12
1. Connect a manometer to the
valve outlet pressure tap.
Pressure tap is opened by
turning the screw counter-
clockwise (see Figure 3).
2. Light stove and place main
burner in operation on low.
3. For LP, the low rate is set by
installing a calibrated low
pressure orifice, included with
this kit. Once the Stowe has
been converted to LP with the
fixed rate low flow orifice, the
low rate is not adjustable. If
LP minimum pressure is not
within ±0.1 i.w.c. of specified
minimum pressure, ensure
that low pressure orifice is
properly seated in valve.
Conversion label placement:
When fuel conversion is complete,
fill out and apply included marking
labels to the appliance as shown.
Fill out all fields on large rating
plate conversion label 3300-589
(number in lower right corner) and
place over field provided on stove
lighting instruction tag (see Figure
20).
Figure 21 – Ash Lip Conversion
Label Location
Figure 20 – Rating Plate
Conversion Label Location
Fill out all fields on smaller ash lip
conversion label 3300-593 and
place on inside surface of ash lip
(see Figure 21).
Place small valve warning label
3300-585 on or near valve body
(see Figure 22).
Figure 22 – Valve Warning Label
Location