attempt to complete any part of 
the installation or adjustment of 
this unit unless technically 
qualified to do so.

 

 
Restrictor Plate 

The restrictor plate is used to 
control excess draft if necessary. 
Controlling the draft also changes 
the aesthetics of the flame. The 
restrictor plate has a large range of 
possible settings (See Figure 19). 
The adjustment point is on the left 
side of the firebox (from front). 
 

Restrictor Plate Position

 

The restrictor plate is factory set in 
the fully open position for shipping. 
This ensures proper flames for a 
wide variety of vent configurations 
and efficiency. The restrictor plate 
consists of a rotating flap in front 
of the firebox exhaust port behind 
the cast iron baffle plate. 
Depending on your vent 
configuration, you may need to 
adjust the restrictor plate position 
to reduce draft.  
 

Restrictor Plate Adjustment

 

Loosen the screw and position the 
restrictor plate in the desired 
location. Tighten the screw to lock 
in place.

 

Figure 19 – Restrictor Indicator 

To verify input rate:

 

The approximate input rate of the 
converted Stowe may be checked 
as follows: 

1.

 

Ensure that no other gas 
appliances are in operation. 

2.

 

Place Stowe in operation on 
high, and allow to burn for 15 
minutes. 

3.

 

Using residential gas meter, 
measure the time in seconds 
required for the Stowe to 
consume 1 cubic foot of gas. 

4.

 

The gas consumption of the 
Stowe in BTU per hour may be 
calculated as (3,600 x heating 
value of gas) ÷ seconds to 
consume 1 cubic foot.  Use 
local gas supplier’s heating 
value, or use 2,500 for LP or 
1,012 for NG. 

EXAMPLE: Using LP with a heating 
value of 2,500, and a time of 392 
seconds (6 minutes 32 seconds): 

(3,600 x 2,500) ÷ 392 = 9,000,000 ÷ 
392 = 22,959 BTU per hour 

Note:

 Stowe may operate safely up 

to 105% of its rated input, or 
23,520 BTU per hour.  If Stowe 
input is incorrect, it is necessary to 
adjust the gas supply pressure. 
Supply line/manifold gas line 
pressure adjustments must be 
performed by qualified service 
personnel.  Do not attempt to 
complete any part of the 
installation or adjustment of this 
unit unless technically qualified to 
do so.

 

Summary of Contents for TDS93-56231

Page 1: ...ary to derate the Stowe 8323 at elevations above 2000 feet Table Settings and Specifications Specification NG LP INPUT RATING Btu hr 0 2000 ft 22 400 22 400 INPUT RATING Btu hr 2000 4500 ft 21000 2240...

Page 2: ...paint Figure 1 Orifices Marking Locations Convertible regulators are designed to deliver either of two fixed outlet pressures for Natural Gas NG or LP Gas To change from one gas to the other turn the...

Page 3: ...et two hex head screws front R and L corners and swing the front of the valve assembly down 7 With 5 32 hex wrench loosen and remove the existing low pressure NG screw by turning counter clockwise unt...

Page 4: ...igure 6 NG Low Pressure Screw Removal Figure 7 Press LP Orifice into Valve to Compress O ring Figure 8 Tighten LP Low Pressure Orifice To Switch Pilot to LP Operation Refer to Figures 9 12 The pilot a...

Page 5: ...ot Tower by pushing on the upturned edge by the NAT lettering until the upturned edge is flush with the Pilot Tower surface You will see the NG LP Pilot Gate protruding from the back edge of the Pilot...

Page 6: ...ition Checking for leaks To perform initial gas leak test 1 Check carefully for gas leaks immediately after the conversion has been performed Do this before attempting to operate the appliance or othe...

Page 7: ...Continuing beeps confirm that ignition is in progress Once pilot ignition is confirmed valve will open to allow gas flow to main burner After main burner ignition the handset will automatically go in...

Page 8: ...ent view the flame pattern with the valve output at its highest setting Allow unit to operate for 10 minutes to allow the flame pattern to stabilize then observe flame pattern and adjust as necessary...

Page 9: ...tment CAUTION ADJUSTING ROD IS HOT WARNING ONLY A QUALIFIED GAS TECHNICIAN SHOULD MAKE ADJUSTMENTS TO THE AIR SHUTTER The air shutter is adjustable while the stove is burning Loosen the set screw on t...

Page 10: ...the screw to lock in place Figure 19 Restrictor Indicator To verify input rate The approximate input rate of the converted Stowe may be checked as follows 1 Ensure that no other gas appliances are in...

Page 11: ...e main burner in operation on high 3 Turn pressure regulator adjustment screw see Figure 15 to set required burner pressure Pressure is increased by turning clockwise pressure regulator models or decr...

Page 12: ...at low pressure orifice is properly seated in valve Conversion label placement When fuel conversion is complete fill out and apply included marking labels to the appliance as shown Fill out all fields...

Reviews: