HearthStone Quality Home Heating Products Inc
Champlain
Model #8300
22
H
ORIZONTAL
T
ERMINATION
V
ENTING
C
ONFIGURATIONS
-
A minimum of 2’ rise is required (with or without offsets)
-
30’ maximum system height (with or without offsets – note shutter setting)
-
10’ maximum offset (refer to Figures 8, 9, & 12 – note shutter setting)
-
maximum rise to run = 1 to 5 (refer to Figures 8 & 9 – note shutter setting)
-
The termination must fall within the area outlined by the shaded area shown in
Figure 8 and the Chart in Figure 9 should be considered as well.
-
Use a vinyl siding stand off when installing against a vinyl siding.
-
Horizontal sections require a ¼” rise every 12” of horizontal run.
-
For each 90º elbow after the second, remove 5’ from horizontal run.
-
At minimum vertical rise, maximum horizontal run is 10’
-
Use with snorkel termination 10’ maximum horizontal run.
Figure 12. Horizontal Termination
Approved DV Venting Configuration for
Horizontal Termination with:
1. (1) 90º Elbow & (1) 45º Elbow
•
90º Elbow
•
45º Elbow
•
Straight Pipe
2. (1) 90º Elbow
•
90º Elbow
•
Straight Pipe
3. (2) 90º Elbow
•
(2) 90º Elbows
•
Straight Pipe
4. Snorkel
•
Snorkel (3 foot)
•
Straight Pipe