figure 7 10 Attach the rst vent section it will snap into place Slide the insulation gasket onto the vent section up against the appliance and over the tabs Figure 7 7 To attach the rst section of vent pipe make sure to use the berglass gasket in the manual bag to seal between the rst vent component and the outer replace wrap Use 2 self tapping screws t...

Page 28: ...ut nailing tabs on each side Keep nailing tabs Àush with the framing Secure the appliance to the framing by using nails or screws through the nailing tabs Figure 7 11 Proper Positioning Leveling and Securing of a Appliance WARNING WARNING Fire Risk ALWAYS maintain speci ed clearances around the appliance Do NOT notch into the framing around the appliance spacers Failure to keep insulation framing ...

Page 29: ...on the appliance Push the pipe section into the appliance collar until all the lances see Figure 8 1 have snapped in place Tug slightly on the section to con rm it has completely locked into place Figure 8 1 Lances Figure 8 2 A B Figure 8 3 Figure 8 4 Seams Note Make sure that the seams are not aligned to prevent unintentional disconnection INCORRECT CORRECT Once both inner and outer Àues are star...

Page 30: ...p section is too long the inner and outer Àues of the slip section can be cut to the desired length Assembling Minimum Installations MI Sections MI sections are non unitized so that they can be cut to a certain length Cut these sections to length from the non expanded end see Figure 8 5 They can then be attached by rst connecting the expanded end of the MI inner Àue with the inner pipe from the ad...

Page 31: ...mber s strap Figure 8 8 Securing Vertical Pipe Sections To disassemble any two pieces of pipe rotate either section see Figure 8 10 so that the seams on both pipe sections are aligned see Figure 8 11 They can then be carefully pulled apart Figure 8 11 Align and Disassemble Vent Sections Figure 8 10 Rotate Seams for Disassembly Figure 8 9 Securing Horizontal Pipe Sections Fire Risk Explosion Risk C...

Page 32: ...aming members Attach the First Vent Component to Starting Collars To attach the rst vent component to the starting collars of the appliance Lock the vent components into place by sliding the concentric pipe sections with four 4 equally spaced in terior beads into the appliance collar or previously installed component end with four 4 equally spaced indented sec tions When the internal beads of each...

Page 33: ...g on the extended heat shield should rest on the top of the vent pipe section to properly space it from the pipe section see Figure 8 12 Installing the Horizontal Termination Cap Vent termination must not be recessed in the wall Siding may be brought to the edge of the cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap fo...

Page 34: ... SHIELD FIRESTOP EXTERIOR WALLSHIELD FIRESTOP INTERIOR HEAT SHIELD Fire Risk Exhaust Fumes Risk Impaired Performance of Appliance WARNING Ensure vent components are locked together correctly Pipe may separate if not properly joined Position the wall shield restops on both sides of the hole previously cut and secure the wall shield restops with nails or screws The heat shields of the wall shield re...

Page 35: ...ough the pilot holes in the outer collar of the cap into the outer Àue of the pipe see Figure 8 17 Roof Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 Figur...

Page 36: ...rap the storm collar around the exposed pipe section and align brackets Insert a bolt provided through the brackets and tighten nut to complete storm collar assembly see Figure 8 20 Slide the assembled storm collar down the pipe section until it rests on the roof Àashing Caulk around the top of the storm collar see Figure 8 17 CAUTION Sharp Edges Wear protective gloves and safety glasses dur ing i...

Page 37: ...ide of the appliance provided the hole in the outer wrap does NOT exceed 2 1 2 inches in diameter and does not penetrate the rebox NOTE A listed and Commonwealth of Massachusetts ap proved 1 2 inch 13mm T handle manual shut off valve and Àexible gas connector are connected to the 1 2 inch 13mm control valve inlet If substituting for these components please consult local codes for compliance Pressu...

Page 38: ...500 feet in Canada check with local authorities Ensure that gas line does not come in contact with outer wrap of appliance Follow local codes Incoming gas line should be piped into the valve com partment and connected to the 1 2 inch connection on the manual shutoff valve CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk Check all ttings and connections Do not use open Àame After the ...

Page 39: ...ollow parameters for locating thermostat see individ ual thermostat instructions to ensure proper operation of appliance C Standing Pilot Ignition System Wiring CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Shock hazard Replace damaged wire with type 105O C rated wire Wire must...

Page 40: ...k and a 3 voltAC transformer which requires the installation of the supplied junction box It is highly recommended that the junction box be installed at this time to avoid reconstruction The battery pack requires two D cell batteries not included CAUTION Battery polarity must be correct or module damage will occur CAUTION Label all wires prior to disconnection when servicing controls Wiring errors...

Page 41: ...tment Feed the necessary length of wire through the connector Make all necessary wire connections to the junction box receptacle and reassemble the junction box receptacle to the outer shell NOTE Do NOT wire 110VAC to wall switch F Wall Switch Installation for Fan Optional If the box is being wired to a wall mounted switch for use with a fan See Figure 10 4 The power supply for the appliance must ...

Page 42: ...r other Combustibles above Appliance NOTE There are 3 metal tabs holding the non combustible board in place for shipping These tabs are to be cut off or bent back before nishing around the appliance front Fire Risk Do NOT obstruct air inlet or outlet grilles Do NOT modify grilles Modifying or covering grilles could cause temperature rise and re hazard WARNING Finishing materials must not interfere...

Page 43: ... problems Place lava rock on base pan on both sides of the burner Do NOT place on burner top Save the remaining ember materials for use during appli ance servicing The embers provided should be enough for 3 to 5 applications Appliance Setup 12 A Remove Shipping Materials Remove shipping materials from inside or underneath the rebox B Clean the Appliance Clean vacuum any sawdust that may have accum...

Page 44: ...e gure 3 REFRACTORY REFRACTORY RETAINER TAB RETAINER TAB Step 4 Install logs according to the install manual Figure 1 Figure 3 Figure 1 Figure 3 Figure 1 Figure 3 CAUTION Refractory is fragile Carefully remove the refractory from the packaging Step 1 Remove the logs from the replace Place the back wall refractory centered against the back of the replace on top of the grate tabs While steadying the...

Page 45: ...g 1 backwards onto the back of the rebox The right side of the log should be Àush with the edge of the third grate bar from the left LOG 2 SRV530 704 Position log 2 on the far right of the burner grate With the burned out portion of the log facing left and the Àat part facing down place the back end of the log against the burner tab and position the forked end of the log straddling the far right g...

Page 46: ...m the left LOG 4 SRV530 705 Position log 4 so that the burned out section of the log is facing the back of the unit Center the left end against the burner tab and place the right end in the indent of log 3 The notch on the bottom of this log should straddle the 2nd grate bar LOG 5 SRV530 703 Position log 5 burned out section facing right so that the bottom is centered and rests up against the 1st ...

Page 47: ...the logs from the packaging 1 1 2 2 STEP 2 LOG 1 SRV2065 704 Place log 1 on left Àat side of the burner assembly Pull the log and slide it to the right until the notches under the log are in the burner grooves STEP 3 LOG 2 SRV2065 703 Place log 2 on the grate bar and push it back against the refractory The pilot should be centered within the large notch on log 2 LOG NOTCHES 1 1 1 1 2 2 3 3 5 5 4 4...

Page 48: ...hown in Figure 1 LOG NOTCHES STEP 5 LOG 4 SRV2065 705 Place log 4 so that the notch is touching the rst grate tine and is laying in the Àat spot of log 2 The right end of log 4 should touch the back refractory panel See Figure 2 STEP 6 LOG 5 SRV2065 701 Place log 5 on log 2 The front left of the log will rest on log 4 Log 5 must be pushed back against refractory See Figure 3 3 3 1 1 2 2 4 4 3 3 2 ...

Page 49: ...e logs from the packaging LOG NOTCHES STEP 2 LOG 1 SRV2066 704 Place log 1 on left Àat side of the burner assembly Pull the log forward and slide it to the right until the notches under the log are in the burner grooves STEP 3 LOG 2 SRV2066 703 Place log 2 on the grate bar and push it back against refractory The pilot should be centered within the large notch on log 2 1 1 2 2 3 3 4 4 5 5 1 1 2 2 1...

Page 50: ...s shown in Figure 1 STEP 5 LOG 4 SRV2066 705 Place log 4 so that the notch is touching the rst grate tine and is laying in the Àat spot of log 2 The right end of log 4 should touch the back refractory panel See Figure 2 STEP 6 LOG 5 SRV2065 701 Place log 5 on log 2 The front left of the log will rest on log 4 Log 5 must be pushed back against refractory See Figure 3 1 1 2 2 3 3 4 4 2 2 1 1 2 2 3 3...

Page 51: ... optional marble and brass trim surround kits as desired Marble brass brick tile or other noncombustible materials can be used to cover up the gap between the sheet rock and the appliance Do not obstruct or modify the air inlet outlet grilles When overlapping on both sides leave enough space so that the bottom grille can be lowered and the trim door removed I Air Shutter Setting This appliance has...

Page 52: ...lied with an integral barrier to prevent direct contact with the xed glass panel Do NOT operate the appliance with the protective barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one Glass door must be in place when appliance is operating Risk of Combustion Fumes Fire Do NOT operate appliance with glass door removed...

Page 53: ...IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building DO NOT CONNECT 110 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Refer to the owner s information manual pro vided with this appliance This appliance needs fresh air for safe operation and must b...

Page 54: ...ion manual pro vided with this appliance This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air If not installed operated and main tained in accordance with the manufac turer s instructions this product could expose you to substances in fuel or fuel combustion which are known to the State of California to cause ca...

Page 55: ... remote control if absent or if appliance will not be used for an extended period of time Property damage possible from elevated temperatures CAUTION Fire Hazard Keep combustible materials gasoline and other Àammable vapors and liquids clear of appliance Do NOT store Àammable materials in WARNING the appliance s vicinity Do NOT use gasoline lantern fuel kerosene charcoal lighter Àuid or similar li...

Page 56: ...t for maximum Àame impingement Ensure that the thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt meter lead wire on the tip of the thermcouple and the other meter lead wire on the thermocouple copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15mV ...

Page 57: ...ion a No LP in tank Check the LP propane tank Re ll the fuel tank b Inner vent pipe leaking exhaust gases back into the system Check venting system for damage Replace repair improperly assembled pipe sections c Glass too loose and air tight packet leaks in corners after usage Replace glass panel assembly d Bad thermopile or thermocouple Replace if necessary e Improper vent cap installation Check f...

Page 58: ...ween 3 2 and 2 8 volts AC b A shorted or loose connection in wir ing con guration or wiring harness Remove and reinstall the wiring harness that plugs into module Verify there is a tight t Verify pilot assembly wiring to module Remove and verify continuity of each wire in wiring harness c Improper wall switch wiring Verify that 110 VAC power is ON to junction box d Module not grounded Verify black...

Page 59: ...timeter with ohms set at lowest range e Faulty module Turn ON OFF rocker switch or wall switch to OFF posi tion Remove ignitor wire I from module Place ON OFF Rocker switch or wall switch in ON position Hold ground wire about 3 16 inch away from I terminal on module If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is ne Inspect pilot assembly for ...

Page 60: ...stion fumes Odors Handle glass assembly with care NOTE Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white lm on glass CAUTION When cleaning glass door Avoid striking scratching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white lm Do NOT clean glass when hot Turn off appliance after 3 4 hours...

Page 61: ...tion Sand and repaint as necessary 2 Replace appliance if rebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for plugged ports corrosion or deterioration Replace burner if necessary 3 Replace ember materials with new dime size and shape pieces Do not block ports or obstruct lighting paths 4 Ch...

Page 62: ...l appliance dimensions Use for reference only For framing dimensions and clearances refer to Section 3 Figure 16 1 Appliance Dimensions SL 750TRS IPI D Location Inches Millimeters L 8 203 M 8 3 4 223 N 16 1 4 414 O 1 2 13 P 30 3 4 781 Q 15 3 8 391 R 15 7 8 403 S 6 5 8 168 T 33 5 8 854 U 2 1 4 57 V 6 153 Location Inches Millimeters A 41 1041 B 36 1 8 918 C 35 5 8 905 D 32 813 E 21 5 8 549 F 34 1 2 ...

Page 63: ...175 I 23 3 8 594 J 32 9 16 827 K 35 1 2 902 Location Inches Millimeters L 8 168 M 8 3 4 222 N 16 1 4 413 O 1 2 13 P 25 3 4 654 Q 12 7 8 327 R 15 7 8 403 S 6 5 8 168 T 30 1 8 765 U 2 1 8 54 V 6 153 Figure 16 2 Appliance Dimensions SL 550TRS IPI D J G H A B C U V K øS M N O R Q P ELECTRICAL ACCESS ø L GAS LINE ACCESS D F E I T Appliance Dimensions Table A Appliance Dimension Diagrams continued ...

Page 64: ...24 1 8 613 E 16 406 F 28 1 8 714 G 3 1 2 90 H 6 7 8 175 I 21 3 8 543 J 30 5 8 777 K 34 1 2 877 Location Inches Millimeters L 8 203 M 8 3 4 223 N 16 1 4 413 O 1 2 13 P 22 3 4 578 Q 11 3 8 289 R 15 7 8 403 S 6 5 8 168 T 29 737 U 2 1 8 54 V 6 153 Appliance Dimensions Table H G J I F E B A C U V O N M R P Q øS K øL ELECTRICAL ACCESS GAS LINE ACCESS D T A Appliance Dimension Diagrams continued ...

Page 65: ...m 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP 10 in 254 mm 24 in 610 mm DVP HVS Vent Support DVP AS Attic Shield DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 276 mm 13 mm Pipe Effective Length Inches Millimeters DVP4 4 102 DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 ...

Page 66: ...ap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield B Vent Components Diagrams continued Figure 16 5 DVP vent components EFFECTIVE LENGTH Term Cap ...

Page 67: ... Multi pak 31 in 787 mm 24 5 8 in 625 mm 13 1 4 in 367 mm RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm DRC RADIUS Cap Shield 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADD Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm ...

Page 68: ...5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW Vertical Termination Cap High wind B Vent Components Diagrams continued Figure 16 7 DVP vent components PVK 80 For use with IPI and DSI appliances only 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 ...

Page 69: ... 3 4 SL 12D 11 3 4 SL 12 17D 11 3 4 to 16 3 4 SL 17 24D 16 3 4 to 23 3 4 SL 24D 23 3 4 SL 36D 35 3 4 SL 48D 47 3 4 SL FLEX 2 24 SL FLEX 3 36 SL FLEX 5 60 SL FLEX 10 120 There must be a 25 reduction in total H when using the snorkel cap except when using the simple up and out installation 6 1 2 in SL SERIES WALL BRACKET Figure 16 8 SL Series Vent Components ...

Page 70: ...this warranty unless expressly authorized and approved by HEARTH HOME TECHNOLOGIES in writing 6 Any damages caused by environmental conditions inadequate ventilation or drafting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other such causes are not covered by this warranty 7 This warranty will be void if a The Product is ...

Page 71: ...____________________________________________________________________ ________________________________________________________________________________ DO NOT DISCARD THIS MANUAL CAUTION Leave this manual with party responsible for use and operation Read understand and follow these instructions for safe installation and operation Important operating and maintenance in structions included This produc...

Reviews: