Heat & Glo • SL-750TRS-IPI-D, SL-550TRS-IPI-D, SL350TRS-C • InD • 2065-985 Rev. o • 3/07
15
H
2
H
1
V
1
Figure 5.5
Two Elbows
Note:
Use SL-D Series
components only.
NOTE
: There MUST be a 25%
reduction in total H when using
À
ex vent except when using the
simple up and out installation
(see Figure 5.3).
V Minimum
H
1
Maximum
SL-350TRS, SL-550TRS-D,
SL-750TRS-D
90° Elbow
NOT ALLOWED
0.5 ft.
152 mm
1 ft.
305 mm
1.5 ft.
457 mm
2 ft.
610 mm
2.5 ft.
762 mm
4 ft.
1.2 m
3.5 ft.
1.1 m
6 ft
1.8 m
4.5 ft.
1.4 m
14 ft.
4.3 m
H + H1 Maximum= 14 ft. (4.3 m)
V + H + H1 Maximum= 40 ft. (12.2 m)
Propane
V Minimum
H
1
Maximum
90° Elbow
Not Allowed
1 ft.
305 mm
1 ft.
305 mm
1.5 ft.
457 mm
2 ft.
610 mm
2.5 ft.
762 mm
4 ft.
1.2 m
3.5 ft.
1.1 m
6 ft.
1.8 m
4.5 ft.
1.4 m
14 ft.
4.2 m
H Maximum= 14 ft. (4.3 m)
V + H Maximum = 40 ft. (12.2 m)
Natural Gas